background image

 

                                   

3 of 11 

 

 

 

Integrity                       Excellence                       Teamwork                       Innovation 

Filtration Media Loading

 

 

Media filtration systems supplied by Blake Water Solutions are shipped without the media preloaded. 

Aeration/Oxidation filtration media selected for Iron, Manganese, Hydrogen Sulfide removal or (other conditions your equipment 

supplier has identified) are dependent on many factors and are carefully selected and applied based on reported water conditions at 

the time of testing. Variables such as pH changes, changes in mineral concentration, unreported water contaminants as well as 

increased flow and usage rates may affect the performance of this system. 

 

1. With the bypass valve in the bypass position disconnect the control valve from the bypass valve and remove the control valve 

from the mineral tank. Care should be exercised to avoid damage to the distribution tube and screen while loading the selected 

media for the application. 

2. Plug the open end of the riser tube to ensure that no filtration media or gravel falls down into the riser tube.  The riser tube should 

be firmly seated and centered in the tank and should be flush with the top of the tank opening (or tank top bushing if required). 

Underbed support gravel if required should be pre-rinsed to remove fines and grit which could clog the screens and then carefully 
loaded covering the distributor basket. Adding a sufficient amount of water (approximately 6” above the distributor) to the vessel 
prior to adding the gravel will minimize the potential for damage and help to level the support bed. 

3. Next load the required amount of media selected for the application. Again, adding additional water to the vessel will assist in 

loading by minimizing dust and optimize leveling. 

4. Unplug the riser tube, carefully position the valve over it and turn the valve into the threads in the fiberglass tank, tightening 

securely into tank and secure to the existing piping bypass. 

Note: Ensure that the internal O-ring in the valve fits securely over the riser tube.

   

Silicone lubricant should be applied to the O-ring to ease installation of the riser tube. 

DO NOT use petroleum based lubricants as they will cause swelling of O-ring seals. 

The bypass valve supplied with the equipment should still be in the bypass position and the filter tank can now be completely filled 

with water by depressing REGEN on the control valve to initiate backwash and slowly opening the bypass to fill the tank with water 

and purge any air. Once filled and purged of air the bypass should be returned to the bypass position. The valve controller can now 

be cycled back to the service position. This step will allow the media to absorb water and will reduce the chance of backwashing 

media out of the tank during the initial backwash on final start-up.  Once the media is sufficiently hydrated the system regeneration 

cycle should be initiated and the bypass valve slowly opened as the valve cycles into backwash. The backwash cycle should 

continue unit the water runs clear. The valve can now be cycled to service and the bypass valve opened allowing treated water to 

enter the household piping. 

Caution: most Medias including, but not limited to, Carbon, Filter Ag, and Chemsorb require hydration prior to being put 

into service as they are shipped dry. A minimum of 4 hours presoak, but preferably overnight saturation is recommended to 

condition any newly installed media for service. 

 
 
 

Содержание AIO

Страница 1: ...XOWSEEAIO REV 06 2018 OPERATION AND INSTRUCTION MANUAL SPECIALIST SERIES AERATION FILTER SYSTEM For Residential Filter Systems with Clack WS1EE 4 Button AIO Control Valve ...

Страница 2: ...ation Requirements Page 1 Installation Commissioning Page 2 Filtration Media Loading Page 3 Backwash Regeneration Cycles Page 4 Bypass Valve Page 5 Controller Page 6 Programming Setting Time of Day Installer Settings Page 8 Programming System Setup Page 9 Replacement Parts Page 10 Filtration Media Overview Page 11 ...

Страница 3: ... use in a single tank valve system configuration reducing both installation and maintenance costs yet delivering years of trouble free service No chemical additives or air compressors are required for operation or regeneration with the Clack WS1EE AIO s unique and advanced design Do not install this system if methane is present in the water DANGEROUS DEADLY GAS CAN ACCUMULATE This system is not in...

Страница 4: ...lowly slide the deflector over the distributor tube down about 1 When threading the AIO valve to the tank the bottom of the threads will slide the deflector down As shown below 7 Lubricate the distributor O ring and tank O ring Place the main control valve on tank Note Only use silicone lubricant 8 Solder joints near the inlet outlet drain must be done prior to making thoses connections Leave at l...

Страница 5: ... application Again adding additional water to the vessel will assist in loading by minimizing dust and optimize leveling 4 Unplug the riser tube carefully position the valve over it and turn the valve into the threads in the fiberglass tank tightening securely into tank and secure to the existing piping bypass Note Ensure that the internal O ring in the valve fits securely over the riser tube Sili...

Страница 6: ... were trapped during service to be dislodged from the media and flushed to drain The media is also de compacted and readied for the the air injection step After the 10 minutes of flow to drain the valve piston will drive to the draw position The Backwash step can be lengthened if necessary but it should never be shortened 2 Air Recharge 40 minutes During this cycle water flows to drain creating a ...

Страница 7: ...ed during the backwash regeneration cycle 2 Bypass Operation The inlet and outlet handles point to the center of the bypass the control valve is isolated from the water pressure contained in the plumbing system Untreated water is supplied to the plumbing system 3 Diagnostic Mode The inlet handle points in the direction of flow and the outlet handle points to the center of bypass valve system water...

Страница 8: ...ys User 1 Displays gallons until backwash not shown if set for time clock operation User 2 Displays number of days until next backwash User 3 Displays present flow rate in gallons per minute always reads 0 because no meter is installed User 4 Displays total volume in gallons since last reset always reads 0 because no meter is installed User 5 Shows current time ...

Страница 9: ...volatile memory Control Operation during a Power Failure The control valve includes a coin cell backup battery In the event of power failure the control shifts into power saving mode and stops monitoring water usage The display and motor shut down but the control continues to keep track of the time for approximately 8 hours System configuration settings are stored indefinitely in non volatile memo...

Страница 10: ...n 8 hours and the time of day flashes this indicates that the battery is depleted The time of day should be reset and the non rechargeable battery should be replaced The battery is a 3 Volt Lithium Coin Cell type 2032 Time of day should be reset when Daylight Savings Time starts ends Installer Settings To enter Installer Display press NEXT and simultaneously for about 5 seconds and release Day Ove...

Страница 11: ...to previous step Step 7S Select the time for the third cycle using or Default oFF DO NOT CHANGE Press NEXT to go to Step 8S Press REGEN to return to previous step Step 8S Select the time for the fourth cycle using or Default oFF DO NOT EXCEED 1 MINUTE Press NEXT to go to Step 9S Press REGEN to return to previous step Step 9S Select the pounds for the fifth cycle using or Default oFF DO NOT CHANGE ...

Страница 12: ...STON OV32 INLET CHECK VALVE OV15HT AIR DRAW CHECK VALVE H6061 AIR DRAW SCREEN KTSCREEN SCREEN W TUBE K74V4144AIO AIR DRAW ASSY COMPLETE AIOGROM GROMMET D7147 UPPER DEFLECTOR K74V30101F INJECTOR F BLUE RKWS1AIO AERATION MAINTANANCE KIT Includes Blue Injector Pistons Stack Assy Stack Puller Tool and Service Wrench VARIES DRAIN LINE FLOW CONTROL Injector may vary on larger tanks ...

Страница 13: ...ides superior filtration down to 5 micron at high flows up to 12 18 gpm ft Advantages include the removal of a wide range of colloidal and soluble inorganic contaminants by surface sorption chemical binding charge neutralization coagulation reactions and or ion exchange phenomena Certified to NSF ANSI Standard 61 Corosex Color brownish white Density 75 lbs per CF Mesh size 6 x 16 Corosex is a spec...

Страница 14: ...NOTES ...

Страница 15: ...NOTES ...

Страница 16: ...91 7867 MAINE BLAKE EQUIPMENT HERMON 1194 Odlin Road Hermon ME 04401 Phone 800 450 6822 BLAKE EQUIPMENT PORTLAND 70 Ingersoll Drive Unit 1 Portland ME 04103 Phone 800 308 2213 The Blake Group is a growing family of companies dedicated to providing our valued customers with superior products and technologies in commercial industrial and residential markets compliant with industry standards and meet...

Отзывы: