let is on your left. Although water piping 
throughout your structure may be other 
than copper, we recommend that copper 
piping be used for at least 0.92 m before 
and after the heater. Keep water inlet pipe 
to no less than 1/2” diameter to allow the 
full flow capacity.

2. Remember that water pressure must be 

sufficient to activate the heater when 
drawing hot water from the top floor. If the 
hot and cold connections to the heater are 
reversed, the heater will not function. 1/2’’ 
copper or brass fittings work best when 
connected to the connectors. No pipe 
dope or thread tape is to be used at this 
joint. Be certain there are no loose particles 
or dirt in the piping (Figure 5.9).

3. Water pressure must be sufficient to ac-

tivate the water heater, the maximum 
pressure for the appliance is 10 bar, even 
with the effects of water dilation, the water 
pressure in the appliance shall not exceed 
this value.

•  Hot water outlet

1. It is recommended that copper pipe is 

used to connect the hot water outlet to 
the installation hot water distribution pipe 
work.

Installation of the flue

•  Flue duct installation of forced-exhausted 

gas water heater (C13 type).

This product is forced exhaust type gas water 
heater; it can be used only after the flue duct 
is installed according to the requirements and 
can exhaust the waste gas to an outdoor area. 
It’s not allowed to use the gas water heater 
without installing the flue duct correctly.

Please follow the below requirements during 
the installation of flue duct:

1. The appliance is set up for connection to 

a 60/100 coaxial air intake and flue gas 
exhaust ducting system. For split types of 
suction and exhaust, using the specified 

adapter (Figure 5.10). If the specified adapt-
er is used, the path of the flue gas exhaust 
and combustion air channels must be the 
same and must leave the installation room 
on the same wall at the minimum distance. 
If the flue duct is too short, you can extend 
it (Figure 5.11 and Figure 5.12). Check the 
flue duct and see if there is any damage or 
leakage every year.

2. The length of the flue duct should be 

less than 3 m, and the number of elbows 
should not be more than 3 (one elbow is 
the equivalent to 1 m of straight pipe).

3. The horizontal distance of the flue duct is 

the shorter the better. The flue duct end 
should have 2° downward inclination (Fig-
ure 5.12), so as to let the condensing water 
flow out.

4. The distance between the flue duct and 

combustible materials should be more 
than 150 mm. If the flue duct needs to 
get through the combustible materials or 
wall, it should use the heat shield material 
to pack the flue duct with a thickness over 
20 mm (Refer to Figure 5.4).

5. It is a UK legal requirement that the flue is 

sealed to the wall using a sand and cement 
mortar.

6. The flue duct should be fixed tightly. 

Self-adhesive may be used on joints the 
waste gas going back into the room.

Figure 5.10

Содержание MULTIPOINT 14S

Страница 1: ...User manual and installation instructions MULTIPOINT...

Страница 2: ...ric accidents e g injuries or bruises DANGER Instructions marked with this symbol must be observed to avoid electri cal accidents electrocution DANGER Instructions marked with this symbol must be obse...

Страница 3: ...f freezing empty the water heater of the water it contains In the event of a fault and or poor operation of the unit turn it off refraining from any at tempt to repair it or any direct intervention Ma...

Страница 4: ...re shown on the unit s data plate comply with the following Euro pean Directives Regulation EU 2016 426 on appliances burning gaseous fuels Efficiency Directive 92 42 EEC Electromagnetic Compatibility...

Страница 5: ...revention of freezing 15 4 2 Gas accident prevention 16 4 3 Fire prevention 17 4 4 Carbon Monoxide toxicosis prevention 17 4 5 Abnormal conditions 17 4 6 Scald prevention 17 5 INSTALLATION 18 5 1 Pack...

Страница 6: ...each 0 02 MPa 0 2 bar or a minimum flow rate of 2 5 L min so it could also be used in the residence area with low pressure AI Artificial Intelligent Memory Function The water heater remembers the last...

Страница 7: ...II2H3B P Nom gas supply pressures G20 Pa mbar 2000 20 G30 Pa mbar 2900 29 G31 Pa mbar 3700 37 Min gas supply pressures G20 Pa mbar 1700 17 G30 Pa mbar 2000 20 G31 Pa mbar 2500 25 Max gas supply press...

Страница 8: ...les ignition Destination country GB IE Gas inlet joint G 1 2 G 1 2 Cold water inlet joint G 1 2 G 1 2 Hot water outlet joint G 1 2 G 1 2 Flue duct diameter mm 60 x 100 60 x 100 ErP Data MULTIPOINT 14S...

Страница 9: ...e 3 Thermostat 4 Main board 5 Direct current fan 6 Power cord 7 Flame detector 8 Igniter 9 Earth 10 Display 11 Water inlet temperature sensor 12 Water outlet temperature sensor 13 Water flow sensor 14...

Страница 10: ...T 2 3 Parts 14S 16S Figure 2 2 1 Flue duct connector 2 Front panel 3 Display and control panel 4 Safety valve discharge 5 Hot water outlet 6 Gas inlet 7 Cold water inlet 8 Cold water inlet filter 9 Po...

