background image

IS200 Electro-Hydraulic Actuator Positioner 

 

 

Orange Instruments Limited. 

Drwg. No.: 1357-007     Issue : K     Date : 07/10/2013          Page : 

3 of 9 

Iss c - Certificate number added.   Iss D - Ta changed to -20 to +60    
Iss E - Details of fail modes, timers and retrans. O/P added.   Retrans. Signal barrier changed to KFD0-CC-Ex1  
Iss F 

– Details of change in Max/min on & off times + addition of 10R in line with pos o/p –ve 

Iss G 

– Stepping times range change to allow finer adjustment 15/11/2007 

Iss H 

– CE Cert. of Conformity details added, Ta to –40degC, 60079:0,26 mods 25/06/2008 

Iss J 

– Harmonised standards in C of C modified to meet current status 04/08/2008 

Iss K -  Markings changed to meet EN 60079-0:2012 02/10/2103 
ATEX Certified Equipment - Change Authority ATEX Manager ONLY 

Operation 
 

The IS200 is designed for the closed loop positioning of electro-hydraulic actuators. 
The instrument compares two analogue signals, one representing the desired position (command signal) and the other 
representing the actual position (feedback signal) of the actuator. 
A difference between these two signals will cause one of the IS200 outputs to operate, driving the actuator to the desired 
position. 
A positional Dead-

zone may be adjusted to overcome “hunting” problems associated with mechanical overrun of the 

actuator. 
The speed of transit of the actuator can be reduced by selecting the stepping mode that provides independently adjustable 
on and off times for the open and close solenoid operation. 
 

Physical 

 
The IS200 is housed in a small DIN rail mounted polyester enclosure measuring 85 x 70 x 58h.   The circuit boards are 
coated with a resist layer that protects the track from moderate condensation and mould growth problems.   Connections are 
via screw terminals with a capacity of 2.5mm

2

 but the use of ferrules or crimps is recommended.   All adjustments are 

accessible on the front panel of the enclosure. 
 

Wiring

 

 

To comply with the IS Certification the IS200 must be wired as shown in the circuit on Page 7.  Wiring should be completed 
by suitably trained personnel taking into account the following notes: 
 

  To ensure RFI compliance the analogue signals MUST be routed in copper braided screened cables with a fill factor 

density of at least 0.7.   

  The screens should be terminated to the metal of the actuator housing, ideally at a suitable metal cable gland. 

  Signal cables should be routed separately from power and switching conductors.  

 

  Ensure that all supply and signal barriers are present and correctly connected and supplied with power from the safe 

area.

 

 
Positioner set-up 

The solenoid sense and command signal default mode are set up by a sequence of push button operations at power up.  
These operations will affect the outputs to the solenoids so it is important that the actuator is isolated hydraulically during 
these operations to avoid unwanted movement of the actuator.   Note that a low value resistor, 10R, might be required in the 
negative lead, Terminal 19, of the retransmitted signal output to reduce instability in the IS200 / barrier loop. 
 

Setting solenoid operating sense 

If the actuator has a spring assisted return to a default position it may be necessary to change the sense of the output 
solenoid such that at the desired balance point one of the solenoids is energised thus holding the actuator position against 
the spring.   A one-off operation of the positioner will store the choice in non-volatile EEPROM memory. 
 

1.  Hold in the CALIBRATE pushbutton and apply power to the positioner. 
2.  The CALIBRATE LED will light continuously and pressing the manual DECREASE and INCREASE pushbuttons will 

cause the appropriate DECREASE and INCREASE LEDS to “toggle” on and off. 

3.  Select the pattern of LEDs to reflect what is required at balance e.g. for an actuator that fails downscale the 

DECREASE LED should be lit. 

4.  When satisfied press the CALIBRATE button again. 
5.  Remove power from the positioner. 

 

Содержание IS200

Страница 1: ...IS200 Intrinsically Safe Actuator Positioner Operation Installation and Maintenance Manual Operation Installation and Maintenance Manual ORM0006 IS200 O M Rev 0...

Страница 2: ...co uk Northampton NN3 6XF United Kingdom The IS200 has the following specific approvals Name and Type ACTUATOR POSITIONER TYPE IS200 Certificate Number Baseefa 03ATEX0686X Specific Marking of Explosi...

Страница 3: ...t panel of the enclosure Wiring To comply with the IS Certification the IS200 must be wired as shown in the circuit on Page 7 Wiring should be completed by suitably trained personnel taking into accou...

Страница 4: ...s required the ON and OFF timers for the open and close solenoids have to be set This operation is best performed when the actuator hydraulics are isolated but the settings can be trimmed during norma...

Страница 5: ...sh twice briefly every second 6 Use the INCREASE and DECREASE buttons to set the actuator to the required position for the maximum 20mA command signal As before this can be any position within the mec...

Страница 6: ...standards in C of C modified to meet current status 04 08 2008 Iss K Markings changed to meet EN 60079 0 2012 02 10 2103 ATEX Certified Equipment Change Authority ATEX Manager ONLY IS200 dimensions a...

Страница 7: ...y Safe barriers before connection to the IS200 See circuits on Page 7 COMMAND SIGNAL INPUT 4 20mA nominal 240R input impedance ANALOGUE POSITION OUTPUT SIGNAL 0 4 9V can be calibrated anywhere in this...

Страница 8: ...2 24V dc 7 8 16 15 16V 1 2 24V dc 7 8 3 4 16V 1 2 24V dc 7 8 8 9 4 20mA 1 5 6 4 20mA Command MK35 Li Ex0 2 24V dc 7 8 20 21 0 4 9V 1 9 8 KFD0 CC Ex1 2 18 19 6 7 2 1 13 14 or Fault O P ESD Soln Instume...

Страница 9: ...16V Always at supply potential 2 Increase Solenoid ve output 16V Set to 0V to energise solenoid 3 Increase Solenoid Supply ve 16V Must be an isolated IS supply 4 Increase Solenoid Supply 0V 0V 5 No c...

Отзывы: