background image

                     TECHNICAL DATA OF PRODUCT                                         

        

INSTALLATION AND USERS GUIDE 

DESCRIPTION AND USING

Switching   power   supply   JS-30-XXX/DIN_KK   is   intended   for   power   supply   of   controlling   and 

monitoring electronic devices in industrial area in settings with no danger of explosion with wide 

range of operational temperature.

The Supply is placed in a 3M wide metal box with possibility of attachment to a DIN35 plinth.  

Input and output connection is made with terminal boxes. Output networks are SELV type.

TECHNICAL PARAMETERS

Input voltage

    

230V AC (180-260V AC)

Input current 

    

0,25A  by 230V AC

Dielectric strentgh 

3000V AC primary-secondary

Isolating resistivity

more than 50MΩ

Outup parameters (voltage and current) are printed on the type label of power supply.

ENVIROMENTAL CONDITIONS 

Operating temperature

-40 až 70ºC

Humudity (non condensing)

10 to 80% RV

Installation altitude

till 2000m 

IP code

IP20 (terminals IP00)

Weight  

240g

Cooling 

natural

Dimensions

90x53x58mm (HxWxD)

Class of device                                 Class I

Power derating from 60°C to 70°C – 1%/°C (linearly).

TECHNICAL STANDARDS

Safety

 EN 60950-1

EMC

 EN 61000-6-1 ed.2

 EN 61000-6-3 ed.2

PACKING AND STOCKING

The product is delivered in a box made of white cardboard (particular packing). Instructions for 

installation and tender are enclosed to the supply. The product is to be stocked in temperatures  

from –40 to 80°C, in relative humidity to 90%, in areas where can be no ship ´s sweating on the  

products. The product can´t be striked, exposed to mechanical shock and injurious gases.

INSTRUCTIONS FOR INSTALLATION

Connecting of the supply can be made only by qualified persons. Screw clamps make possible 

connecting wire of crosscut from 0,5 to 2,5mm

2

. Operating position of the supply is random, 

vertical is better. The product is intended for installation to an area with no danger of explosion.

CONNECTION

    
SETTING IN OPERATION

The Supply is intended for permanent operating, has a T1AH/250V fuse unit on input and there 

is no need to have it secondary secured. Terminal of supply voltage must be possible to switch 

off. After wiring output terminals of network and connecting input voltage is the Supply ready for 

operating.

SERVICE AND REPAIRING

The product doesn´t require servicing or maintenance.

The product is to be repaired by the producer. Products for repairing are to be send in a box that 

protects it from damage during delivering.

DURABILITY

Minimum effective life of the product is 50 000 hours.