Technical Status: 11/2010     Page 5

Gas Detector

Operating and Installation Instructions

ExDetector HC 150 / HC 150-K

Adjustment

Important note

!

The relevant regulations for work in areas where there is an explosion
hazard must be observed without fail.

The following accessories and equipment are required:

Voltmeter

Test gas set consisting of:
-

1 x Minican of test gas (e.g. 40% LEL)

-

1 x Minican of synthetic air

-

Pressure regulator unit with regulating valve and flow meter.

-

Test gas cap (see Accessories)

-

Measurement leads (see Accessories)

Adjustment

Remove the cover from the housing.

Important

: before opening make sure that an explosive atmosphere is not

present.

Fit test-gas cap to the sensor.

The flow rate of the two gases should be 10 to 15 l/h (second graduation).

Setting the bridge voltage

Apply zero-response gas (synthetic air) if the environment contains the gas
to be detected.

Connect the voltmeter at the measurement socket „Br“.

Wait for the voltage reading to stabilise.

Adjust the „Br“ potentiometer until the voltmeter reads 0 mV.

Setting the base current to 4 mA

Connect the voltmeter at the „0.4-2V“ socket.

Wait for the „0.4-2V“ voltage signal to stabilise.

Adjust the „N“ potentiometer until the voltmeter reading is 400 mV (4 mA).

Setting the 4-20 mA output current

Apply test gas of a known concentration C1.

Wait for the „0.4-2V“ voltage signal to stabilise.

Adjust the „V“ potentiometer until the voltage corresponds to the value U

S

U   = 0,4V +1,6V  

C

Cmax

1

C  = testgas concentration in % LEL

1

max

C        = Measuring range (100%LEL)

U  = Signal voltage

s

24VDC
4-20 mA
GND

0,4-2V

Br

N

V

Br

4
5
6

1
2
3

Measuring the sensitivity (bridge voltage)

Connect the voltmeter at the measurement socket „Br“.

Note the voltage reading U

Br

 in mV.

Remove the test gas.

Write a test report.

Testing sensor sensitivity E:

Calculate E using the following formula:

U

BR

 = bridge voltage

C

1

 = known test gas concentration

If sensor sensitivity E < 0.5, the sensor must be replaced.

If sensor sensitivity E is below 50% of the E value from initial adjustment
(works calibration), the sensor also must be replaced.

E =

U

BR

 (mV)

C

1

 (%UEG)

Содержание ExDetector HC 150

Страница 1: ...Gas Detection and Warning Systems Operating and Installation Instructions ExDetector HC 150 ExDetector HC 150 K...

Страница 2: ...collection point and a possible ignition source Consider the density of the gas For gases with a lower density than air for example methane the detector must be located above a possible leakage point...

Страница 3: ...sing in the presence of an explosive atmosphere Terminal Assignment Max outside diameter of cable 10 mm Three core cable with screen Terminal assignment 24VDC 4 20 mA GND 0 4 2V Br N V Br 4 5 6 1 2 3...

Страница 4: ...on hazard Ex RL Rules for avoiding dangers from a potentially explosive atmosphere with a collection of examples Explosion Protection Rules Example Connection to GMC8022 Screening The screen is to be...

Страница 5: ...or the voltage reading to stabilise Adjust the Br potentiometer until the voltmeter reads 0 mV Setting the base current to 4 mA Connect the voltmeter at the 0 4 2V socket Wait for the 0 4 2V voltage s...

Страница 6: ...ing sensor Procedure Switch off the power supply to the detector Remove the housing cover Disconnect the leads from terminals 4 5 and 6 Undo the locknut Unscrew the sensor Screw the replacement sensor...

Страница 7: ...ust be observed Further relevant standards DIN EN 60079 14 Electrical apparatus for explosive gas atmospheres Electrical installations design selection and erection DIN EN 60079 17 Electrical apparatu...

Страница 8: ...ctor HC 150 HC 150 K Bieler Lang GmbH Gas Detection and Warning Systems PO Box 1129 D 77842 Achern Oberkirchstr 19 21 D 77855 Achern Telephone 49 0 78 41 69 37 0 Telefax 49 0 78 41 69 37 99 E mail inf...

Отзывы: