AXES KNX Keypad Panels Manual – V1.1
Page 12 of 23
Button parameters
Each keypad panel button has its own individual parameters.
According to the keypad panel model the correct number of buttons will be available.
All the button groups are disabled by default; each button must be enabled to be configured with the
desired function and parameters from the dropdown list
List of functions
Function
Type
Description
Object
Depth
Switch
ON
Send always the On command
Send ON
1 bit
OFF
Send always the Off command
Send OFF
1 bit
Toggle
Send alternating On/Off (1 bit) command
Toggle
1 bit
Time limited
toggle
Send On/Off command within a delay time
Time limited
toggle
1 bit
Push button Send On command when pressed, send Off command when
button is released or vice versa.
Push button
1 bit
Dimming
Increase /
Decrease
Enable the operations:
Short press: toggle On/Off
Long press: cyclical increase/decrease dimming
Additional long press parameter can be configured
Dimming On/Off
Dimming
1 bit
4 bits
ON /
Increase
Enable the operations:
Short press: toggle On
Dimming On/Off
1 bit