TECHNICAL DATA OF PRODUCT
INSTALLATION AND USERS GUIDE
DESCRIPTION AND USING
Switching power supply JS-30-XXX/DIN_KK is intended for power supply of controlling and
monitoring electronic devices in industrial area in settings with no danger of explosion with wide
range of operational temperature.
The Supply is placed in a 3M wide metal box with possibility of attachment to a DIN35 plinth.
Input and output connection is made with terminal boxes. Output networks are SELV type.
TECHNICAL PARAMETERS
Input voltage
230V AC (180-260V AC)
Input current
0,25A by 230V AC
Dielectric strentgh
3000V AC primary-secondary
Isolating resistivity
more than 50MΩ
Outup parameters (voltage and current) are printed on the type label of power supply.
ENVIROMENTAL CONDITIONS
Operating temperature
-40 až 70ºC
Humudity (non condensing)
10 to 80% RV
Installation altitude
till 2000m
IP code
IP20 (terminals IP00)
Weight
240g
Cooling
natural
Dimensions
90x53x58mm (HxWxD)
Class of device Class I
Power derating from 60°C to 70°C – 1%/°C (linearly).
TECHNICAL STANDARDS
Safety
EN 60950-1
EMC
EN 61000-6-1 ed.2
EN 61000-6-3 ed.2
PACKING AND STOCKING
The product is delivered in a box made of white cardboard (particular packing). Instructions for
installation and tender are enclosed to the supply. The product is to be stocked in temperatures
from –40 to 80°C, in relative humidity to 90%, in areas where can be no ship ´s sweating on the
products. The product can´t be striked, exposed to mechanical shock and injurious gases.
INSTRUCTIONS FOR INSTALLATION
Connecting of the supply can be made only by qualified persons. Screw clamps make possible
connecting wire of crosscut from 0,5 to 2,5mm
2
. Operating position of the supply is random,
vertical is better. The product is intended for installation to an area with no danger of explosion.
CONNECTION
SETTING IN OPERATION
The Supply is intended for permanent operating, has a T1AH/250V fuse unit on input and there
is no need to have it secondary secured. Terminal of supply voltage must be possible to switch
off. After wiring output terminals of network and connecting input voltage is the Supply ready for
operating.
SERVICE AND REPAIRING
The product doesn´t require servicing or maintenance.
The product is to be repaired by the producer. Products for repairing are to be send in a box that
protects it from damage during delivering.
DURABILITY
Minimum effective life of the product is 50 000 hours.