Страница 11: ...ions 14S 16S Figure 2 3 A Hot water outlet 1 2 B Gas inlet 1 2 C Cold water inlet 1 2 F Safety valve discharge G Cold water inlet filter A F B G C 100 60 79 12 85 130 180 566 602 616 655 187 88 68 88...

Страница 12: ...of gas consumption Adjust temperature adjustment icon Temperature adjustment mode flashing display Always alight non adjustment state Main digital display area In normal operation the tempera ture set...

Страница 13: ...C you must turn off the hot water demand first then you can increase the temperature before turning on again When a water outlet is open but the switch stays in the OFF position the water heater will...

Страница 14: ...he heater starts to work Eco mode Eco display light is bright In Ecomode aftercalculationbythemicrocom puter the water heater automatically adjusts the amount of gas supply This not only saves gas but...

Страница 15: ...own in m3 When the counter has reached 999 m3 it will automatically reset to 0 Cumulative gas consumption and cumula tive amount of water is automatically cleared after power failure The contents of t...

Страница 16: ...gas leak age is detected open the room windows and doors At that moment do not ignite or oper ate the switch of electric appliances or plugs because the flame or electric spark can cause an explosion...

Страница 17: ...the heat exchanger due to long periods of use and affect the combustion performance caus ing Carbon monoxide to increase Therefore contact a qualified person to clean and clear the dust and accumulat...

Страница 18: ...1 Self tapping screws 2 Flue duct C13 type optional 1 5 2 Installation requirements The flue of the gas water heater should be installed through an external wall the heater cannot be installed outdoo...

Страница 19: ...e than 400 mm The power socket must have a reliable earth wire to improve safety It is recommend ed that a neon fused switch socket is used Whenever the water heater is not in use please switch it off...

Страница 20: ...over to be sure that the heater is rated for the same gas to which it will be connected 2 All such pipe shall be either new or previ ously used for no other purpose than con veying gas and must be in...

Страница 21: ...outdoor area It s not allowed to use the gas water heater without installing the flue duct correctly Please follow the below requirements during the installation of flue duct 1 The appliance is set u...

Страница 22: ...13 Flue gas exhaust and air suction duct through external wall in the same range of pressure C33 Flue gas exhaust and air suction duct from outside with roof terminal in the same range of pressure Cau...

Страница 23: ...ALLATION 5 4 Conversion instructions Biasi UK supply this water heater pre set as a Natural Gas or LPG Please ensure you have the cor rect model for your requirements MULTIPOINT 14S MULTIPOINT 16S Fig...

Страница 24: ...ss On Off key to enable the adjustment function and then Up or Down key to adjust the flow rate Figure 5 17 shows the flow rate parameter settings 3 Gas type selection After the gas flow rate is adjus...

Страница 25: ...essure screw and conduct leakage test with fire Note After you modify the secondary pressure wait for 2s or 3s to ensure that the system has recorded the updated the current value You must verify the...

Страница 26: ...ne is the smaller size nozzle the upper row is the larger size nozzle G30 G31 JSQ16L7_06_01B3 Hole 0 62 Hole 0 88 Volume parameter settings Figure 5 17 No Displayed Symbol Parameter Parameter Descript...

Страница 27: ...n 14S G20 1070 20 Pa 250 10 Pa G30 1150 20 Pa 250 10 Pa G31 1340 20 Pa 250 10 Pa 16S G20 950 20 Pa 250 10 Pa G30 1080 20 Pa 250 10 Pa G31 1250 20 Pa 250 10 Pa Attention Conversion to other gases shall...

Страница 28: ...ture is too low and the hot water volume is so high so that it ex ceeds the heater s heating power the outlet water will be not hot enough please reduce the water volume In order to ignite immediately...

Страница 29: ...s valve half on Turn on the main gas valve fully There is air in the gas pipe Constantly continue to turn on and off a hot water outlet High supply gas pressure Contact the installer to check the gas...

Страница 30: ...e If the display still shows the fault code please be sure to close the water valve turn off the power and contact your installer or the manufacturers after sales service Error Code Explanation 01 Inl...

Страница 31: ...f correctly separating the different materials for recycling where possible The installer must dispose of the packaging used to transport the boiler Recycle and dispose of the boiler and any accessori...

Страница 32: ...est e The defect is not due to a ventilation failure or to interruptions to the electric water or gas supply to the system f The product is installed within the mainland United Kingdom and Ireland g T...

Страница 33: ...their responsibility to register with the manufacturer within the allotted time period It is essential that the boiler is serviced in line with the manufacturers recommendations at least annually Thi...

Страница 34: ...High Fire m hr ft hr Burner Pressure Lo mbar Hi mbar Inlet Pressure Dynamic at Hi Fire and all other appliances running mbar Inlet water temp C Water Heater Set Temperature C Maximum Flow Rate Achieve...

Страница 35: ...D No Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Operative ID No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Operative ID No Comments Sign...

Страница 36: ...Biasi UK Ltd Commercial Road Leamore Enterprise Park WALSALL WS2 7NQ Sales Tel 01922 714600 Tech Service Tel 01922 714636 www biasi co uk 1796233511 17962 3351 1 1022 36A5 UK 08 03 2022 N...

Отзывы: