A. Check alarm or CAT5 cable has not been used to power the device. If it has, the warranty will 
be void. Please remove and replace as per instructions. 
 

Q. The unit powers up but is not showing network reception or will not respond to SMS. 

A. This means the unit is not able to detect the network for some reason. 
-Check the SIM card is activated and has calling credit.  
-Power off the unit, remove the SIM and check it in a mobile phone to verify it can make a call. 
-Check the SIM does not ask for a PIN code when put in a phone. If it does, then disable the PIN 
code request. 
-Check the SIM is a standard voice SIM and not a data only SIM for a tablet. 
-Check the reception is strong. Poor reception is not sufficient. 
- Check alarm or CAT5 cable has not been used to power the device. If it has, the warranty will be 
void. Please remove and replace as per instructions. 
-Power off, remove the SIM, use fine sand paper or a sharp object to lightly clean the SIM pads 
and contacts on the GSM unit. Gently bend the contacts upwards so that they make better contact 
with the SIM and try again. 
 

Q. The caller ID part does not work. 

A. Be sure to program the caller ID part under 72 feature. If your number is a private or number 
withheld, then it will not work. 
-Even if you have already programmed a number to receive a call from the device, if you also 
want that number to have caller ID access, it must be programmed under the 72 feature also. 
-Ensure the number is entered as you would normally dial it from another phone.   
 

Q. The keys do not work when the device calls a phone. 

A. Check if you can hear the relay clicking at the gate when the keys are pressed during a call. If it 
can be heard, then the system is working, check wiring between the relay and the lock or gate 
panel. If the relays do not make a clicking sound, then check this feature on a different mobile cell 
phone or landline. If it works on a different phone, check the settings on the phone in question 
under DTMF tones. 
Failure of DTMF tones to operate correctly is also a symptom of low reception. Check steps above 
on improving reception. Try pressing the buttons longer when attempting to activate the gates or 
door. 
Also check that the relays are not already latched with the *22# command. If they are latched, 
they need unlatched before the trigger keys will work. 
 

Q. The system was operating the gates fine, but now it will not trigger the gates. 

Most of the time, this is cause by the user accidentally latching the relay. This latches the output 
relay permanently on. Send the intercom the following SMS *22#. The device should reply with a 
message detailing the relay status.. If it has been latched, the

n the message will state “the relay is 

ON”. In this case refer to the user guide to read how to unlatch it again. 
 

Q. The unit no longer calls out to phones but I can make a call to it from my phone

– Check there is balance on the SIM card. 

– Switch off the power, remove the SIM, put it into a phone, and check that a call can be made 

from a phone. This will verify if the SIM is still working and in service. 

Change History 

 
Key:  

Содержание Prime

Страница 1: ...nual For Cell Switch Prime GSM Cellular Gate opener and GSM alarm signalling device BFT Americas 6100 Broken Sound Parkway N W Suite 14 Boca Raton FL 33487 www bft usa com Toll Free 877 995 8155 Office 561 995 8155 Fax 561 995 8160 ...

Страница 2: ...Device Pg 6 Internal Clock Function Pg 7 Winter Summer Daylight Saving Pg 7 Set Automatic Triggering Times Pg 7 Delete all Automatic Triggering Times Pg 8 Notification Number Pg 8 Programming as an Alarm Dialling Device Pg 8 Complete List of Parameters Pg 8 Controlling Relays when used as Alarm Pg 10 Control by SMS Pg 10 Check Door Gate Status Pg 10 Setting up the free App Pg 10 Using the Android ...

Страница 3: ...lets and will not work in the unit Power TIP Most technical calls received are due to installers using CAT5 or alarm cable to power the unit Neither are rated to carry enough power 2 amp peak Please use following cable Up to 2 metres 6 feet Use minimum 0 5mm2 18 gauge Up to 4 metres 12 feet Use minimum 0 75mm2 16 gauge Up to 8 metres 24 feet Use minimum 1 0mm2 14 gauge Using insufficient power cab...

Страница 4: ...he door Do NOT force it Connections on the GSM Controller N C COM N O GSM modem N C COM N O Out 1 Out 2 eg 12 24ac dc Optional input trigger for alarm device function Optional exit button triggers output 1 for programmed time 12 24v ac dc Optional gate position limit switch Relay outputs Signal LED CPU Power Micro SIM Insert this way Output Connections Example Do not use a SIM card for a tablet as...

Страница 5: ...utput 1 will be triggered and if the 78 feature is programmed the unit will send an SMS Powering Up Perform a final check of wiring making sure that the power supply is no more than the absolute maximum is no more than 26v AC and ensure the antenna is connected before switching on the power Once the power is switched on the power LED should illuminate TIPS My GSM LED is still searching Check the S...

Страница 6: ...to another network which may have better coverage Programming as a Gate Door Access control Device The unit is able to store up to 100 telephone numbers which can call the intercom and trigger the relay automatically with caller ID Programing text messages must start with a pass code string followed by a command followed by data and each command is separated in the SMS by Send the SMS 20 as shown ...

Страница 7: ... a schedule It will send an SMS to itself to check time every set number of days according to the function below 9999 87 Pass code Function code 1 99 days 0 no SMS sheduling Set Automatic Triggering times This feature is useful to automatically trigger electric gates at pre set times of the day or night For gates not set on auto closing this can be used to have opened and closing times with moment...

Страница 8: ...ster user phone number every time the intercom is used to grant access It will send a SMS any time a relay is activated To use this feature firstly turn the function on 9999 802 change 2 to 1 to disable again Now you must store the phone number which is to receive the notification 9999 78number Now you may store a customised SMS content which will be sent to the stored number 9999 79enter any text...

Страница 9: ...his to avoid voicemail picking up a call 10 99 secs 20 secs 46 Calling time for second number adjust this to avoid voicemail picking up a call 10 99 secs 20 secs 47 Calling time for third number adjust this to avoid voicemail picking up a call 10 99 secs 20 secs Scheduled service calls 77number Store a service number to receive a scheduled call or SMS from the unit Useful for SIM cards which are n...

Страница 10: ...ontrol the relays with DTMF touch tones on their phone as follows Control by SMS This device allows the user to send SMS commands to control the relays as follows 1234 1 Relay 1 momentary trigger 1234 2 Relay 1 latch ON or hold ON 1234 3 Relay 1 unlatch or switch OFF 1234 4 Relay 2 momentary trigger 1234 5 Relay 2 latch ON or hold ON 1234 6 Relay 2 unlatch or switch OFF Check if door or gate is op...

Страница 11: ... App on Android Iphone Android and Iphone users can download an optional app called BFT Cellbox PRIME This makes the procedure of triggering gates and creating automatic trigger times easy for the end user Android Setup Apple Setup ...

Страница 12: ...ult engineers code or user code have been changed from their defaults then please change as required in the relevant section above IMPORTANT On using the app if you receive an error message stating Command Failed go to Settings Application Manager Permissions and turn on all permissions for the app Now you should be ready to use the app Using the App on Android ...

Страница 13: ...intercom for output 2 UNLATCH UNHOLD Press to release a latched relay allow gates to close LATCH HOLD OPEN Press to hold ON the relay Press to change controls from relay 1 to relay 2 useful for pedestrian gates HOME TIME SETTINGS Features such as auto triggering do not disturb activity log NOTIFICATION OPTION Press to setup SMS notifications when gates are triggered ...

Страница 14: ...y trigger gates to perhaps open every morning at a pre set time or close every night at a pre set time TIP Enter times in 24 hour format without any colon E g 10pm should be entered as 2200 select the days and press SAVE Can be used to send a SMS notification to a master user each time someone calls the device and access is granted Toggle the feature on firstly Then enter a phone number which will...

Страница 15: ...ller ID access numbers Check signal strength on your intercom Level 1 31 Must be above 14 for successful operation Check last 20 users who triggered gates including date and time date is international format DD MM YYYY Check the state of both relays ON or OFF ON latched open state Check status of gate limit switch if fitted ...

Страница 16: ...to hold ON the relay TIME SETTINGS Features such as auto triggering do not disturb activity log set clock etc Press to change controls from relay 1 to relay 2 useful for pedestrian gates UNLATCH UNHOLD Press to release a latched relay allow gates to close NOTIFICATION OPTION Press to setup SMS notifications when gates are triggered KEYPAD SETTINGS Not used on this device ...

Страница 17: ...y trigger gates to perhaps open every morning at a pre set time or close every night at a pre set time TIP Enter times in 24 hour format without any colon E g 10pm should be entered as 2200 select the days and press SAVE Can be used to send a SMS notification to a master user each time someone calls the device and access is granted Toggle the feature on firstly Then enter a phone number which will...

Страница 18: ...nd I for dial in caller ID access numbers Check signal strength on your intercom Level 1 31 Must be above 14 for successful operation Check last 20 users who triggered gates including date and time date is international format DD MM YYYY Check the state of both relays ON or OFF ON latched open state Check status of gate limit switch if fitted ...

Страница 19: ... the number is entered as you would normally dial it from another phone Q The keys do not work when the device calls a phone A Check if you can hear the relay clicking at the gate when the keys are pressed during a call If it can be heard then the system is working check wiring between the relay and the lock or gate panel If the relays do not make a clicking sound then check this feature on a diff...

Страница 20: ...v adaptor in kits 2 2 Software feature added for call log to show last 25 caller ID calls 3 2 Main capacitor regulator diode upgraded for 24v dc 4 2 24v ac power board added to allow 24v ac power input 4 6 PRIME model new firmware larger flash storage Micro SIM holder antenna connects direct to PCBA Red colour PCBA all black model design ...

Страница 21: ...P a g e 21 ...

Отзывы: