DESCRIPTION

The Bird NFPA Alarm Panel is a signal booster
alarm status annunciator that provides a conve-
nient  means  of  monitoring  your  signal  booster
alarms from a reasonably nearby location such as
a security desk or main lobby desk located in the
same building as the signal booster. The alarm
panel is capable of monitoring the five required
NFPA alarms including; Signal Booster Failure,
Loss of AC Power, Antenna Malfunction, Low Bat-
tery Condition, and Charger Failure.

The NFPA Alarm Panel can be used with any Bird
Signal Booster that uses Form-C relay contacts to
announce NFPA alarm conditions. The connection
between the signal booster and the alarm panel
box consists of a twisted pair of wires for each
monitored alarm function. In addition, the alarm
panel requires a DC operating voltage of +12 VDC
to +24 VDC.

INSTALLATION

The following sub-sections of the manual discuss
general  considerations  for  installing  the  alarm
panel. All work should be performed by qualified
personnel. Bird provides the alarm panel only, the
customer is responsible for supplying cabling as
well as the alarm panels DC operating voltage.

Installing the Alarm Panel

The alarm panel is designed to be wall mounted
and has a built-in mounting flange on the top-rear
and bottom-rear of the box. Each flange has two
screw  holes  and  all  four  holes  should  be  used
during installation to insure the box is fastened
firmly. Place the panel in a convenient viewable
location. There  is  no  audio  indication  from  the
panel so the panel needs to be placed such that a
change  in  the  color  of  the  LED’s  can  be  easily
noticed. 

Figure 1

 shows the mechanical mounting

details of the alarm panel enclosure.

Signal Lines

With the panel box installed run a twisted pair for
each monitored alarm function from the inside of
the  alarm  panel  box  to  the  inside  of  the  signal
booster.  The  terminal  connectors  in  the  alarm
panel can accommodate wire gauge between 16
and 28. For ease of installation it is recommended
that CAT 6 STP (shielded twisted pair) or even CAT
7 cable be used to carry the alarm information from
the signal booster to the alarm panel box.

One of the important considerations when installing
the twisted pairs for signal lines is noise on the
lines which may cause false alarm indications at
the alarm panel. Using good quality cable with suf-
ficient shielding is important. Also, when laying the
cable run avoid running it next to the buildings AC
wiring or near strong noise sources like motors.

Because the alarm panel signal inputs are MOS-
FET the twisted pairs do not carry current and the
physical distance between the signal booster and
the alarm panel can be considerable, several thou-
sand feet comfortably when using Cat 6 or 7 cable.
If your installation requires the distance between
the  signal  booster  and  the  alarm  panel  to  be
greater than several thousand feet consult with the
factory before running the signal cable. The wire
gauge and shielding used for the signal lines will
determine the workable distance, thicker wire gives
greater distance but can be cost prohibitive.

Inside the alarm panel enclosure the twisted pairs
must be connected to the appropriate terminals at

Figure 1:

 Alarm Panel mounting dimensions.

30303 Aurora Rd. Solon, OH 44139   Tel: 1-440-248-1200   [email protected]  

www.birdrf.com

Содержание 6150-ALM-01

Страница 1: ...Manual 7 9619 1 08 21 18 Page 1 Installation Instructions for the Model 6150 ALM 01 NFPA Alarm Panel Manual Part 7 9619 1 30303 Aurora Rd Solon OH 44139 Tel 1 440 248 1200 sales birdrf com www birdrf...

Страница 2: ......

Страница 3: ...619 1 08 21 18 Page 2 Manual Part Number 7 9619 Copyright 2018 Bird First Printing August 2018 Version Number Version Date 1 08 21 18 30303 Aurora Rd Solon OH 44139 Tel 1 440 248 1200 sales birdrf com...

Страница 4: ...such that a change in the color of the LED s can be easily noticed Figure 1 shows the mechanical mounting details of the alarm panel enclosure Signal Lines With the panel box installed run a twisted p...

Страница 5: ...d up operating normally with no alarm conditions Bring the twisted pairs from the booster into the alarm panel box through one of the conduit open ings at the bottom of the box Use one of the con duit...

Страница 6: ...ghtened down the connector head can be re attached to the circuit board at the J1B location The DC operating voltage should be supplied by an uninterrupted source so that the alarm panel remains funct...

Страница 7: ...ard When the alarm panel is powered up the sta tus lights will be green for any of the 5 monitored parameters that have their alarm input terminals connected to normally closed contacts That means bac...

Страница 8: ...2 38 100 4 37 98 6 36 96 8 35 95 0 34 93 2 33 91 4 32 89 6 31 87 8 30 86 0 29 84 2 28 82 4 CELCIUS FAHRENHEIT 27 80 6 26 78 8 25 77 0 24 75 2 23 73 4 22 71 6 21 69 8 20 68 0 19 66 2 18 64 4 17 62 6 16...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...Bird Manual 7 9619 1 08 21 18 Page 8 30303 Aurora Rd Solon OH 44139 Tel 1 440 248 1200 sales birdrf com www birdrf com...

Отзывы: