UPSI-IP-3 Series
Revision 1-0
20
F General Data
F1 Assembly and installation advice
The installation of devices that are not ready to be plugged in is to be carried out by the respec-
tive network operator or by a registered specialist company, who will also assist in obtaining the
approval of the respective network operator for the installation of the device.
F2 Convection, installation position and mounting
In order to achieve the best possible convection, the device has to be mounted vertically on a stable wall or
other surface. This is the only way to operate in the specified technical areas. Other installation methods are
possible, taking into account the reduced performance range.
Required fastening aids such as dowels or other systems are to be selected according to the mounting surface
used.
A distance of at least 100 mm (10 cm) in all directions from the housing wall to other, neighboring devices
should be maintained. The devices comply with the IP protection class 65.
D
C
B
A
A 4 x Hex spax screw,
6 mm x 60 mm or longer
B 4 x tension washer, 6.4 mm,
DIN 6796
C 4 x 8 mm mounting dowels for wall
attachment
D 8 mm hole
62
402
8
(4x)
Drilling template, dimensions in mm
Содержание UPSI-IP-3 Series
Страница 3: ...UPSI IP 3 Series Revision 1 0 3...