BIG GOOSE BG-101 Скачать руководство пользователя страница 2

Check that the float is in the lower position. 

If it is not, lower the float using your finger, as 

shown on (Fig. 4). 

 

At start up, check initial average load. 

 

With unit on, test switch by raising float as 

shown. Unit should stop running if switch is 

correctly wired. 

 

To test switch responsiveness, fill pan with 

water to ensure that the switch stops the unit 

before the pan overflows; once confirmed, 

remove the water.

a.

b.

c.

d.

TEST THE FLOAT SWITCH

4.

WIRING THE BG-101 IN A 

CONVENTIONAL HVAC SYSTEM

(To ensure proper performance of product, 

instructions must be followed.)

Ensure the power is disconnected to the unit at 

the main panel prior to moving to the next step. 

Refer to the appliance manufacturer’s installation 

and operating instructions and also review wire 

layout in their instructions. 

 

Locate the Red wire coming from the 24 volt 

thermostat “R” terminal. 

 

NOTE: If not present, it is recommended that an 

inline fuse to protect 24-volt circuit be installed.

Disconnect or cut red wire. Connect one of the 

long wires of the BG-101, using a wire nut, to the 

thermostat side of the circuit. Connect the other 

long wire of the BG-101, using a wire nut, to the air 

handler side of the circuit or to the terminal in the 

unit.  Incorporating both switch wires in the red 

circuit will shut the unit off (fig.3) 

INSTRUCCIONES

 

ESPANOL

Visite en línea para obtener instrucciones en español 

BigGoose.com/instructions/

For warranty information, please go to 

www.biggoose.com

UL 508  APPROVED

 

40-001007 

REV S

Fig. 3

Fig. 2

Typically Red 

Normally Closed

Normally Closed

Fig. 4

1.

2.

3.

24 volts AC, 4 Amps  

US Patents Pending

Отзывы: