Inputting Motor, Elevator Installation and Speed & Curves parameters 

 

How? 

Open the Main Menu by touching on 

.  Select  Motor  Parameters,  Elevator  Installations  and 

Speed & Curves menus to input requested parameters respectively.

  

 

 

 

 
 

 
 
 
 
 

8) 

Perform Learning 

(oil temperature >22°C) 

How?

 

Open the Main Menu and select 

OPERATION MODE

 

Before performing learning make sure that oil temperature is above 22°C (72°F). Let the elevator make a few 
normal travels at nominal speed. If motor is running but the lift is not moving change the direction of rotation 
of the motor by changing the parameter 

b1-14

 (eg. If b1-14 is 1 then set it to 0 or vice versa).  

During learning, software  will start and stop  the  lift several times.  After a few short travels,  lift will stop and 
software  will  show  “

Learning  completed

”  (a  check  sign  in  the  box).  It  will  switch  to 

Normal  operation

 

automatically.  
When the run is interrupted, mode will return to 

“Normal operation” and the app shows “

learning drive NOT 

completed successfully

”.

 

 
 
 

 
 

 
 
 
 

9) 

If necessary, perform fine tuning 

 

How?

  After  making  some  travels,  open 

TRAVELS

  menu  and  click  on  a  travel.  Check  the  total  travel  and 

levelling times. If necessary, change the deceleration and acceleration durations from 

SPEED & CURVES

 menu. 

 

 
Note

The  terminals

  HC,  H1,  H2 

(on  the  inverter)  must  be  linked  otherwise,  the  motor  will  not  start  unless  Safe 

Disable function is used.

 

  

DELAY DEENERGIZING MOTOR CONTACTORS ABOUT 1 SECOND AFTER THE CAR REACHES THE STOP 
SWITCH.

 