manualshive.com logo in svg
background image

8

Version 06/14 - Page 5

9.0 feet

10.0 feet

0.0 feet

19.0 feet

TOOLS  NEEDED  FOR  INSTALLATION

• Saber Saw or Jig Saw

• Drill

• 1  1/4" Wood Drill Bit

• Pliers

• Phillips Screwdriver

• Wire Stripper or Utility Knife

• Metal Snips

• Measuring Tape or Ruler

• Level

• Pencil

• Caulking Gun

• Duct Tape

PARTS  SUPPLIED  FOR  INSTALLATION 

• 1 Backdraft Damper

• 1 Vent Grate (for recirculating installations only)

• 1 Vinyl Trim

• 1 Literature Package

PARTS  NEEDED  FOR  INSTALLATION

• 2 Conduit Connectors

• Power Supply Cable

• 1 Wall or Roof Cap

• All Metal Ductwork

PLAN  THE  DUCTWORK

The Cristal HC slideout  rangehood is designed to offer wide flexibility of installations.  

The rangehood can be ducted vertically or horizontally through a 6" round vent.  

The unit can also be installed in a recirculating configuration.  The unit comes 

standard in the top venting position.  

FIGURES 1 and 2

 show vertical and horizontal 

installations for this unit. 

 FIGURE 3

 shows recirculating installation.

The Cristal HC requires 6" round ductwork.  To ensure that the blower performs to 

its highest possible capacity, ductwork should be as short and straight as possilbe.

RECIRCULATING  INSTALLATIONS

For recirculating installations 

(FIGURE 3)

Charcoal Filters

 are necessary. Remove all four grease filters and set aside.  Attach 

one charcoal filter to each end of the blower.  Each charcoal filter attaches to the black grid on the side of the blower.  Rotate 

the filter clockwise to install and counterclockwise to remove 

(FIGURE 3A)

.  Replace all four grease filters.  

Some ductwork 

must be installed

 to exhaust the rangehood back into the kitchen, either at the top of the cabinet or at the face of the soffit.  A 

plastic vent grate 

(FIGURE 3B)

 supplied with the rangehood can be used to cover the duct opening.  This duct work must not 

terminate into a dead air space.

FIGURE  3A

45˚ Elbow

90˚ Elbow

90˚ Flat Elbow

Wall Cap

FIGURE  A

9 Feet Straight Duct

2 - 90˚ Elbows

Wall Cap
Total System

FIGURE  B

3.0 feet

5.0 feet

12.0 feet

0.0 feet

VERTICAL 

DUCTING

FIGURE 2

HORIZONTAL  

DUCTING

FIGURE  1

For direct rear venting 

(FIGURE 2)

, you must 

change the blower position.  Remove the 12 

screws that hold the metal housing to the 

rangehood body.  Remove the 4 screws that 

hold the blower housing to the metal housing.  

Rotate the blower 90 degrees toward the back 

and then flip it over 180 degrees.  Be sure that 

the power supply cable is properly positioned.  

Replace all screws, making sure that they are 

firmly fastened.  

cabinet

ceiling

6” round

duct

hood

cabinet

ceiling

6” round

duct

hood

soffit

vent grate

vent grate

FIGURE  3B

FIGURE  3

For satisfactory performance the duct run should 

not exceed 50 equivalent feet if ducted using the 

required minimum 6" round duct. The equivalent 

feet in 

FIGURE A

 for each piece of duct in the 

system  An example is given in 

FIGURE B

.  

For 

best results, use no more than three 90° 

elbows. Make sure that there is a minimum of 

24" of straight duct between elbows if more 

than one is used. Do not install two elbows 

together.

 If you must elbow right away, do it 

as far away

 from the hood's exhaust opening 

as possible.

RECIRCULATING INSTALLATIONS

For recirculating installations 

(FIGURE 3)

Charcoal Filters

 are necessary. Remove all four grease filters and 

set aside. Attach one charcoal filter to each end of the blower. Each charcoal filter attaches to the black grid 

on the side of the blower. Rotate the filter clockwise to install and counterclockwise to remove 

(FIGURE 3A)

Replace all four grease filters. 

Some ductwork must be installed

 to exhaust the rangehood back into the 

kitchen, either at the top of the cabinet or at the face of the soffit. A plastic vent grate 

(FIGURE 3B)

 supplied with 

the rangehood can be used to cover the duct opening. This duct work must not terminate into a dead air space.

For direct rear venting 

(FIGURE 2)

, you must 

change the blower position. Remove the 12 screws 

that hold the metal housing to the rangehood 

body. Remove the 4 screws that hold the blower 

housing to the metal housing. Rotate the blower 

90 degrees toward the back and then flip it over 

180 degrees. Be sure that the power supply cable 

is properly positioned. Replace all screws, making 

sure that they are firmly fastened.

FIGURE 1

FIGURE 2

Version 06/14 - Page 5

9.0 feet

10.0 feet

0.0 feet

19.0 feet

TOOLS  NEEDED  FOR  INSTALLATION

• Saber Saw or Jig Saw

• Drill

• 1  1/4" Wood Drill Bit

• Pliers

• Phillips Screwdriver

• Wire Stripper or Utility Knife

• Metal Snips

• Measuring Tape or Ruler

• Level

• Pencil

• Caulking Gun

• Duct Tape

PARTS  SUPPLIED  FOR  INSTALLATION 

• 1 Backdraft Damper

• 1 Vent Grate (for recirculating installations only)

• 1 Vinyl Trim

• 1 Literature Package

PARTS  NEEDED  FOR  INSTALLATION

• 2 Conduit Connectors

• Power Supply Cable

• 1 Wall or Roof Cap

• All Metal Ductwork

PLAN  THE  DUCTWORK

The Cristal HC slideout  rangehood is designed to offer wide flexibility of installations.  

The rangehood can be ducted vertically or horizontally through a 6" round vent.  

The unit can also be installed in a recirculating configuration.  The unit comes 

standard in the top venting position.  

FIGURES 1 and 2

 show vertical and horizontal 

installations for this unit. 

 FIGURE 3

 shows recirculating installation.

The Cristal HC requires 6" round ductwork.  To ensure that the blower performs to 

its highest possible capacity, ductwork should be as short and straight as possilbe.

RECIRCULATING  INSTALLATIONS

For recirculating installations 

(FIGURE 3)

Charcoal Filters

 are necessary. Remove all four grease filters and set aside.  Attach 

one charcoal filter to each end of the blower.  Each charcoal filter attaches to the black grid on the side of the blower.  Rotate 

the filter clockwise to install and counterclockwise to remove 

(FIGURE 3A)

.  Replace all four grease filters.  

Some ductwork 

must be installed

 to exhaust the rangehood back into the kitchen, either at the top of the cabinet or at the face of the soffit.  A 

plastic vent grate 

(FIGURE 3B)

 supplied with the rangehood can be used to cover the duct opening.  This duct work must not 

terminate into a dead air space.

FIGURE  3A

45˚ Elbow

90˚ Elbow

90˚ Flat Elbow

Wall Cap

FIGURE  A

9 Feet Straight Duct

2 - 90˚ Elbows

Wall Cap
Total System

FIGURE  B

3.0 feet

5.0 feet

12.0 feet

0.0 feet

VERTICAL 

DUCTING

FIGURE 2

HORIZONTAL  

DUCTING

FIGURE  1

For direct rear venting 

(FIGURE 2)

, you must 

change the blower position.  Remove the 12 

screws that hold the metal housing to the 

rangehood body.  Remove the 4 screws that 

hold the blower housing to the metal housing.  

Rotate the blower 90 degrees toward the back 

and then flip it over 180 degrees.  Be sure that 

the power supply cable is properly positioned.  

Replace all screws, making sure that they are 

firmly fastened.  

cabinet

ceiling

6” round

duct

hood

cabinet

ceiling

6” round

duct

hood

soffit

vent grate

vent grate

FIGURE  3B

FIGURE  3

For satisfactory performance the duct run should 

not exceed 50 equivalent feet if ducted using the 

required minimum 6" round duct. The equivalent 

feet in 

FIGURE A

 for each piece of duct in the 

system  An example is given in 

FIGURE B

.  

For 

best results, use no more than three 90° 

elbows. Make sure that there is a minimum of 

24" of straight duct between elbows if more 

than one is used. Do not install two elbows 

together.

 If you must elbow right away, do it 

as far away

 from the hood's exhaust opening 

as possible.

Version 06/14 - Page 5

9.0 feet

10.0 feet

0.0 feet

19.0 feet

TOOLS  NEEDED  FOR  INSTALLATION

• Saber Saw or Jig Saw

• Drill

• 1  1/4" Wood Drill Bit

• Pliers

• Phillips Screwdriver

• Wire Stripper or Utility Knife

• Metal Snips

• Measuring Tape or Ruler

• Level

• Pencil

• Caulking Gun

• Duct Tape

PARTS  SUPPLIED  FOR  INSTALLATION 

• 1 Backdraft Damper

• 1 Vent Grate (for recirculating installations only)

• 1 Vinyl Trim

• 1 Literature Package

PARTS  NEEDED  FOR  INSTALLATION

• 2 Conduit Connectors

• Power Supply Cable

• 1 Wall or Roof Cap

• All Metal Ductwork

PLAN  THE  DUCTWORK

The Cristal HC slideout  rangehood is designed to offer wide flexibility of installations.  

The rangehood can be ducted vertically or horizontally through a 6" round vent.  

The unit can also be installed in a recirculating configuration.  The unit comes 

standard in the top venting position.  

