EI90

Fire damper BSK9

200924.0001_ENG / Sept. 2021   teamfr

ont.se

Options 1 and 2

1.  Create a hole, corresponding to the damper’s nominal 

dime 50 mm, in the building element. 
If installing in plasterboard, a steel reinforcement frame 
of 45x45 must be used. 

2.  The damper is secured flat and tight using fire-retardant 

sealant between the damper and wall/joist structure 
with all fastening lugs, which are opened out. 
Screw Ø 5 mm with a minimum length of 45 mm to be 
used when mounting in drywall. The screw is pulled 
through the reinforcement stud.

3.  Check that the gap between the damper and the wall 

is 25 mm all the way round. Sealing is carried out by 
caulking with mineral wool, min 40 kg/m

3

.

4.  Fit the cover frame against the substrate with suitable 

fixings. Now fasten the frame on the damper with steel 
blind rivets Ø 5 mm through the pre-punched holes in 
the mounting frame. Fit with blind rivets from inside out. 
Ensure that the damper blade runs freely.

Building element (wall or joist structure) in fire resistance class EI90.

Damper’s fire resistance class: EI90 (ve ho i <–> o) S.

EU certificate 0402-CPR-SC1299-13

Option 1                                                                Option 2

5.  When using a Fire damper as a transfer-air or end 

 device, a non-combustible louvre intended for the 
damper must be mounted on the non-connected sides 
of the damper. 
The minimum distance between the damper blade in 
the open position and the louvre is 50 mm.

6.  Connect the actuator device to the control unit and 

carry out a function check.

7.  Install the duct system according to applicable require-

ments. Ensure that connecting ducts systems do not 
affect dampers during fire loading.

•  The shortest distance between dampers must be  

200 mm.

•  The shortest distance to wall/floor must be 75 mm.
•  The damper shaft must be mounted horizontally.

Damper’s nom. 
dimensions 
+ 50 mm

Seal with 
fire-retardant 
sealant

Seal acc. 
to section 3

(Possible 
protective 
grille, see 
section 5)

Fastening 
Ø8 x 65 mm 
for concrete 
or lightweight 
concrete.

Fastening 
lugs

Assembly 
plate RBMP

Steel blind 
rivets fitted 
from inside out

Min. thickness 
125 mm

Floor with fire 
resistance class 
=>EI90. Applies to 
concrete or light-
weight concrete.

Duct

Duct

Installation instructions

Damper’s nom. 
dime 50 mm

Seal acc. 
to section 3

Seal with fire-
retardant sealant

(Possible protective 
grille, see section 5)

Screw 5x45 mm

Fastening lugs

Assembly plate RBMP

Steel blind rivets 
fitted from 
inside out

Reinforcement joist, 
refer to point 1

Min. thickness 95 mm

Mineral wool-insulated 
drywall ≥ 40kg/m3.
Or equivalent wall of 
fire resistance 
class ≥ EI90.

Duct

Duct