CHAPTER 3: Installation

4. Attach the Surge Protector’s braided ground strap directly to the

chassis-ground connection point you have located (see Figure 3-3 on

the previous page). The best way to make this connection is to attach

the braided metal strap using a hex nut or screw on your device.

CAUTION!

Surge energy may run both directions on the ground strap. To provide
the best protection, it is essential that the ground strap on the Surge
Protector be connected to the chassis ground of the protected device. Do
not lengthen the Surge Protector’s ground strap or connect it to a ground
other than chassis ground unless instructed to do so by your supplier’s
technical support.

3.2.2 C

ONNECTING THE

PSP 

AT A

B

ARRIER

(W

ALL

, B

UILDING

E

NTRANCE

, E

TC

.)

1. Disconnect the twisted-pair line you want to protect from the wall jack.
2. Install the Primary Surge Protector between the line and the jack. You

will have to run a straight-through-pinned Category 5 patch cable with

modular RJ-45 connectors from the PSP to the jack; we suggest that

you use the cable supplied with the PSP. It doesn’t matter which end of

the PSP is attached to the twisted-pair line and which end is attached to

the patch cable.

3. Find a common or on-equipment electrical ground close to the jack. We

recommend that you use one of the building’s electrical-safety grounds,

such as an electrical panel or subpanel, but you can use a device’s chassis

ground if the chassis ground is connected to the building’s electrical

ground. If there are no grounds connected to the building’s electrical-

safety grounds within nine inches (23 cm) of the jack, contact your

supplier’s technical support to discuss an alternative grounding solution.

4. Connect the braided ground strap directly to the safety ground you

have located. The best way to make this connection is to attach the

braided metal strap to the metal panel using a hex nut or screw.

CAUTION!

Surge energy may run both directions on the ground strap. To provide
the best protection, it is essential that the ground strap on the Surge
Protector be connected to electrical safety ground. Do not lengthen the
Surge Protector’s ground strap or connect it to a ground not tied to safety
ground unless instructed to do so by your supplier’s technical support.

Содержание SP250A

Страница 1: ...nical support 24 hours a day 7 days a week Call 724 746 5500 or fax 724 746 0746 Mail order Black Box Corporation 1000 Park Drive Lawrence PA 15055 1018 Web site www blackbox com E mail info blackbox...

Страница 2: ...ato el ctrico debe ser montado a la pared o al techo s lo como sea recomendado por el fabricante 8 Servicio El usuario no debe intentar dar servicio al equipo el ctrico m s all a lo descrito en las in...

Страница 3: ...er localizada lejos de las lineas de energia 16 El cable de corriente deber ser desconectado del cuando el equipo no sea usado por un largo periodo de tiempo 17 Cuidado debe ser tomado de tal manera q...

Страница 4: ...er Page 1 Specifications 6 2 Introduction 8 2 1 General Overview 8 2 2 Important Features 9 3 Installation 10 3 1 Applications 10 3 2 Installation Procedures 12 Appendix A IEC Compliance 14 Appendix B...

Страница 5: ...EIA TIA RS 422 and RS 423 10BASE T Type 3 Token Ring 100BASE T 100VG AnyLAN and ATM CAUTION Because of clamp voltage limitations the Surge Protectors are not compatible with ARCNET or Type 1 Token Ri...

Страница 6: ...s than 0 4 dB at 100 Mhz including connector Return Loss Better than 14 dB Group Delay None 1 MHz to 100 MHz Series Resistance Less than 400 m Connectors 2 RJ 45 female Leads Signals Protected All MTB...

Страница 7: ...e the tables in Appendix B Both Surge Protectors will also protect against surges up to and exceeding 2kV 1kA in fail safe mode When hit by strong surges they will fail but in doing so they will short...

Страница 8: ...portant Features Multi level surge protection Operation at data rates up to 100 Mbps EIA TIA TSB 40A Category 5 compliant NEXT better than 43 dB at 100 Mhz Shunts surges directly to chassis ground or...

Страница 9: ...rent applications The following descriptions will give you a general guideline for installing the units in your Category 5 environment 3 1 1 THE SECONDARY SURGE PROTECTOR SP251A The Secondary Surge Pr...

Страница 10: ...nd installations with heavy machinery in close proximity to sensitive LAN equipment and cabling Figure 3 2 below shows a typical application for the PSP For best results the braided grounding strap on...

Страница 11: ...hrough pinned Category 5 patch cable with modular RJ 45 connectors from the Surge Protector to the port we suggest that you use the cable supplied with the Surge Protector It doesn t matter which end...

Страница 12: ...you use the cable supplied with the PSP It doesn t matter which end of the PSP is attached to the twisted pair line and which end is attached to the patch cable 3 Find a common or on equipment electr...

Страница 13: ...es ISO IEC Publications 801 2 and 801 4 which describe Electrostatic Discharge and Electrical Fast Transient requirements ISO IEC 801 5 describes Surge Immunity Requirements see Table A 1 below and is...

Страница 14: ...dB dB dB dB dB dB dB 1 80 80 80 80 80 80 65 4 78 71 0 80 75 0 73 0 77 0 65 8 75 66 0 80 70 0 77 0 66 0 62 10 70 63 0 80 68 0 74 0 69 0 60 16 66 59 3 80 64 0 80 0 72 0 56 20 65 57 6 80 62 0 80 66 0 54...

Страница 15: ...1 10 0 0 0 0 0 0 0 0 0 1 16 0 0 0 0 0 0 0 0 0 2 20 0 0 0 0 0 1 0 0 0 2 25 0 1 0 0 0 0 0 0 0 2 31 25 0 1 0 1 0 1 0 2 0 2 62 5 0 2 0 1 0 2 0 3 0 3 100 0 2 0 2 0 3 0 3 0 4 Attenuation Measurements for t...

Страница 16: ...3 16 37 0 34 0 32 3 33 0 23 20 35 0 30 8 31 0 31 6 23 25 34 5 24 4 29 8 30 4 14 31 25 35 0 23 5 30 0 30 5 14 62 5 24 2 28 7 22 0 22 5 14 100 19 0 27 0 18 3 19 0 14 Return Loss Measurements for the Sec...

Страница 17: ...NOTES...

Страница 18: ...1000 Park Drive Lawrence PA 15055 1018 724 746 5500 Fax 724 746 0746 Copyright 1996 Black Box Corporation All rights reserved...

Отзывы: