1.3 Specifications
Input Signals
Amperes:
0 to 5A ac nominal, three phase, with continuous overload to
10A ac, 400A ac for 2 seconds. 1500Vac isolation, minimum.
Volts:
0
to
150V
ac
nominal, three phase. 1500Vac isolation,
minimum.
Signal Burden
Amperes:
4 mV ac at 5A ac input ( 0.02 VA ).
Volts:
<1 mA ac at 120V ac input ( 0.1 VA ).
Display:
0000 to +/-1999 with decimal determined by CT/PT ratio.
Scaling:
User selectable using internal CT/PT tables.
Accuracy:
0.25% Class (ANSI Std 460-1988).
Signal Frequency:
50Hz to 400Hz (Including Harmonics).
Current Output:
0 to +/- 1mA into 10K ohms or less; 0.4% ripple p-p or less.
Calibrated at 1000W at meter input. Overload to +/- 2mA into
5K ohms or less.
Power Requirements:
115 Vac +/- 20%, 6 VA (230 Vac or Universal AC/DC optional)
Fuse:
1.5
Ampere,
non-time
delay (M) fuse, UL listed located in the
ungrounded (hot) side of the line, external to meter.
Operating Temperature: -30C to 70C. Humidity: 0-95% non-condensing
Installation Category:
IC III
Weight:
2.5 pounds ( 1.14 kilograms )