40 RIVA PLUS COMBI MANUAL
15. Commissioning Cont.
Checking the fl ue system and combustion:
15.9
The fl ue system should be visually checked
•
for soundness. Check all clamps, gaskets
and fi xings are secure and tight.
Ensure that the fl ue terminal is sited cor-
•
rectly in accordance with the fl ue fi tting
instructions.
To check the exhaust gas:
Remove the plugs indicated (Fig. 15.11).
•
Insert the analyzer probe in the exhaust
•
gas sampling point or in the air intake
sampling point.
Reference tables are given in the Sec-
•
tions 2 on page 10 of this manual for
proper CO2 levels.
Figure 15.11
Air-Flue exhaust
sampling points
Instructing the user:
15.10
Hand over the User manual, this Installation,Operation and Service manual to the end user
•
and explain how to use the unit in Central Heating mode.
Take the User step by step through the lighting instructions.
•
Show the User how to switch off the appliance quickly and indicate the position of the elec-
•
tric service switch and the boiler on/off switch.
Explain the proper use and adjustment of all system controls; this will ensure the greatest
•
possible safety and fuel economy.
Explain the function and use of the function switch.
•
Explain how to turn off the appliance for both short and long periods and advise on the pre-
•
cautions necessary to prevent damage should the appliance be inoperative when freezing
conditions may occur.
Fill in the details required on the Boiler Guarantee Certifi cate and hand to the User advis-
•
ing them to return the correct section for boiler Guarantee registration. Finally, advise the
User that, for continued safe and effi cient operation, the appliance must be serviced by a
competent person at least once a year.
Useful output
KW
16.7
18.9
21.1
23.2
25.4
27.5
29.6
31.8
BTU/h
56983
64490
71996
79161
86668
93833
101000
108506
Naturel
Pa
inwc.
290
1.16
370
1.48
460
1.84
560
2.24
660
2.65
780
3.13
900
3.61
1040
4.17
m³/h
1.76
2.00
2.23
2.46
2.69
2.91
3.14
3.36
ft³/h
5.77
6.56
7.31
8.07
8.82
9.54
10.30
11.02
Propane
Pa
inwc.
680
1.45
860
1.69
1060
2.25
1270
3.21
1500
4.34
1740
5.62
2000
7.06
2270
8.95
Kg/h
1.3
1.5
1.7
1.9
2.0
2.2
2.3
2.5
lb/h
3.0
3.3
3.7
4.1
4.4
4.8
5.1
5.5
Table 15.1
Содержание M135.30CM
Страница 13: ...RIVA PLUS COMBI MANUAL 13 5 Electric Diagrams Cont 5 1 Sequence of Operation ...
Страница 18: ...18 RIVA PLUS COMBI MANUAL 9 Venting Cont ...
Страница 45: ...RIVA PLUS COMBI MANUAL 45 Vent Part Spares 18 Figure 18 1 Description Order Number Twin pipe kit 10999 0393 0 ...
Страница 46: ...46 RIVA PLUS COMBI MANUAL Figure 18 2 Description Order Number Coaxial flue kit 10999 0387 0 18 Vent Part Cont ...
Страница 49: ...RIVA PLUS COMBI MANUAL 49 ...
Страница 50: ...50 RIVA PLUS COMBI MANUAL ...
Страница 51: ...RIVA PLUS COMBI MANUAL 51 ...
Страница 52: ...17962 1481 0 2508 52A4 USA 20 06 2008 N ...