Fire damper BSK6

EI60

Installation

BSK6 is installed in duct work separating walls or joist sys-
tems, according to the adjoining installation instructions. 
Should not be installed outdoors or in damp areas.

Actuator

BSK6 is always supplied with an electric safety actua-
tor with spring return complete with thermal sensor with 
pushbutton for local manual operating test. The sensor 
disconnects the power to the actuator if the temperature 
exceeds 72°C inside or outside the damper. 24V actuators 
are always used in connection with the MRB monitoring 
system. Dampers can also be supplied with electric actu-
ator 230V.
Note that the BSK6 damper is always supplied with an 
actuator.

Activation

According to Boverket’s Building Regulations smoke de-
tectors must be verified according to SS-EN 54-7 to acti-
vate dampers. The mandatory thermal sensor closes the 
damper at 72°C according to ISO 10294-4.

Control and monitoring

When the damper is used to prevent the spread of fire and 
combustion gases it must be closed via impulses from the 
smoke detector. This must be fitted in the ventilation duct 
in the proximity of the damper or in another suitable loca-
tion. Smoke detectors are monitored by means of Bevent 
Rasch’s MRB system or the like. The MRB monitoring 
system also performs automatic operating checks on the 
damper every 48 hours and is designed so that faults are 
indicated immediately and the damper closes.  
See www.bevent-rasch.com for further details.

Quick facts

•  Fire resistance class EI60 / EI60S
•  Sizes from 200 x 200 mm to 800 x 800 mm 
•  Prefitted safety actuator 24V or 230V
•  Low weight
•  Easy installation 
•  CE-marked building product according to 15650:2010
•  Available in MagiCAD

Use

Damper in combination with walls or joist systems for fire 
separation of heating, ventilation and air conditioning in-
stallations in buildings. In accordance with the harmonised 
European standard EN 15650:2010. In designs according 
to associated documents, installation instructions and 
when the damper is used in combination with smoke 
detectors and monitoring system (MRB), or the like, the 
spread of fire/combustion gases is prevented. No further 
action against the spread of fire/combustion gases is re-
quired.

Performance

EC certificate according  
to EN 15650:2010

0402-CPR-SC1299-13

Classification of fire resistance  
according to EN 13501-3

EI60 (ve ho i <–> o) S 

For complete classification,  
see the Declaration of Performance.