Hardware Installation 
 

Inputs (COE-8

I

Connect the inputs to the COE-8

using the screw terminals on the printed circuit card, as illustrated. Inputs 

can be either dry relay or switch contacts, or a +VDC voltage (3 to 30 V), referenced to a common ground. 
 

Status   Dry Relay    DC Voltage 

Open          Open             >3VDC 
Closed      Closed           <=0VDC 
 
Input Specification Dry Contact (common ground) or Wet ±30VDC Max

 

 

Relays (COE-8O) 

Connect the inputs to the COE-8I using the screw terminals on the printed circuit card, as illustrated.  
 
Relays are Form A. Relay Specifications 

 
Rating (resistive)  

 

0.5 A 120 VAC or 1 A 24 VDC 

Maximum Carrying Current  

2 A 

Maximum Switching Power  

60 AV, 24 W 

Maximum Switching Voltage  

120 VAC/60 VDC 

Maximum Switching Current  

1A 

Life Expectancy:  

 

5 Million Operations Mechanical 100K Operations at rated load 

 

Network 

Connect the network to the connector provided. A yellow LED indicates a successful connection to the 
network, a green LED data activity. 
 

Power 

Apply power only when the cover is secured onto the COE-8. Use only the wall mounted power supply 
provided.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание COE-8I

Страница 1: ...evices and Transmitter Unit COE 8I and a Receiver Unit COE 8O The COE 8I provides 8 inputs for switch contacts relay closures or DC Voltage Upon a change of state for any channel it will transmit a me...

Страница 2: ...sing the screw terminals on the printed circuit card as illustrated Relays are Form A Relay Specifications Rating resistive 0 5 A 120 VAC or 1 A 24 VDC Maximum Carrying Current 2 A Maximum Switching P...

Страница 3: ...Board Diagram COE 8I COE 8O LEMV295034 LEEM295035...

Страница 4: ...onfiguration for the unit Open a browser to the default or current IP address of the unit Enter the default username and password Factory Defaults IP Address 192 168 1 254 Username admin Password admi...

Страница 5: ...Subnet Mask and Gateway as provided by your network administrator Click Apply to save the changes You will then be prompted to reboot the COE 8 Click on the Reboot button The COE 8 will reboot and the...

Страница 6: ...en a Command Prompt window 2 Type the following command arp s IP Address MAC Address Where IP Address is the desired IP address for the COE 8 and the MAC address is the MAC Address of the COE 8 The MA...

Страница 7: ...and all COE 8Os that receive status from it must be set the same If a port other than the default Port 80 is used for web browser access that port must specifically be used in the URL when accessing t...

Страница 8: ...hange of state on any COE 8 channel Check the box provided to enable this If both the COE 8I and COE 8O are configured to send traps two messages will be received by each SNMP manager for each event P...

Отзывы: