2.0 ALARMS LIST 

 

[DISPLAY] 

 

ALARM DESCRIPTION 

 

NOTES 
 

[bELt]

 

Engine Belt break or Charger failure shutdown. The Be172 triggers this 
alarm and shuts down the engine if the input (D+/W.L) is continuously 
below 3Vdc for at least 20 seconds.   

 

Check for the belt 
or the charger 
alternator. 

[°C]

 

Engine High-Temperature alarm. The Be172 triggers this alarm and 
shuts down the engine if the switch input (°C) is closed for at least one 
second. 
 

 

Check the engine 
cooling system. 

 

[ALAr] 

 Emergency alarm. The Be172 triggers this alarm and shuts down the 
engine if the switch input (ALR) is closed for at least one second. 

 

Check the 
emergency 
button status.

 

[FuEL] 

Fuel level alarm. The Be172 triggers this alarm if the switch input (FUEL) 
is closed for at least one second. Based on the settings of the parameter 
[P3], the BE172 triggers a warning (it features auto-reset) or shuts down 
the engine after a programmable time. 

 

Refuel the tank 

[ALr1] 

Alarm 1. The Be172 triggers this alarm if the switch input (ALARM1) is 
closed for at least one second. Based on the settings of the parameter 
(P4), the BE172 triggers a warning (it features auto-reset) or shuts down 
the engine after a programmable time.  

 

Check the Alarm 
1 source.

 

[oiLP] 

Low oil pressure. The Be172 triggers this alarm and shuts down the 
engine if the oil pressure switch connected to the (OIL) input is closed for 
at least one second. This alarm is ignored for 15 seconds after starting 
the engine. 

 

Check the oil 
level.

 

[FAIL] 

Fail to start alarm. The Be172 triggers this alarm and shuts down the 
(FUEL) output if it does not detect, within 20 seconds, a valid source of 
engine running from terminal (D+/WL) or a valid transition of the (OIL) 
input (closed-to-open).   

 

Check the engine 
or check if have 
forgotten the KEY 
in the ON 
position.

 

[Err-]

 

The Be172 

fails to enter the ‘PROGRAM MODE’ due to an erroneous 

inputs setup.

 

Check the 
programming 
instructions.

 

[Err1] 

Failure of the memory.

 

Check the supply and retry programming. If the error persists, 

replace the Be172.

 

[Err2]

 

The supply is lower than 10V. The Be172 denies access to the memory. 
Check the dc supply. 

 

[EE.Er]

 

The Be172 failed the memory initialization routine during the power on. Remove the supply 
for a few seconds. If the error persists, replace the Be172. 

 

 
 

3.0 FUEL SOLENOID & STOP SOLENOID 

 

    In order to stop the engine, we recommend that you use a 

FUEL SOLENOID 

(energized to run)

This 

solenoid must be connected to the output (FUEL) via a pilot relay. If for a particular application, you use 

STOP SOLENOID 

(energized to stop), you are required to set up the adjustable parameter [P2] as 

indicated in the programming instructions. Connect the 

STOP SOLENOID

 to output (ALARM) via a pilot 

relay as indicated in the wiring diagram. The Be172 will energize the output for the programmed time. 
When you use the output (ALARM) to drive a 

STOP SOLENOID

, the 

ALARM

 function output will no be 

longer available. In other words, the 

STOP SOLENOID

 output shares the same output used for 

ALARM.

 

Factory setting for the (ALARM) output is 

ALARM MODE

 

 