Cell Temperature Protection
If the temperature of any cell surpasses 70°C or drops below 0°C, the BMS will stop
charging. If the temperature of any cell surpasses 75°C or drops below -20°C, the
BMS will stop the discharge.
PCB High Temperature Protection
If the PCB temperature surpasses 95 °C, the BMS will stop charging or discharging
until the temperature drops below the recovery value.
Cell Balancing
During charging, if all cell voltages are greater than 3.4V and the voltage difference
between cells (ΔU) is > 40mV (ΔU = Max. Cell Voltage - Min. Cell Voltage), the BMS
will trigger the balancing process.
3.4 Control Panel Indicators
BMS Protection Indicators
When the LED alarm light comes on, a BMS protection has been triggered and the
battery has been protected. Please refer to the table below for individual warning
indicators and their recovery process and take the appropriate action.
State
Protection
Indicator
Recovery
Charging
Over Voltage
ALARM
Stop charging. Check module
voltage and charger.
Over Current
ALARM
Stop charging. Check settings and
limitations.
Temperature
ALARM
Stop charging. Wait for the
temperature recovery condition.
Discharging
Under Voltage
ALARM
Stop discharging. Begin charging.
Over Current
ALARM
Stop discharging. Check for current
overload.
Temperature
ALARM
Stop discharging. Wait for the
temperature recovery condition.