heat should shut off when the wires are separated. 

For more complex troubleshooting of either thermal cutouts or 

heater contactors, please consult a qualified electrician or the 

factory.

Q. Why didn’t the Intelliswitch save the changes I made to a 

program?

A.

  If a program is active (a dot is illuminated by one of the 

clock digits), changes can be made to any settings on the User 

Menu. These changes however will only remain in effect until 

the program changes to the next time zone. To make changes 

permanent, settings must be changed in the program from the 

Program Menu. Access the Program Menu by holding down the 

left arrow for 5 seconds until “PRO” is displayed. Arrow down 

to select programming and arrow left to select the program to 

edit. Use the down arrow to step through the options and make 

changes as desired. Continue to press the down arrow until Stor 

is displayed. Press OK or down to keep or store the changes.

Q. How do I undo a change that I made to a program in the 

Program Menu?

A. 

 Changes to programs cannot be undone. The programs can 

however be reset to the factory default settings. This must be 

done on the Factory Menu. Access to the Factory Menu is at-

tained through the Diagnostics Menu. Press and hold the right 

arrow for 5 seconds until “DIAG” is displayed. From the “DIAG” 

display press and hold the up and down simultaneously for 10 

seconds until “FACT” is displayed. Use the down arrow to select 

“DEFn” on the display then use the right arrow to select “DEFP”. 

Press “OK” to reset. The control display will go blank then blink 

as confirmation.

Q. My air curtain won’t turn on?

A.

   Check the AM/PM setting on the Start and Stop times or the 

clock (considering the AM indicator light whensetting values). 

Note: set the start time and stop time to the exact time for the 

unit to be active full time. Check to see if a program is active 

that may have different start/stop times than those expected.

Q. My building has a Building Management System, can the 

Intelliswitch work with a BMS?

A.

  The Intelliswitch can be controlled by a Building Manage-

ment System (BMS) but currently does not have the ability to 

communicate with them. Dry contacts on the BMS may be used 

to control the unit activation through the door switch connec-

tions (blue wires 9 & 10) and the heat activation thought the 

remote thermostat connections (orange wires 6 & 7). Consult 

factory.

any mode that is activated by the door switch.

5.) If the air curtain is heated, make sure that the thermostat 

isn’t wired to the door switch leads. Door switch leads are blue 

and labeled 9 & 10.

Q.  How can I check the door switch to be sure it’s working?

A.

 The Intelliswitch may be in the wrong mode, be mis-wired or 

have a faulty door switch.

1.) Test the wiring and controller function at the same time first. 

Locate the door switch and open its wiring compartment by re-

moving the two screws holding on the back cover. There should 

be two wires connected to screws inside the switch. There is no 

danger of getting shocked because the signal is 5 volt dc. Be 

sure not to touch the wires to anything metal (or grounded). 

Either disconnect both wires from the screws (noting which 

screws the wires are under) and touch them together (with air 

curtain in “Auto” mode) or make a short jumper wire and touch 

the jumper to both screws at the same time to see if air curtain 

comes on. If it does, the controller and wiring work.

2.) If the wiring and unit pass the function test, the problem 

could be either misalignment or a faulty door switch. On a 

magnetic reed switch check for magnet alignment, for plunger/

roller type switch, check contact engagement with door.

3.) If you have access to an electrical test meter, the door switch 

contacts can be tested for continuity when the door switch 

wires are disconnected from the unit.

Q.  Why won’t my heat shut off?

A.

  The Intelliswitch may need adjusted, have been mis-wired or 

have a faulty thermostat.

1.) Heat is activated by one of two thermostat connections. 

To test the internal thermostat set the external thermostat to 

OFF. The settings of the unit mounted thermostat probe are 

accessed through the display. Press the down arrow until the 

Temp Set indicator lights up; check if the temperature setting 

and unit of measure are correct. Test to see if it shuts off by set-

ting the thermostat temperature to OFF or lower than the room 

temperature.

2.) If an external thermostat is connected to the unit, there 

could be a short in the field connections or the thermostat 

leads may be mis-wired. To test the external thermostat set the 

internal thermostat to OFF. Disconnect the external thermostat 

connections at the unit. Open the wiring tray on top of the unit 

and be cautious of high voltage connections. Disconnect the 

orange wires labeled 6 & 7 from the field wiring to the thermo-

stat or make sure they are not tied together. There is no danger 

of getting shocked because the signal is 5 volt dc. Be sure not 

to touch the orange wires to anything metal (or grounded). The 

INTELLISWITCH™ FAQ’s Continued (Frequently Asked Questions)

www.intelli-how2.com

13

Содержание Maxair

Страница 1: ...ONNECTIONS NEC Code ANSI NFPA No 70 E When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities F To reduce the risk of fire do not store or use gasoline...

Страница 2: ...ver housing A When determining the mounting location for the air door s make sure that nothing interferes with the curtain of air developed when the discharge vanes are directed from 0 to 20 toward th...

Страница 3: ...the air door with the discharge opening facing down toward the floor While holding the air door level slide the heads of the shoulder bolts into the larger hole of the keyhole slots of the mounting pl...

Страница 4: ...over on air doors that are comprised of modules remove the wiring tray cover that is located closest to the electrical rating nameplate if it has not already been done D Electric steam and hot water h...

Страница 5: ...h coupler the cables are connected to 9 The first and last air curtains in the group will each have an empty coupler after all connections are made So if there are only two air curtains connected each...

Страница 6: ...n must be properly installed before it is used 1 Control packages control the unit s sequence of operation Unit modes control packages are built into the unit and may not be changed in the field Refer...

Страница 7: ...t peak efficiency by cleaning the blower wheels motor s and intake grille Buildup of dust on the blower wheels can cause vibration noise and excessive wear on the motor bearings The frequency of clean...

Страница 8: ...SWITCH SPEED SENSOR ADJUSTMENT 1 Set Intelliswitch mode to off 2 Disconnect power to the unit 3 Remove the intake grille by removing the locking screws on each end of the unit Lift the intake A INTELL...

Страница 9: ...liswitch mode to off 2 Disconnect power to the unit 3 Remove the wiring tray cover 4 Cut necessary cable ties that may be holding the brown temperature sensor lead 5 Disconnect the temperature sensor...

Страница 10: ...e unit will operate only when the door is open delu delu DELUXE For use with a door switch the unit will operate only when the door is open with a minimum 1 minute delay before turning off when it clo...

Страница 11: ...a 1 minute time delay 24 hours a day 7 days a week See Appendix A page 18 for more detailed information Modes of Operation continued PRO2 Pro2 PROGRAM 2 Recommended for heated units This setting will...

Страница 12: ...f at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warni...

Страница 13: ...curtain is heated make sure that the thermostat isn t wired to the door switch leads Door switch leads are blue and labeled 9 10 Q How can I check the door switch to be sure it s working A The Intelli...

Страница 14: ...s four menus User Menu Section 4 Program Menu Section 5 Diagnostic Menu Section 6 Factory Menu Section 7 The User Menu is the top level menu where values for each op tion is entered based on the Mode...

Страница 15: ...is the period of operation defined by the use for the unit to be active Both zones may operate one after the other or have gaps between them AUTO air door will run when terminals 9 10 are connected t...

Страница 16: ...rt Time multi level Set start time for zone program to activate including am pm Note Zone 1 has priority over Zone 2 and if conflicting times are entered Zone 1 will always activate and take pre ceden...

Страница 17: ...the OK button select action and return to the User Menu 7 1 Speed Range single level rn N 0 1 2 3 4 5 6 7 8 9 10 11 99 O Select the fan speed range from 0 to 11 using the left or right arrows The spee...

Страница 18: ...control 11 heated multiple 2 speed ITC relay control 99 lock out scrolling request for user input 7 2 Thermostat Probe Mode single level In St Standard mode the lowest operating point for the thermos...

Страница 19: ...NING FANS ARE NOT ROTATING MINIMUM AIR ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN X TROUBLESHOOTING SYMPTOMS REMEDY CAUSE NO SPEED ADJUSTMENT Speed sensor not detecting trigger rotation Adj...

Страница 20: ...any expense or liability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without w...

Отзывы: