UPSI-2412DPx
Revision 1-1
25
CONNECTOR
PART NO.
COUNTERPART NO.
V
IN
/V
OUT
Würth Elektronik 691317510004 Würth Elektronik 691340500004
RL
Würth Elektronik 68800211722
Würth Elektronik 688002113322
USB
Würth Elektronik 61400416121
USB type B connector
RS232
D-Sub9 Female
D-Sub 9 Male
F7 Overview connector / counterpart with description / Scope of delivery
SCOPE OF DELIVERY
QUANTITY
DESCRIPTION
1x device
UPSI-2412DP2 or UPSI-2412DP3 - DC UPS
1x
V
IN
/ V
OUT
connector counterpart
1x
Relay cable, 50 cm, AWG 22
F8 Charging time
Charging times depend on energy storage, input voltage and the load current.
F9 Reverse polarity / Overload / Short circuit
Reverse polarity:
The device has passive reverse polarity protection at the input. In the event of reverse polarity, the input fuse
trips irreversibly and the device goes into a safe state.
Overload:
If the load current at the output is too high, the device switches it off. For maximally allowed current values
and peak current values refer to chapter D „Technical Data”. The status LED indicates the error status by means
of a very rapid flashing sequence. A restart attempt occurs every 10 seconds in normal mode. During battery
mode there is no restart attempt.
Short circuit:
In the event of a short-circuit at the output of the UPS, the output is immediately disconnected (<5 ms). The
status LED indicates the error status by means of a very rapid flashing sequence. A restart attempt occurs every
second in normal mode (non-latch). During battery mode there is no restart attempt. The impact of a short-
circuit to the device depends on length and diameter (impedance) of the output wiring. In case of a short-circuit
directly at the plugs a damage of the device can occur.