Chapter 3: Installation
Kep nuts
Grounding
lugs
2-hole ground
connector
Figure 3-3. Grounding components.
To properly ground the POTS 2-Wire to Fiber Converter:
1. Obtain one (1) grounding conductor (12 AWG copper wire gauge or larger)
with a two-hole, compression-type, grounding connector.
2. Attach the grounding conductor to the device by placing the two-hole
connector onto the grounding lugs and fasten with lock-washers/lug-nuts (not
included) at the proper torque (per the manufacturer’s specification).
3. Attach the opposite end of the grounding conductor to the common bonding
network (CBN), which is the building’s grounding system.
Grounding
wire
Grounding
lugs
Grounding
connector
Figure 3-4. Grounding the POTS 2-Wire to Fiber Converter.
3.3 Installing the Cable—Standard Configuration
NOTE: Unit B MUST be configured for Standard Configuration (see Section 2.4.1).
3.3.1 Fiber
1. Use fiber cable with male, two-stranded TX to RX connectors installed at both
ends.
2. Connect the fiber cables to Unit A (TE160A-R2, TE162A-R2, or TE164A-R2) as
described: