 Compressed air or oxygen shall not be used for 

purging refrigerant systems.

♦ 

 For appliances containing flammable 

refrigerants, refrigerants purging shall be 

achieved by breaking the vacuum in the system 

with oxygen-free nitrogen and continuing to 

fill until the working pressure is achieved, then 

venting to atmosphere, and finally pulling down 

to a vacuum. This process shall be repeated 

until no refrigerant is within the system. 

When the final oxygen-free nitrogen charge 

is used, the system shall be vented down to 

atmospheric pressure to enable work to take 

place. This operation is absolutely vital if 

brazing operations on the pipe-work are to take 

place.

♦ 

 Ensure that the outlet for the vacuum pump is 

not close to any potential ignition sources and 

that ventilation is available.

♦ 

Charging procedures

In addition to conventional charging procedures, the 

following requirements shall be followed.

♦ 

Ensure that contamination of different 

refrigerants does not occur when using 

charging equipment.

♦ 

Hoses or lines shall be as short as possible to 

minimise the amount of refrigerant contained 

in them.

♦ 

Cylinders shall be kept in an appropriate 

position according to the instructions.

♦ 

Ensure that the refrigerating system is earthed 

prior to charging the system with refrigerant.

♦ 

Label the system when charging is complete 

(if not already).

♦ 

Extreme care shall be taken not to overfill the 

refrigerating system.

♦ 

Prior to recharging the system, it shall 

be pressure-tested with the appropriate 

purging gas. The system shall be leak-

tested on completion of charging but prior to 

commissioning. A follow up leak test shall be 

carried out prior to leaving the site.

14.  Decommissioning

♦ 

Before carrying out this procedure, it is 

essential that the technician is completely 

familiar with the equipment and all its detail. 

It is recommended good practice that all 

refrigerants are recovered safely.

♦ 

Prior to the task being carried out, an oil and 

refrigerant sample shall be taken in case 

analysis is required prior to re-use of recovered 

refrigerant. It is essential that electrical power 

is available before the task is commenced.
a.  Become familiar with the equipment and its  

 operation.
b.  Isolate system electrically.
c.  Before attempting the procedure, ensure  

 that:

♦ 

 Mechanical handling equipment is 

available, if required, for handling 

refrigerant cylinders;

♦ 

 All personal protective equipment is 

available and being used correctly;

♦ 

 The recovery process is supervised at all 

times by a competent person;

♦ 

 Recovery equipment and cylinders conform 

to the appropriate standards.

d.  Pump down refrigerant system, if possible.
e.   If a vacuum is not possible, make a 

manifold so that refrigerant can be removed 

from various parts of the system.

f.   Make sure that cylinder is situated on the 

scales before recovery takes place.

g.   Start the recovery machine and operate in 

accordance with instructions.

h.   Do not overfill cylinders (no more than 80% 

volume liquid charge).

i.   Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j.   When the cylinders have been filled 

correctly and the process completed, make 

sure that the cylinders and the equipment 

are removed from site promptly and all 

isolation valves on the equipment are 

closed off.

k.   Recovered refrigerant shall not be charged 

into another refrigerating system unless it 

has been cleaned and checked.

Содержание BXEH60003GB

Страница 1: ...BXEH60003GB www blackanddecker co uk ...

Страница 2: ...ENGLISH Original instructions 2 2 1 6 4 3 5 What s in the box Instruction Manual Dehumidifier Features 1 Air outlet 2 Control panel 3 Air inlet 4 Filter 5 Water tank 6 Handle ...

Страница 3: ...of fire electric shock personal injury and material damage Using Your Appliance Please read the operating instructions carefully before using your appliance for the first time Check that the voltage of the main circuit corresponds with the rating of the appliance before operating Children shall not play with the appliance Do not let the cable hang over the edge of a table or counter or let it come...

Страница 4: ...appliance is used near pets Do not allow the cord to become twisted After Use While cleaning DO NOT use a wet cloth or use water on any part of the unit as this may cause a short circuit or electrical shock Keep this unit clean Do not allow objects to enter the ventilation opening as this may cause electric shock or damage to the unit Switch off the unit and then remove the plug from the socket wh...

Страница 5: ...n windows as contact with rain and other natural elements could cause an electrical hazard Do not put heavy objects on the appliance Do not tip the unit on its side Never insert any other object into the unit body to avoid any hazard or unit failure Do not put the unit close to heat generating devices or near flammable and dangerous materials If the supply cable is damaged it must be replaced by t...

Страница 6: ...e in a room with a floor area of less than 4m2 Be aware that the refrigerant may be odourless and that leaks may not be detectable by smell ALWAYS take care to comply with national gas regulations Keep ventilation openings clear of obstruction Store the appliance in a well ventilated area where the room size corresponds to the room area specified for operation Any person who is involved with worki...

Страница 7: ...ch the appliance off and remove the plug from the socket Features 1 Air outlet 2 Control panel 3 Air inlet 4 Filter 5 Water tank 6 Handle Use About the Controls Dry clothes Normal Operation Continuos Operation Ventilation Sleep Mode Operation and Efficiency This appliance operates in temperatures between 5 32 C Defrosting operation The evaporator in the dehumidifier may defrost automatically if it...

Страница 8: ...storing Dehumidification Modes There are 4 modes to select from Normal dehumidification adjustable fan speed and adjustable humidity Continuous dehumidification a set low fan speed and humidity is not adjustable Ventilation mode adjustable fan speed and humidity is not adjustable Drying mode a set high fan speed and set humidity is not adjustable Press the mode button to cycle through the options ...

Страница 9: ... The drainage hose should not be installed outdoors at low temperatures Drainage Manually When the water tank is full the water full indicator is will illuminate and the unit will stop working Pull out the water tank and pour away the water Replace the water tank The dehumidifier will restart Note Before putting in the water tank please ensure the float inside it moves freely Cleaning and maintena...

Страница 10: ...ew plug Connect the blue lead to the neutral terminal If the product is class I earthed connect the green yellow lead to the earth terminal Note If your product is class II double insulated only 2 wires in the cord set no connection is to be made to the earth terminal Follow the fitting instructions supplied with good quality plugs Any replacement fuse must be of the same rating as the original fu...

Страница 11: ...such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed to make sure that there are n...

Страница 12: ...serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s specifications 11 Repair to intrinsically safe components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use Intrinsically safe co...

Страница 13: ...ging but prior to commissioning A follow up leak test shall be carried out prior to leaving the site 14 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall b...

Страница 14: ... is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant waste transfer note arranged Do not mix refrigerants in recovery un...

Страница 15: ...s please contact our customer services team The product must be installed and used in accordance with the instructions contained in this instruction guide It must be used only for domestic purposes It does not cover wear and tear damage misuse or consumable parts This guarantee is valid in the UK and Republic of Ireland For all customer service enquires please contact us below RKW Sutton House Ber...

Страница 16: ...11 2020 ...

Отзывы: