DB-300-9
9
Type
Reservoir fluid
capacity
dm
3
(l)
Category according
to 2014/68/EU (PED)
Fluid group 2
Category according
to 2014/68/EU (PED)
Fluid group 1
Conformity as-
sessment de-
pending on the
module
FS4752(P)
473
IV
IV
B + D
FS5502(P)
550
IV
IV
B + D
OA1954(A)
40
III
IV
B + D
OA4188(A)
88
III
IV
B + D
OA9111(A)
228
IV
IV
B + D
OA14111(A)
395
IV
IV
B + D
OA25112(A)
655
IV
IV
G
OAC14011A
616
IV
IV
G
OAC25112A
868
IV
IV
G
OAS322
2.7
I
II
A2
OAS744
7
I
II
A2
OAS1055
10
II
III
B + D
OAS1655
16
II
III
B + D
OAS3088
30
II
III
B + D
OAF6288
62
III
IV
B + D
OAF15211
152
IV
IV
B + D
OAH2888
112
IV
IV
B + D
OAH7088
228
IV
IV
B + D
OAHC65051A
630
IV
IV
B + D
OAHC80051A
1130
IV
IV
G
OAHC100051A
2250
IV
IV
G
Tab. 2: Category and conformity assessment
4
Mounting
4.1
Transporting the pressure vessel
Transport the pressure vessel screwed on a pallet. Lift
it using the eyebolts or the upper fastening brackets if
available.
DANGER
Suspended load!
Do not step under the machine!
4.2
Installation location
For outdoor installation, take suitable measures to pro-
tect the pressure vessel against corrosion (e.g. caused
by seawater or aggressive atmosphere) and low out-
side temperatures. Consultation with BITZER is recom-
mended.