DPM-100 Digital Panel Meter Modbus
®
Display
Instruction Manual
35
Setting the Tags (
tAg
) & Units
(
units
)
Each PV can be setup with its own tag and units. See
the flow charts on the previous pages to access the
display menu to show the tag or toggling tag & units.
The engineering units and custom tags can be set
using the following 7-segment character set:
Display Character
Display Character
0
0
k
K
1
1
l
L
2
2
n m
m
3
3
n
n
4
4
O
O
5
5
o
o
6
6
p
P
7
7
q
q
8
8
r
r
9
9
s
S
A
A
t
t
b
b
u
u
C
C
v
V
c
c
u w
w
d
d
x
X
e
E
y
Y
f
F
z
Z
g
G
-
-
9
g
/
/
H
H
[
]
h
h
]
[
I
I
=
=
I
i
!
Degree(<)
j
J
Space
Notes:
Degree symbol represented by (<) if programming with
ScanView.
The letters “m” and “w” use two 7-segment LEDs each;
when selected the characters to the right are shifted one
position.
Press and hold up arrow to auto-scroll the characters in
the display.
Application Example 1
In this application we have a system consisting of (4)
multivariable tank level gauges connected to (2)
DPM-100 Modbus scanners displaying Product Level,
Interface Level, and Average Temperature.
One of the Modbus Scanners is located next to the
tanks and the other is located in the control room.
Register Numbers & Process
Variables
30001 - Product Level
30003 - Interface Level
30017 - Average Temperature
The following table shows the system setup for a
typical multivariable level gauge, one DPM-100
Master, and one DPM-100 Snooper:
Parameter
PD6088
Master
PD6088
Snooper
Description/
Comment
Mode
Master
Snooper
PV1 Slave
ID
1
1
Function
Code
04
04
Register
PV1
30001
30001
Tank 1
Product
Level
Data Type
Long
integer
Binary,
Signed
Long
Byte Order
1234
1234
PV2 Slave
ID
1
1
Function
Code
04
04