Cell Temperature Protection

If the temperature of any cell surpasses 70°C or drops below 0°C, the BMS will stop
charging. If the temperature of any cell surpasses 75°C or drops below -20°C, the
BMS will stop the discharge.

PCB High Temperature Protection

If the PCB temperature surpasses 95 °C, the BMS will stop charging or discharging
until the temperature drops below the recovery value.

Cell Balancing

During charging, if all cell voltages are greater than 3.4V and the voltage difference
between cells (ΔU) is > 40mV (ΔU = Max. Cell Voltage - Min. Cell Voltage), the BMS
will trigger the balancing process.

3.4 Control Panel Indicators

BMS Protection Indicators

When the LED alarm light comes on, a BMS protection has been triggered and the
battery has been protected. Please refer to the table below for individual warning
indicators and their recovery process and take the appropriate action.

State

Protection

Indicator

Recovery

Charging

Over Voltage

ALARM

Stop charging. Check module

voltage and charger.

Over Current

ALARM

Stop charging. Check settings and

limitations.

Temperature

ALARM

Stop charging. Wait for the

temperature recovery condition.

Discharging

Under Voltage

ALARM

Stop discharging. Begin charging.

Over Current

ALARM

Stop discharging. Check for current

overload.

Temperature

ALARM

Stop discharging. Wait for the

temperature recovery condition.

8

Need Further Assistance?

Email us @

[email protected]

(OR) Call us @ # (818) 280-3091.

Содержание 48V LYNX

Страница 1: ...w...

Страница 2: ...tions 7 3 5 Control Panel Indicators 8 4 Warnings Precautions 10 5 Parts Components 11 5 1 Installation Safety Guidelines 11 5 2 Parts Components 11 5 3 Environmental Requirements 12 5 4 Battery Insta...

Страница 3: ...ium Ion LiFePO4 LFP Chemistry LED BMS Alarm Indicators Dual Ethernet ports RS485 Communications DIP Dial Switch High quality durable steel construction Standardized 175 amp connector for battery power...

Страница 4: ...ff 5 BB175 Connector Easy and safe connection for charging and discharging 6 Reset Reset battery to default specs 7 RS485 RS485 communication interface 8 ID Dial Switch Assign addresses to each module...

Страница 5: ...arging voltage Charging Current Limit Continuous 90 Amps Discharging Current Limit Continuous 130 Amps Max Peak Discharge Current Over 6 seconds 350 Amps Charge Temp Range 0 55 32 131 C F Discharge Te...

Страница 6: ...ltage 3 45 Volts DC Discharge Voltage Protection Low Voltage Protection Limit Range 2 5 2 3 Volts DC Low Voltage Protection Delay Time 2000 Milliseconds Low Voltage Protection Recovery 3 1 Volts DC Ov...

Страница 7: ...tection High Temperature Protection Value when Charging 60 140 C F High Temperature Protection Release Value when Charging 55 131 C F Low Temperature Protection Value when Charging 5 23 C F Low Temper...

Страница 8: ...he protection is removed Charging Over Current Protection During charging if the current surpasses the protection value the BMS will limit the charging current to less than the protection value Discha...

Страница 9: ...Indicators BMS Protection Indicators When the LED alarm light comes on a BMS protection has been triggered and the battery has been protected Please refer to the table below for individual warning ind...

Страница 10: ...al Flash 1 OFF Warning Flash 1 Flash 2 Protection OFF ON Discharge Normal Flash 2 OFF Warning Flash 2 Flash 2 Protection OFF ON BMS Failure OFF Flash 2 OFF For State of Charge SOC each ON LED indicate...

Страница 11: ...s or any other heat source at a minimum distance of two feet away from the batteries Disconnect batteries immediately if during operation or charging they emit an unusual smell develop heat or behave...

Страница 12: ...ondition Use a screwdriver with a rubber coated handle When your battery has been charging and has come to maximum charge up to 58 8V max your battery may experience a slight voltage drop either immed...

Страница 13: ...on Step 1 Mounting Brackets Installation Ensure mounting brackets are attached to both sides of the battery If they are not attached locate the mounting brackets and hardware within the shipment packa...

Страница 14: ...ore connecting each battery to its respective rack busbar using the connection cable provided Step 3 Connecting to the Busbar Connect all sources and loads to the rack busbar observing proper polarity...

Страница 15: ...Module 4 ON OFF ON OFF 5 Module 5 ON OFF OFF ON 6 Module 6 ON OFF OFF OFF 7 Module 7 OFF ON ON ON 8 Module 8 OFF ON ON OFF 9 Module 9 OFF ON OFF ON 10 Module 10 OFF ON OFF OFF 11 Module 11 OFF OFF ON...

Страница 16: ...r any anomalies If any batteries alarm light turns on any batteries circuit breaker turns off a fuse blows arcs or smokes immediately turn off all battery modules sources and loads and correct the fau...

Страница 17: ...ree recycling at the end of life of all our products We are willing to help our customers ship our products back to our facilities and will recycle them at no extra charge to our customers We maintain...

Страница 18: ...arrantied component inspections initiated after the first 30 days of ownership Please note some battery returns may require special documentation and packaging and these instances will encounter extra...

Отзывы: