5.0 Electrical connection

The electrical connection for the power supply is made in the terminal compartment of the signal 
converter - 18-35VDC.

In case of installation in hazardous areas, only certified intrinsically safe equipment may be 
connected to the TDR-1000.

1. Connector:

Terminals:

  

   3 poles + ground. Wire cross-section max 0.059m

2

 (1.5 mm

2

(AWG 16).

p

Cable entries:

  

   M25x1.5 (PG11). Standard cable gland: cable clamping area = 0.315 - 0.39 in    

 

   (8-10 mm). IP65

Signal cable shielding:

      No shielding needed.

Power supply:

1. Remove the screw 

P

 and lift off the connector from the signal converter.

2. Put a screwdriver in 

F

 and separate 

N

 from 

R

.

3. Connect the current loop to terminal 1 and 2 (there’s no polarity to respect). Use ferrules to protect cable    
    ends. The terminal 3 and 

E

 remain non-connected.

4. Re-assemble 

N

 and 

R

.

5. Put the seal in place, connect 

R

 to the signal converter tighten and screw 

P

.

The terminal 

E

 is not connected with the signal connector housing or with the flange system of the instrument.

For standard and Ex applications only the intrinsically safe 2-wire loop must be connected to the terminals 1 
and 2. The terminal 

E

 as well as terminal 3 remains non-connected.

1

2

3

1

2

3

P

R

N

F

E

Содержание TDR-1000

Страница 1: ...TDR180002 Rev B INSTALLATION OPERATION MAINTENANCE MANUAL TDR 1000 GUIDED WAVE RADAR Quick Start Guide...

Страница 2: ...model is not installed correctly or used in approved applications dangers may arise such as product overflow Ensure that all personnel installing wiring and calibrating this device are suitably quali...

Страница 3: ...asured Variable distance level volume 3 1 Measuring Range 1 4 0 Mounting 4 1 Excessive Bending of the Cable 2 4 2 Mounting on a Nozzle 2 4 3 Interference between two TDR s 2 5 0 Electrical Connection...

Страница 4: ...Measured variable distance level volume The primary measured variable is the distance between the tank mounting flange and a reflecting surface surface of the product measured The output represents t...

Страница 5: ...le BE CAREFUL NOT TO BEND OR KINK CABLES TOO MUCH 4 2 Mounting on a nozzle 4 3 Interference between two TDR 1000 Avoid nozzle size higher than 5 9 especially when B 3 1 Try to ensure A does not exceed...

Страница 6: ...ng No shielding needed Power supply 1 Remove the screw P and lift off the connector from the signal converter 2 Put a screwdriver in F and separate N from R 3 Connect the current loop to terminal 1 an...

Страница 7: ...194 F Electronics Temperature 22 to 131 F Connection 1 5 MNPT Protection Category IP66 Nema 4X Power Supply 24VDC 18 to 35VDC Output 4 20mA current loop into max of 750 Ohms Communication HART protoc...

Страница 8: ...t 1 1 6 Probe length 1 2 4 Length unit 1 2 6 1 Unit name 1 2 6 2 Unit factor 1 2 5 Volume unit 1 3 1 Current output function 1 3 2 Current output range error 1 3 3 Min scale for current 1 3 4 Max scal...

Страница 9: ...BINDICATOR Installation Operation Maintenance Manual 6 Notes...

Страница 10: ...NTURE BOULEVARD SPARTANBURG SC 29306 PHONE 864 574 8060 FAX 864 574 8063 CUSTOMER CARE 800 778 9242 WWW BINDICATOR COM SALES BINDICATOR COM 2007 ALL RIGHTS RESERVED ALL DATA SUBJECT TO CHANGE TDR18000...

Отзывы: