Black Box 26577 Скачать руководство пользователя страница 2

724-746-5500

   blackbox.com

BLACK BOX

®

  2 of 2

03/22/2010 

#26577

 

»

  Crystal-clear controller signal out to 4000 feet 

(1219.2 m).

 

»

  Opto-isolation available.

 

»

  Can be configured for two- or four-wire  

and half- or full-duplex operation.

 

»

  Connect to your RS-485 network via RJ-45 

modular connectors or screw-block terminals. 

FEatuRES

BLACK BOX

®

 RS-485 Repeaters extend your RS-485 

communications beyond the 4000-foot limit. Even located 5000 feet 
from your master device, they’ll take your RS-485 communications 
signals and shoot them another 4000 feet. 

Great for connecting multiple RS-485 segments in different 

buildings or rooms, the repeaters enable you to add more devices  
to your network—up to 32 more units per repeater. 

They support either 2- or 4-wire applications, in full- or half-duplex 

operation. Plus, the 

RS-485 Repeaters

 come with a 4-screw terminal 

block, RJ-45 connectors, and an edge card connector, so they fit right 
in with any RS-485 wiring scheme.

To protect your lines from ground loops and other electrical 

problems, order the 

RS-485 Repeater

 with Opto-Isolation (IC158A). 

Ideal for industrial applications, it isolates one segment of your 
extended network from problems that may arise on another segment. 

Inside the opto-isolated repeater, optical isolation circuitry converts 

electrical signals to light and back again to keep signal noise and 
ground loops from crossing between segments of your RS-485 
installation. Electrical noise from your factory floor won’t affect office 
communications, and the difference in ground potential between 
buildings won’t damage your sensitive equipment. 

Simple to install and configure. 

Just set internal jumpers and switches to match the cabling and 

duplex operation of your application as well as to match repeater 

OVERVIEW

ports for terminated and unterminated operation. Then, connect your 
devices to the repeater itself, power it up, and power up the rest of 
your RS-485 network. 

In half-duplex mode, jumpers determine the turnaround delay for 

the receiving repeater. Through these jumpers, you can configure the 
delay to match the length of cables and the number of device drops in 
your application. 

The greater the length of your RS-485 line or the larger the 

number of drops on the your network, the longer the line will remain 
charged after the transmitter has been disabled.

The 

RS-485 Repeaters

 use three different types of delays: a turn-

around delay, a turn-ON delay, and a turn-OFF delay. The turn-ON 
delay prevents the repeaters from passing along noise. It does this by 
delaying the transmitter long enough to allow most noise to dissipate 
before transmitting. With turn-OFF delay, the repeaters‘ transmitter  
is enabled long enough for the input data to propagate though the 
repeater after the sending device drops a signal. 

Both repeater models have three LEDs visible through their front 

panel that indicate power, carrier detect, and when a transmitter is 
enabled on the RS-485 line.  

NOTE: The repeaters do not feature collision detection or hardware  
flow control. 

T e c h   S P e c S

Flow Control —

 Transparent

Leads Supported —

 Both ports: TDA, TDB, RDA, RDB

Operation —

 Half- or full-duplex

Speed —

 Transparent up to 128 kbps

CE Approval —

 Yes

Connectors —

 (2) 4-wire terminal blocks, (2) RJ-45

Indicators —

 Power, Carrier Detect (both ports)

Operating Environment —

 Temperature: 32 to 110ºF (0 to 45ºC)

  Humidity: 0 to 95%, noncondensing

Power —

 115 VAC, 60 Hz (230-VAC, 50-Hz version on request)

Size —

 1.8"H x 5.5"W x 8.5"D (4.6 x 14 x 21.6 cm)

Item   

 

Code

RS-485 Repeater 

IC155a

RS-485 Repeater with Opto-Isolation 

IC158a