v. 3.0
Reference guide
Compressor Control Module CM-RC-01
3.0
27 / 44
No.
Text
Warning Critical Fault
Reset
type
3400
Suction Pressure Low
No
No
Yes
Timed
3411
Discharge Pressure High
No
No
Yes
Timed
3431
High Pressure Switch
No
No
Yes
Extern
35-*
Compressor - Other Input
3500
Oil Level Low
No
Yes
Yes
Extern
3502
Oil pressure low
No
Yes
Yes
Extern
43-*
Motor - Temperature
4301
Motor Temperature High
Yes
Yes
Yes
Extern
4302
Motor Temperature Cooldown
No
No
Yes
Timed
58-*
FC - Electronics Fault
5851
HW: 24V
No
No
Yes
Restart
67-*
Device - SW Configuration
6700
Config Data: No File
No
No
Yes
Restart
6701
Config Data: CRC Error
No
No
Yes
Restart
6702
Config Data: Wrong Version
No
No
Yes
Restart
6703
Config Data: Read Only
No
No
Yes
Restart
68-*
Device - Electronics Fault
6810
HW: 3.3V
No
No
Yes
Restart
6811
HW: User 5V
No
No
Yes
Restart
6813
HW: 24V
No
No
Yes
Restart
69-*
Device - Other
6900
Datalog error
Yes
No
No
N/A
73-*
Sensor - Temperature
7304
Sensor: Motor Thermistor
No
Yes
Yes
Timed
7308
Sensor: Discharge Temperature
No
No
Yes
Timed
7320
Sensor: Aux Temperature
No
No
Yes
Timed
74-*
Sensor - Pressure
7401
Sensor: Suction Pressure
No
No
Yes
Timed
7402
Sensor: Discharge Pressure
No
No
Yes
Timed