background image

 

701-C00    Page 3/16 

GENERAL INSTALLATION AND OPERATION 

 

NOTICE: 

Blackmer pumps must only be installed in systems 
designed by qualified engineering personnel.  System 
design must conform with all applicable regulations and 
codes and provide warning of all system hazards. 

 
 

WELDED CONNECTIONS 

NOTICE: 

Pumps with welded connections contain three non-
metallic o-ring seals that will be damaged if welding is 
done with these o-rings installed.  

Prior to welding the piping, remove the O-rings from under the 
inlet flange, outlet flange and relief valve cover as indicated in 
Figure 1. 

Reinstall the inlet and outlet flanges. Weld the piping to the 
the inlet and outlet flanges. After the welding is complete, 
reinstall the O-rings.

 

 

Figure 1 

 
 

PRE-INSTALLATION CLEANING 

NOTICE: 

New pumps might contain residual test fluid and/or rust 
inhibitor.  If necessary, flush pump prior to use. 

Foreign matter entering the pump WILL cause extensive 
damage.  The supply tank and intake piping MUST be 
cleaned and flushed prior to pump installation and operation. 

 

LOCATION AND PIPING 

Pump life and performance will be significantly reduced when 
installed in an improperly designed system. Before starting 
the layout and installation of the piping system, review the 
following: 

1.  Locate the pump as near as possible to the source of 

supply to avoid excessive inlet pipe friction. 

2.  The inlet piping and fittings should be at least as large as 

the intake port on the pump. It should slope downward to 
the pump, and should not contain any upward loops. 
Minimize the number of intake line fittings and eliminate 
restrictions such as sharp bends; globe valves, 
unnecessary elbows, and undersized strainers. 

3.  A strainer must be installed in the inlet line to protect the 

pump from foreign matter. The strainer should be located 
at least 24" (0.6m) from the pump, and have a net open 
area of at least four times the area of the intake piping. 
Strainers must be cleaned regularly to avoid pump 
starvation. 

4.  The intake and discharge piping system must be free of 

all leaks. 

5.  Expansion joints, placed at least 36" (0.9m) from the 

pump, will compensate for expansion and contraction of 
the pipes. Contact the flexible connector/hose 
manufacturer for required maintenance/care and design 
assistance in their use. 

6. 

ALL piping and fittings MUST be properly supported to 
prevent any piping loads from being placed on the pump.

 

7.  Check alignment of pipes to pump to avoid strains which 

might later cause misalignment.  See Figure 2.  Unbolt 
flanges or break union joints.  Pipes should not spring 
away or drop down.  After pump has been in operation 
for a week or two, completely recheck alignment. 

 

Figure 2 

8.  Install pressure gauges in the NPT ports provided in the 

pump casing to check pump performance at start up. 

9.  The use of a 1.5” or 2” vapor return line will speed up 

delivery by preventing pressure build up at the receiving 
tank and pressure reduction in the supply tank. 

10.  Keeping the liquefied gas systems full of liquid, even 

when idle, will keep the O-rings from changing shape, 
shrinking or super cooling. Evaporation of liquefied gas 
leaves an abrasive powder on the surface which can 
cause wear to the pump, meter, and seals. 

 

Содержание CRL4B

Страница 1: ...site www blackmer com or by contacting Blackmer Customer Service SAFETY DATA This is a SAFETY ALERT SYMBOL When you see this symbol on the product or in the manual look for one of the following signal...

Страница 2: ...al injury or property damage If pumping hazardous or toxic fluids system must be flushed and decontaminated inside and out prior to performing service or maintenance Hazardous or toxic fluids can caus...

Страница 3: ...ot contain any upward loops Minimize the number of intake line fittings and eliminate restrictions such as sharp bends globe valves unnecessary elbows and undersized strainers 3 A strainer must be ins...

Страница 4: ...tting remove the relief valve cap loosen the locknut and turn the adjusting screw inward or clockwise Replace the valve cap 2 To DECREASE the pressure setting remove the relief valve cap loosen the lo...

Страница 5: ...vailable use a straightedge Turn both shafts by hand checking the reading through one complete revolution Maximum offset should be less than 0005 0 127 mm 2 Angular alignment Insert a feeler gauge bet...

Страница 6: ...b should slide smoothly off the shaft If it is tight on the shaft gently pry it loose with a screwdriver or a small wedge placed in the split part of the flange Refer to Blackmer V Belt Parts List and...

Страница 7: ...orizontal as long as the pump is shimmed to have its shaft parallel in all respects to the PTO shaft 5 The yokes of the universals at both ends of the jack shaft must be parallel and in phase 6 The ma...

Страница 8: ...ation by checking the pump rotation arrows 4 Check the pump speed Pump speed must never exceed the recommended maximum See Technical Data section of this manual 5 Check the pressure gauges to ensure t...

Страница 9: ...ed technicians only Follow the appropriate procedures and warnings as presented in this manual STRAINERS Strainers must be cleaned regularly to avoid pump starvation Schedule will depend upon the appl...

Страница 10: ...aft b Slide the lockwasher 24B off the shaft Inspect the lockwasher for damage and replace as required c Repeat steps a and b on the opposite shaft end 6 Remove the head capscrews 21 and carefully pry...

Страница 11: ...kwashers 71A and 71B The drive tangs of the seal jacket should protrude through the center hole of the disc Figure 9 Disc Relief Hole Location 5 Install a new head O ring 72 in the groove on the insid...

Страница 12: ...ot in the locknut The pump should turn freely when rotated by hand f Tighten the opposite locknut 24A by hand until it is snug against the bearing 24 Then using a spanner wrench tighten the nut the wi...

Страница 13: ...ass Valve set too low 8 Operating without a vapor return line 9 Vanes installed incorrectly see Vane Replacement 10 Liner installed backwards Noise 1 Excessive pressure drop on the pump due to a Under...

Страница 14: ...ompatible with the liquids pumped 2 O rings nicked cut or twisted 3 Shaft at seal area damaged worn or dirty 4 Bearings over greased 5 Excessive cavitation 6 Mechanical seal faces cracked scratched pi...

Страница 15: ...701 C00 Page 15 16 NOTES...

Страница 16: ...701 C00 Page 16 16 1809 Century Avenue Grand Rapids Michigan 49503 U S A 616 241 1611 Fax 616 241 3752 www blackmer com...

Отзывы: