BINMASTER MAXIMA+ Series Скачать руководство пользователя страница 9

1020

925-0268 Rev C

SERIES ROT

AR

Y

 LEVEL

 INDICA

TOR

In NRM mode, the Status Relay will have a connection between the C and the NO termi-

nal. In a Fault condition there will be a connection between the C and NC terminals when 

using the standard SPDT relay. The solid state relays are SPST, they do not use the NC 

terminal. In Normal mode with either of the solid state relay options, there will be a con-

nection between the C and NO terminal when the 

 is operating normal. During a 

Fault condition the there will be no connection between the C and NO terminal.
In the Pulse (PLS) mode it is recommended to have one of the solid state relay options.  

In Pulse Mode (PLS) the Status Relay will be energized during a covered condition and 

there will be a connection between the C and NO terminals. When the paddle is rotating 

(uncovered) the Status Relay will be pulsing ON and OFF like the visual LED. During a 

Fault condition the Status Relay will de-energize.

4.0 TIME DELAY

The has selectable time delay for the DPDT relay contacts. This time delay can 

be selected for switching from an uncovered to a covered condition or it can be selected for 

switching between a covered to an uncovered condition or both. The time delay is selected 

by the two time delay DIP switches. Switch 1 is for selecting a time delay for going from an 

uncovered to a covered condition. Switch 2 is for selecting a time delay for going from a 

covered to an uncovered condition. When the switch is OFF there is no time delay. When 

the switch is ON there will be a time delay for that condition.  
By default the time delay is set to 5 seconds for both switches. This time delay can be 

changed by using the SETUP push button switch on the circuit board. (Refer to Figure 10). 

The Delay Time can be set for each switch independently or for both together if the same 

delay time is desired for both ”delay on covered” and “delay on uncovered”. The maximum 

time delay that can be programmed is 25 seconds. Follow the procedure in 4.1 to change 

the delay time.

4.1 Changing Delay Time
Step 1.

 Select the switch for the delay time that you want to change by placing it in the  

ON position. Switch 1 is for “Delay on Covered”. Switch 2 is for “Delay on Uncovered”.  

The new delay time will be set for switch or switches in the ON position. At least one of  

the delay switches must be ON in order to enter the programming mode.

Step 2.

 Press and hold the SETUP switch (refer to Figure 10) for three seconds to initiate 

the programming mode. The LED will flash for these three seconds at a fast rate to indicate 

entry of the program mode. Releasing the SETUP switch during this initial three second 

period will abort the program mode and leave the delay times unchanged.

Step 3.

 After the three seconds has passed, continue holding the SETUP switch for the  

desired amount of delay time in seconds. The LED stops flashing and will blink every 

 

second to give you indication of the delay time so far. Each one second flash is one 

 

second of delay time.

Step 4.

 After the desired amount of delay has passed, let go of the SETUP switch and the 

delay time will be set for the delay switches that are in the ON position. You may enter up 

to 25 seconds. Holding the SETUP switch longer than this will have no effect and limit the 

delay to 25 seconds. 

www.

.com

[email protected]

1.800.561.8187

Содержание MAXIMA+ Series

Страница 1: ...MAXIMA Series Rotary Level Indicator OPERATING INSTRUCTIONS PLEASE READ CAREFULLY BinMaster Division of Garner Industries 925 0268 Rev C 1020 www com information itm com 1 800 561 8187 ...

Страница 2: ...Location and Mounting 5 2 2 Input Power and Field Wiring 6 2 3 Grounding 7 3 0 RELAYS 7 3 1 DPDT Relay 7 3 2 Fail Safe High 7 3 3 Fail Safe Low 8 3 4 STATUS Relay 8 4 0 TIME DELAY 9 4 1 Changing Time Delay 9 5 0 EXTERNAL LED 10 6 0 WARRANTY AND CUSTOMER SERVICE 10 7 0 DISPOSAL 10 EUROPEAN DECLARATION OF CONFORMITY 11 www com information itm com 1 800 561 8187 ...

Страница 3: ...DELS Internally protected no external fusing required Ambient Temperature Electronics 40 F to 158 F 40 C to 70 C Enclosure Type 4X 5 9 12 Hazardous locations Class II Groups E F G DPDT Relay Output 10 Amps 250 VAC Fail Safe Switch selectable High or Low level modes Status Indicator Relay SPDT 10 A 250 VAC optional DC Solid State Relay 1 A 42 VDC optional AC Solid State Relay 1 A 250 VAC Time Delay...

Страница 4: ... contact ratings as called out on the nameplate and in the installation manual Ensure that the enclosure cover is in place and secured tightly during normal operation If this product is used in a manner not specified by the manufacturer the safety protection could be compromised Safety Terms and Symbols WARNING Warning statements identify conditions or practices that could result in injury or loss...

Страница 5: ...ting again to indicate an uncovered condition 2 0 INSTALLATION 2 1 Location and Mounting TOP MOUNT 1 Locate and cut hole in top of bin to fit outside diameter of 1 1 4 pipe coupling 1 950 2 Position coupling halfway into bin and weld 3 Turn unit so conduit opening is in desired location 4 Add 1 4 extension pipe to desired length with standard 1 4 coupling on bottom end 5 Cut 1 1 4 support pipe app...

Страница 6: ...the maximum voltage and current as per equipment ratings and has a temperature rating of at least 70 C For relay outputs use wire that is sized and rated for the maximum voltage and current as per application up to 250 VAC 10A Installation shall be done by qualified personnel Caution Use supply wires suitable for 25 C above surrounding ambient Attention Utiliser des fils D Alimentation qui convien...

Страница 7: ...be connected to different phases only for voltages up to 125 VAC For voltages above 125 VAC the relays shall be connected to the same phase circuit only 3 1 DPDT Relay The DPDT relay utilizes a Fail Safe selection jumper F S There are two positions for this jumper High H and Low L A Fail Safe condition means that the DPDT relay contact positions are set up so that in the event of a fault condition...

Страница 8: ... jumper at the top of the circuit board see Figure 10 In the NORMAL NRM position the Status Relay is energized when the MAXIMA is oper ating correctly In this mode the shaft rotation is monitored If the shaft is not rotating then the covered switch is monitored to see if there is a covered condition If the shaft is not rotating and the covered switch is not indicating covers then the Maxima will g...

Страница 9: ...hat condition By default the time delay is set to 5 seconds for both switches This time delay can be changed by using the SETUP push button switch on the circuit board Refer to Figure 10 The Delay Time can be set for each switch independently or for both together if the same delay time is desired for both delay on covered and delay on uncovered The maximum time delay that can be programmed is 25 s...

Страница 10: ...rm the equipment purchase Failure to do so may void the warranty 2 The manufacturer will repair or replace any part of this equipment found to be defective provided such part is delivered prepaid to the factory Manufacturer s obligation is limited to the cost of material and labor to repair or replace and does not include transportation expenses 3 This warranty shall not apply to any product that ...

Страница 11: ...s described in this manual will provide a safe and reliable point level control device for bulk solid materials Low Voltage Directive 73 23 EEC Standard IEC 61010 1 2001 Product Rotary point level control device Models MAXIMA AC Model 24 VAC 115 VAC 230 VAC DC Models 12 VDC and 24 VDC All test reports and documentation are held and can be obtained from BinMaster Manufacturing Location Lincoln Nebr...

Страница 12: ...onments where it is possible for moisture or moist air to enter the enclosure through the electrical conduit the conduit opening should be sealed with a duct seal compound or putty appropriate for the purpose Always mount unit with conduit opening down Mounting Instructions www com information itm com 1 800 561 8187 ...

Отзывы: