PRESSURE HOLD TEST (CONTINUED)

3.  Use 

[UP/DOWN ARROWS]

 to adjust test duration in 5 minute increments to 

desired setting (Note: Minimum time is pre-set at 5 minutes. Maximum time is 
95 minutes).

4.  Press 

[SET]

 to store 

Test Duration

. Display will advance to 

Pressure Set Screen [FIG.8]

.

hh : mm

Psig 

Pressure Set Screen 

Input Test

Pressure

FIG.7

Psig 

Psig 

APO

Start Vs. Final Pressures

FIG.8

Original Set 

System Pressure 

Value

Final System 

Pressure 

Value

5.  Connect manifold Low and High Side Service hoses to the system to be tested. 

Pressurize the system. 

Regulated

 Nitrogen or Nitrogen/Hydrogen trace gas is 

recommended.

6.  The pressure in the system will be displayed in the UPPER LEFT.
7.  Press 

[SET]

 to start test. Starting test pressure is indicated in upper left display 

[

FIG.7

]. Current system pressure is shown in upper right display. Timer (lower left 

display) decrements and when at zero, a bell will sound indicating test completion 
and 

Start Vs. Final Pressures

 will be displayed [

FIG.8

] to determine if system 

leaks.

VACUUM HOLD TEST

Normally, systems with vacuum levels within 250-500 microns are deemed as having a 

good seal and are ready for charging. As with any recharged system, a good electronic leak 

detector should be used to test for leaks after the charge has been completed. MD50W 

or MD100W manifold series will function as accurate vacrometers when used with the 

MDXVG Remote Vacuum Accessory (page 6)

.

1.  Plug the MDXVG Vacuum Accessory into the upper right side of the manifold [

FIG.9

]. 

2. The 

Vacuum Display Screen

 [

FIG.10

] appears.

MDXVG Vacuum Gauge Accessory Connection

Connection port

FIG.9

Vacuum Display Screen

Vac

mic

FIG.10

www.

.com

[email protected]

1.800.561.8187

Содержание CPS MD100W

Страница 1: ...CPS Link App 2 Valve Series MD50W MD50WHE MD50WVHE 4 Valve Series MD100W MD100WHE MD100WVHE WIRELESS SERIES For use with free BLACKMAX app featuring CPS Link US Patent No 9 043 161 For Android or iOS...

Страница 2: ...nt 26 Appendix E Cleaning Sensor in MDXVG Vacuum Gauge 26 Appendix F Limited Warranty 27 Appendix G Refrigerants Stored in MD50W and MD100W series 27 Appendix H Error Indicator Screens 28 CONTENTS OVE...

Страница 3: ...ENT MANUFACTURER S TEST PROCEDURES WHEN SERVICING THOSE SPECIFIC TYPES OF EQUIPMENT WARNING Remove all hoses with care as they may contain liquid refrigerant under pressure Contact with refrigerant ma...

Страница 4: ...ASS Monitor refrigerant flow 12 VACUUM VALVE MD100 Series Only Controls flow through LEFT MIDDLE 3 8 SAE PORT 13 LOW SIDE VALVE Controls flow to LEFT SIDE SAE Port 14 CENTER PORT MD50W Series Only A S...

Страница 5: ...lass 12 Vacuum Valve 13 Low Side Valve 1 On Off 2 Set 3 Refrigerant 4 Mode 5 Superheat Subcool 21 Connection Points For Thermistor Sensors 18 Swivel Hook 19 Battery Compartment 20 Hose Hangers 15 9V D...

Страница 6: ...T45 Brass Tee Connector Included with MDXVG Kit MDXCP Thermistor Sensor with 6 Ft lead for taking Superheat and Subcool true temperatures on pipes Vacuum Gauge Accessory Kit MDXVG U S Plug 5 Ft Cord U...

Страница 7: ...CKMAX CPS Link icon from your mobile device 5 The application will appear on your mobile device screen in landscape mode 6 Select one BLACKMAX Wireless Digital Manifold to operate 7 Review and adhere...

Страница 8: ...ital Scale Current Refrigerant Home Screen Settings Data Logging Vacuum Hold Presure Hold Working Temperature s CHANGE OR CONFIRM SETTINGS High Side Low Side Touch arrows to toggle between Home Screen...

Страница 9: ...each use especially if manifold has been dropped or pressurized beyond 800 psig 55 Bar BLACKMAX APP SETTINGS SCREEN Select One Change Language Zero Offset Target Superheat Change Units Settings www co...

Страница 10: ...ct a new active refrigerant Note Refrigerant selected will become the default but not affect FAVORITE FIVE Changing FAVORITE FIVE refrigerants permanently must be done using the manifold See page 21 f...

Страница 11: ...ccessory to Digital Manifold initiate vacuum to enable test Note See Appendix E for cleaning the sensor 2 Touch Start or Stop at any time 3 Default duration 5 minutes Max time 100 mins 4 You may navig...

Страница 12: ...which the manifold will record values 3 View maximum time remaining 4 Start Stop logging at any time or let system run until no more Manifold memory All stored files have option of showing Geolocation...

Страница 13: ...elect for general description of any item 1 General 2 Home 3 Pressure Hold 4 Vacuum Hold 5 Data Logging 6 Settings 7 Side Menu Video Watch instructional videos on how to use this app www com informati...

Страница 14: ...t another region 8 The next screen will be the MAIN screen FIG 1 showing default status for the following Battery charge status APO On or Off High and low side working pressures High and low side temp...

Страница 15: ...APO Super Heat Sub Cool Screen Sub Cool Super Heat FIG 3 5 Note In this mode and to prevent errors refrigerant cannot be changed using the REF key Press CLR to return to Main Screen FIG 1 from this vi...

Страница 16: ...eak rates less than 1 oz year In practice there should be no pressure hold detected if the system is deemed leak proof enough to add refrigerant Large leaks should be found before adding refrigerant L...

Страница 17: ...ted in upper left display FIG 7 Current system pressure is shown in upper right display Timer lower left display decrements and when at zero a bell will sound indicating test completion and Start Vs F...

Страница 18: ...Screen FIG 13 8 Use UP DOWN ARROWS to adjust test duration in 5 minutes increments minimum time is pre programmed at 5 minutes A Press SET to store Vacuum Test duration time Vacuum Hold Test Screen FI...

Страница 19: ...played to enable determination of any vacuum loss over a set period of time Inactive Current Vacuum Level Leak test duration FIG 14 D Press CLR to return to Main Screen FIG 1 NOTE If it is required to...

Страница 20: ...PO FIG 16 FIG 17 3 The Initial Refrigerant blinking in upper right should be R 11 and Counter Lower Right should start at 000 4 Use UP DOWN ARROWS to scroll through 93 refrigerants Press and hold eith...

Страница 21: ...exit this menu and go to the next Temperature Units Screen press SET or 8 To return to Main Screen FIG 1 press and hold CLR after step 6 9 If all 5 refrigerants are changed manifold automatically adva...

Страница 22: ...red by pressing SET Menu In either case units become current units and manifold returns to Main Screen FIG 1 Psig mic APO F Units Summary Screen Blinking symbols indicate Pressure Temperature and Vacu...

Страница 23: ...ts L and H 2 Connect hose from to open port on the tee C to Refrigerant Recovery Unit inlet port 2 Connect hose from port 4 to Refrigerant Recovery unit inlet port 3 Start Recovery Unit 3 Open low sid...

Страница 24: ...VacuumLeaktestorHighSideChargingProcedure EVACUATING PROCEDURES CHARGING PROCEDURE LOW SIDE MD50W 2 Valve Manifold FIG 24 MD100W 4 Valve Manifold FIG 25 1 The following instructions are to add charge...

Страница 25: ...indication accuracy 10 microns requires MDXVG accessory SH SC and saturation temperature accuracy 0 5 F 0 3 C Instrument working temperature 4 0 F to 122 F 20 C to 50 C Instrument working RH range 0...

Страница 26: ...ries for the first time turn manifold off and connect one end of charger to Manifold 9V DC plug FIG 26 and the other end to an appropriate wall outlet socket Charge NiMH batteries for 2 hours The Batt...

Страница 27: ...pttorepairBLACKMAXproducts CPShasthesolerighttodetermine ifaclaimisvalidandifcompensationisjustified THEFOREGOINGWARRANTYISINLIEUOFALLOTHEREXPRESSWARRANTIES TOTHEEXTENTALLOWED BY LAW ANY IMPLIED WARRA...

Страница 28: ...thermistor sensor connected to that port is short circuited Replace sensor with CPS model number TMX3C Err Upper Left Display Appears in upper left display when T function is selected and one or both...

Отзывы: