IMPORTANT
Before using the space heater, please read carefully all the instructions for use described below and follow the
indications scrupulously.
The manufacturer cannot be held responsible for damage to persons and/or property caused by improper use of
the equipment.
This instruction manual is an integral part of the equipment and must therefore be kept carefully and passed on
with the unit in the event of a change of ownership.
DESCRIPTION
Space heaters
are designed for non domestic heating of
medium and large ventilated premises, for which mobile heating
system is required in accordance with EN 1596:2008.
Warning
DO NOT USE TO HEAT HABITABLE AREAS OF
RESIDENTIAL BUILDINGS.
REFER TO NATIONAL REGULATIONS FOR USE IN
PUBLIC BUILDINGS.
Space heaters can be run on propane gas (G31) or on L.P.G.
(butane G30 and propane G31) according to the different gas
categories indicated on Tab. I and shown on the heater
identification plate.
Space heaters are of the direct combustion type. The air is
heated by the thermal energy generated during combustion and
is then conveyed to the room to be heated with the products of
combustion: the room must in any case be suitably ventilated in
order to ensure adequate air circulation.
Various safety devices trip in the event of serious malfunction:
• the thermocouple and the thermal gas valve trip closing the
gas flow if the flame is irregular or if it goes out;
• the overheating thermostat LI trips when the temperature of
the combustion chamber exceeds the safety limit;
In each of the cases described above, the space heater stops
working in lock out condition.
Warning
You must always identify the cause of the “block”
and eliminate it before restarting the heater (see:
“FAULTS, CAUSES AND REMEDIES”).
GENERAL ADVICE
Installation, setting up and use of the hot air generator must be
effected in accordance with the applicable regulations and laws
relating to the use of such equipment.
The minimum distance from surrounding walls and/or ceiling
must be at least 2 m.
Warning
Do not use the heater on floors made with
flammable materials.
Warning
Use in basements or below ground level is
hazardous because of gas stagnation.
Make sure that:
• The instructions in this manual are carefully followed;
• The generator is not installed in an area where there is a
high risk of fire or explosions;
• No flammable materials are stored in the vicinity of the
heater (the minimum distance must be at least 3 m)
• A check is made that there is no overheating of walls,
ceilings or floors made of flammable materials
• All precautions have been taken to prevent fires;
• The premises in which the heater is installed are sufficiently
ventilated for the burner requirements; in particular the limits
regarding the quality of the air in the room to be heated
must be complied with, as prescribed by the applicable
national or local laws or, in the absence of any standards
and/or indications, in compliance with the provisions of EN
1596:2008:
• minimum room volume must be measured with thermal
power/volume ratio equal to 100 W/m
3
. Room volume
must NEVER be less than 100 m
3
;
• a minimum ventilation area of 25 cm
2
per kW of thermal
power must be provided, the minimum being 250 cm
2
,
divided equally between the upper and lower part.
• The air suction and/or supply hoses are not blocked in any
way, there are not sheets or covers resting on the machine
or walls and bulky objects near the generator;
• The generator is placed near a power switchboard having
specifications that conform to those declared;
• The unit is placed in a stable position
• The hot air jet is directed towards the cylinder.
• The heater is regularly monitored during operation and
checked before being started up;
• At the beginning of each working period, before plugging it
into the electrical power supply, a check is made that the
fan moves freely;
• At the end of each working period the main switch is
disengaged and supply power cord removed, main gas
stopcock is closed and gas tube disengaged and sealed.
Warning
This unit may not be used by persons (including
children) with reduced physical, sensorial or
mental capacities or with limited experience and
familiarity unless they are under supervision or
instructed on how to use the equipment by the
person responsible for its safety.
INSTALLATION INSTRUCTIONS
Warning
All the operations described in this section must
only be performed by professional and skilled
personnel.
POWER CONNECTIONS
Warning
The power line of the generator must be fitted with
an earth lead and a residual current circuit breaker.
The supply cable must be connected to a
switchboard that has an isolation switch.
All the control and safety devices are already electrically
connected.
Before switching on the heater, and therefore, before plugging
it into the electrical power supply, a check must be made that the
power supply specifications are the same as those stated on the
identification plate.