MK LIT (E5) 01/2021
page 68/172
Bleeder screw
Secured lever
for manual release
Filler neck
Lock nut
Valve outlet
The high-pressure hose may only be connected after a successful test.
DANGER
Danger of suffocation and poisoning by leakage of CO
2
in high concentration
(> 4 Vol.-%).
Death due to suffocation.
∅
Do NOT remove the lock nut for connecting the high-pressure hose (chap. 11.1.5),
without a successful valve test.
After the test, screw the bleeder screw back in a gas-tight manner.
11.1.5 Connecting the CO
2
flushing line (high-pressure hose)
•
To connect the high-pressure hose, remove the lock nut
Lock nut position
Thread without lock nut