background image

EX200 Electro-Hydraulic Actuator Positioner 

 

 

Bifold Orange Limited. 

 

Drwg. No.: ORM0001     Issue : 1    Date : 24/06/2015          Page : 

9 of 20 

 

First time operation 
 
WARNING!! 
The actuator and associated mechanical equipment connected to it could possibly move in an unpredictable 
manner during initial calibration.  Ensure that all personnel take appropriate precautions.   

 
1.  Ensure that any end of travel limit switches and mechanical stops are correctly adjusted before operation. 
2.  Apply power and provide the 4-20mA command signal.  Press the Auto/Manual Switch.   Check that the Auto/Manual 

LED is lit. 

3.  Operate the Increase and Decrease buttons and confirm that the actuator moves as required.

 

4.  The system must be calibrated before automatic mode is selected.

 

 
Calibration 

Calibration can only be carried out local to the EX200 unit so it is essential to have purged the area in order to access the 
EX200 and provide local command signal injection.   An alternative is to use the remote DCS to inject and read the actual 
position signal and transfer the information by handheld radio.  If this approach is used ensure that the radio is operated 
2m or more from the EX200 and associated wiring. 

 
A command signal is required, normally in the range 4-20mA (Terms 20+ and 21-) and a DVM with a 0-200mA range to 
read the retransmitted position signal (Terms 13+ and 14-). 

 

1.  Press the CALIBRATE button, and hold until the CALIBRATE LED goes out.  When the button is released, the 

CALIBRATE LED will flash briefly once per second. 

2.  The positioner has been switched automatically into Manual, non-stepping mode so use the INCREASE / 

DECREASE buttons to set the actuator to the required position for the minimum, 4mA command signal.   This 
must be the position the DEC solenoid will drive the actuator to. 

3.  Set the command signal to 4mA. 
4.  Adjust the CAL1 potentiometer to give the required output for the chosen position.   Note that this not need be 

4mA to match the command signal, but can be any value in the range 0.5mA to 22mA. 

5.  Press and hold the CALIBRATE button until the CALIBRATE LED goes out.   Release the button and the 

CALIBRATE LED will flash twice briefly every second. 

6.  Use the INCREASE and DECREASE buttons to set the actuator to the required position for the maximum, 20mA 

command signal.  This must be the position the INC solenoid will drive the actuator to. 

7.  Set the command signal to 20mA. 
8.  Adjust the CAL1 potentiometer to give the required output for the chosen position.   Note that this not need be 

20mA to match the command signal, but can be any value in the range 0.5mA to 22mA. 

9.  Press and hold the CALIBRATE button until the CALIBRATE LED goes out.   Release the button to complete the 

calibration sequence. 

 

 
General operation 

When calibration has been completed the EX200 reverts to automatic mode and to stepping operation if DIL switch 4 is 
set ON.   The actuator should now follow the command signal input and move to the desired position.    
If there is any instability in positioning, particularly if the hydraulic flow rate is high, then the DEADZONE potentiometer 
can be set progressively clockwise, half a turn at a time, until stable positioning following a step change can be achieved. 
 

 
Normal operation - fault detection 

If the command signal or the feedback signal goes towards zero (less than 0.5V at the terminals, across any shunt fitted) 
then the selected fail mode will operate and the OK light will be removed.   The actuator will either freeze position, drive 
down or drive up and the control to the auxiliary solenoid will be removed.   The system will recover to normal operation 
when the signals are re-instated.   If the external fault contact is broken, then the fault output will change, as will the 
auxiliary solenoid if they are linked as described in Positioner Set-up.   The fault condition is reset as soon as the external 
fault contact is restored.  If the unit is in "stepping mode" (DIL switch 4 = ON) then failure mode drive can be either in the 
selected stepping mode or, if DIL switch 1 is ON, then the unit will fast-fail to its default position.  
 
For the EX200 with the “Hart” Communication option, if the external fault contact is broken, then the fault output will 
change, as will the auxiliary solenoid if the appropriate bit is set, via HART in Command 129 (81h), otherwise the fault 
input operates only the fault output.   The fault condition is reset as soon as the external fault contact is restored.  If the 
unit is in "stepping mode" (DIL switch 4 = ON) then failure mode drive can be either in the selected stepping mode or, if 
DIL switch 1 is ON, then the unit will fast-fail to its default position.  If remote changes are enabled then all the above 
option can by changed via HART in Command 129 (81h). 

Содержание EX200

Страница 1: ...EX200 ELECTRO HYDRAULIC ACTUATOR POSITIONERS Operation Installation and Maintenance Manual ...

Страница 2: ...ing option timers 7 Setting the HART private command enable and remote slow fast operation 8 First time operation 9 Calibration 9 Normal operation fault detection 9 Self contained operation 10 Maintenance 10 EX200 H Hart Version HART Revision 7 16 bit Manufacturers and Device ID 11 HART Command Summary 11 Universal Commands 11 Common Practice Commands 11 Private Commands 11 Specification 13 EX200 ...

Страница 3: ...rol of the position driver including electro hydraulic actuators and reversing ac motors with the addition of suitable relays contactors or motor control equipment The EX200 can accept positional feedback from a three wire potentiometer or a position transducer with a current output All signals and power supplies are referenced to power supply zero ensuring safe connection to centralised digital c...

Страница 4: ...mounted polyester enclosure measuring 85 x 70 x 58h The circuit boards are coated with a resist layer that protects the track from moderate condensation and mould growth problems Connections are via screw terminals with a capacity of 2 5mm 2 but the use of ferrules or crimps is recommended All adjustments are accessible on the front panel of the enclosure Initial configuration adjustments are via ...

Страница 5: ... up The EX200 comes with two communication options selected within the part number system Standard and the Hart Protocol Setup of instrument functions differs for this communication selection See below for position of jumper links required for EX200 set up Figure 1 EX200 Standard Jumper Link Options Figure 2 EX200 Hart Jumper Link Options ...

Страница 6: ...lect a factory set unit for a spring to close actuator please add SC where indicated in the part number selection chart and for spring to open add SO Setting retransmitted actual position signal drive type Sourcing or Sinking Links SO and SI can select the excitation for the retransmitted actual position signal Link SO selects INTERNAL 12V excitation and Link SI selects EXTERNAL 12 30V excitation ...

Страница 7: ...only triggers fault output In External fault triggers fault output auxiliary solenoid output and instrument default mode For the EX200 with Hart Communication option this is changed via HART in Command 129 81h Setting the self contained pump control options The EX200 has an output to control a hydraulic pump supplying power to the actuator The pump can be configured to operate on demand when a cha...

Страница 8: ...gured to enable disable reception of a private command used to remotely set the pulsing mode timers and the dead zone The procedure also allows local resetting of the HART command allowing local adjustment of stepping times and selection of continuous or stepping operation should HART communications fail 1 Hold in the CALIBRATE pushbutton and apply power to the positioner 2 Release the CALIBRATE p...

Страница 9: ...mA command signal This must be the position the INC solenoid will drive the actuator to 7 Set the command signal to 20mA 8 Adjust the CAL1 potentiometer to give the required output for the chosen position Note that this not need be 20mA to match the command signal but can be any value in the range 0 5mA to 22mA 9 Press and hold the CALIBRATE button until the CALIBRATE LED goes out Release the butt...

Страница 10: ... The unit must be left for 30 minutes with power off before the cover is removed To maintain an IP66 environmental rating after removing the Ex d enclosure cover the male threads of the enclosure should be liberally coated with Molykote BR2 Plus grease Please contact Bifold Orange if you have difficulty in sourcing this material The cover should be tightened sufficiently such that the cover to bod...

Страница 11: ...he positioners The body of the message is 11 bytes Command 128 80h Device Specific Command Read positioner parameters Received Data None Response Data 0 1 INC off time H L 2 3 Dec off time H L 4 5 INC on time H L 6 7 DEC on time H L 8 9 Dead zone H L 10 Remote enable byte Command 129 81h Device Specific Command Write positioner parameters Received Data 0 1 INC off time H L 2 3 Dec off time H L 4 5...

Страница 12: ...tepping mode via DIL switch position 4 factory default Bit 3 Set stops the actuator and ignores changes in command signal if Bit 1 is set Clear positions to command signal factory default Bit 4 Set Drives actuator down if Bit 1 is set Clear positions to command signal factory default Bit 5 Set Drives actuator up if Bit 1 is set Clear positions to command signal factory default Note only one of bit...

Страница 13: ...h 2 No function DIP Switch 3 Select stepping mode timers DIP Switch 4 Select stepping mode DZ Potentiometer to set positioning dead zone clockwise to increase CAL1 Calibration adjustment and ON time for stepping mode CAL2 Adjustment for OFF time for stepping mode INTERNAL LINKS Output sense one position or must be selected for each output even if the output is unused LINC and Increase solenoid sen...

Страница 14: ...to 0V to energise output 8 Fault output ve output max 36V Always at supply potential 9 Pump output ve output max 36V Set to 0V to energise output 10 Pump output ve output max 36V Always at supply potential 11 Instrument Supply ve 15 to 36V 12 Instrument Supply 0V 0V 13 Actual position signal ve 12V 30V Scaled to actuator movement 14 Actual position signal ve 0V set in range 0 5 22mA 15 Instrument ...

Страница 15: ...k Potentiometer Decrease Solenoid 200R or greater Feedback Pot Alternative Device 4 20mA EX200 POSITIONER 0 5 22mA Actual Position 2 Solenoid Increase 1 Solenoid Increase 9 Output Pump control 24V 10 External relay contactor coil Pump supply AC or DC Pump fuse Hydraulic Pump 24V dc open drain active when healthy 16 17 18 15 19 5V 5V 5V 0V 0V External fault High pressure switch Low pressure switch ...

Страница 16: ...osure Dimensions and Front Panel Size 70mm wide 58mm high 85mm deep Weight 0 25kg Enclosure Lexan Top cover Noryl Base section Equipment rating IP40 The EX200 in the din rail mount enclosure can be fitted on Standard Symmetric EN50054 component mounting rail 35 x 7 5 Use a purpose designed tool for adjusting small potentiometers on the front panel ...

Страница 17: ... Positioner Bifold Orange Limited Drwg No ORM0001 Issue 1 Date 24 06 2015 Page 17 of 20 EXD2010 Ex d Enclosure System Typical Layout Typical layout drawing for information only See product specific layout drawings for precise details ...

Страница 18: ...e Limited Drwg No ORM0001 Issue 1 Date 24 06 2015 Page 18 of 20 EXD2010 Ex d Enclosure System Typical Wiring Drawing Typical system wiring diagram for information only shown with all feedback options See product specific hook up drawings for precise details ...

Страница 19: ...EX200 Electro Hydraulic Actuator Positioner Bifold Orange Limited Drwg No ORM0001 Issue 1 Date 24 06 2015 Page 19 of 20 EX200 in EXD2010 Ex d Enclosure PCB Assembly ...

Страница 20: ...t must be installed by skilled electricians or instructed personnel in accordance with National Legislation and relevant technical standards The equipment must NOT be operated in Zone 0 hazardous area The technical data listed on the enclosure label must be observed Changes to the design of the equipment are not permitted The equipment shall only be operated as intended and only in an undamaged co...

Отзывы: