SW3 

Position 

Sensitivity

0

.5 pF, Very High

1

1 pF, High

2

2  pF

3

3  pF

4

5 pf, Medium

5

8  pF

6

10 pF, Low

7

15 pF, Very Low

SW5 

Position 2

Time Delay Mode

On

The delay set on SW4 is applied when material touches the probe

Off

There is no delay when material touches the probe

SW5 

Position 3

Time Delay Mode

On

The delay set on SW4 is applied when material leaves the probe

Off

There is no delay when material leaves the probe

Figure 3. Sensitivity Settings

Figure 5. Time Delay Mode Settings

(See Fig. 2)

Figure 1. VRF-2000 Electronics

Failsafe Selection

High Level Failsafe Operation

·  DIP Switch SW5 position 1 is on.
·  If the electrical power fails, the relay turns off.  This indicates material as if the

tank were full.

Low Level Failsafe Operation

· DIP Switch SW5 position 1 is off.
· If the electrical power fails, the relay turns off.  This indicates material as if the

tank were empty.

SW4 

Position 

Time Delay

0

200 mSec

1

1  Sec

2

2  Sec

3

5  Sec

4

10 Sec

5

20 Sec

6

30 Sec

7

60 Sec

Figure 4. Time Delay Settings

(See Fig. 5)

(See Fig. 4)

(See Fig. 3)

The output relay contacts are labeled in the un-powered alarm state.  The relay is energized
when the VRF-2000R is not alarmed.  This status may be opposite that of other Bindicator

®

brand units.  If the VRF-2000R is replacing an older Model RF unit, connections will need to
be opposite.  If a connection was made to NC1 terminal of the RF, connect now to the NO1 
terminal of the VRF-2000R.  C1 and C2 connections would remain the same.