FIGURES 1 and 2

 show vertical and horizontal 

installations for this unit. 

 FIGURE 3

 shows recirculating installation.

The Cristal HC requires 6" round ductwork.  To ensure that the blower performs to 

its highest possible capacity, ductwork should be as short and straight as possilbe.

RECIRCULATING  INSTALLATIONS

For recirculating installations 

(FIGURE 3)

Charcoal Filters

 are necessary. Remove all four grease filters and set aside.  Attach 

one charcoal filter to each end of the blower.  Each charcoal filter attaches to the black grid on the side of the blower.  Rotate 

the filter clockwise to install and counterclockwise to remove 

(FIGURE 3A)

.  Replace all four grease filters.  

Some ductwork 

must be installed

 to exhaust the rangehood back into the kitchen, either at the top of the cabinet or at the face of the soffit.  A 

plastic vent grate 

(FIGURE 3B)

 supplied with the rangehood can be used to cover the duct opening.  This duct work must not 

terminate into a dead air space.

FIGURE  3A

45˚ Elbow

90˚ Elbow

90˚ Flat Elbow

Wall Cap

FIGURE  A

9 Feet Straight Duct

2 - 90˚ Elbows

Wall Cap
Total System

FIGURE  B

3.0 feet

5.0 feet

12.0 feet

0.0 feet

VERTICAL 

DUCTING

FIGURE 2

HORIZONTAL  

DUCTING

FIGURE  1

For direct rear venting 

(FIGURE 2)

, you must 

change the blower position.  Remove the 12 

screws that hold the metal housing to the 

rangehood body.  Remove the 4 screws that 

hold the blower housing to the metal housing.  

Rotate the blower 90 degrees toward the back 

and then flip it over 180 degrees.  Be sure that 

the power supply cable is properly positioned.  

Replace all screws, making sure that they are 

firmly fastened.  

cabinet

ceiling

6” round

duct

hood

cabinet

ceiling

6” round

duct

hood

soffit

vent grate

vent grate

FIGURE  3B

FIGURE  3

For satisfactory performance the duct run should 

not exceed 50 equivalent feet if ducted using the 

required minimum 6" round duct. The equivalent 

feet in 

FIGURE A

 for each piece of duct in the 

system  An example is given in 

FIGURE B

.  

For 

best results, use no more than three 90° 

elbows. Make sure that there is a minimum of 

24" of straight duct between elbows if more 

than one is used. Do not install two elbows 

together.

 If you must elbow right away, do it 

as far away

 from the hood's exhaust opening 

as possible.

Содержание KTV30XV

Страница 1: ...KTV30XV Installation Instructions Use and Care Information Instructions d installation Utilisez et d entretien...

Страница 2: ...RNING TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK do not use this fan with any solid state speed control device WARNING TO REDUCE THE RISK OF FIRE ELECTRICAL SHOCK OR INJURY TO PERSONS OBSERVE THE FO...

Страница 3: ...MENTS Determine which venting method is best for your application Ductwork can extend either through the wall or the roof The length of the ductwork and the number of elbows should be kept to a minimu...

Страница 4: ...ollow electrical requirements may result in a fire WARNING State of California Proposition 65 Warning US only WARNING This product contains chemicals known to the State of California to cause cancer a...

Страница 5: ...or maximum effectiveness Also consult the cooktop manufacturer s recommendation NOTE If direct rear venting use the side dimensional diagram below on the right For top venting comes standard in this p...

Страница 6: ...6 30 RANGEHOOD REAR INFORMATION Palazzi Walter 15 Nov 2019 Released...

Страница 7: ...1 and 2 show vertical and horizontal installations for this unit FIGURE 3 shows recirculating installation The KTV30XV requires 6 round ductwork To ensure that the blower performs to its highest poss...

Страница 8: ...24 of straight duct between elbows if more than one is used Do not install two elbows together If you must elbow right away do it as far away from the hood s exhaust opening as possible RECIRCULATING...

Страница 9: ...top setting to the bottom setting by removing the four phillips screws 5 Tighten the rangehood to the cabinet by rotating the screws with a phillips screw driver 6 A grey vinyl strip FIGURE 7 is incl...

Страница 10: ...g plug The plug must be plugged into an outlet that is properly installed and grounded WARNING Improper grounding can result in a risk of electric shock Consult a qualified electrician if the groundin...

Страница 11: ...on the blower and light will automatically operate when the visor is opened and shut off when the visor is closed For Best Results Starttherangehoodseveralminutesbeforecookingtodevelop FIGURE 10 ont...

Страница 12: ...or more frequently with heavy usage Open the visor by pulling it RemovetheFilter pushingittowardsthebackof the unit and at the same time pulling downward RemovethesaturatedActivatedCharcoalFilters as...

Страница 13: ......

Страница 14: ......

Отзывы: