Adjusting Sensitivity Levels
The Leak Detector will default to the NORM sensitivity level
automatically once the unit comes out of the warm up cycle and
the green LED will turn on.
To change sensitivity levels, press the SENS once for HI
sensitivity (red LED will turn on) and again for LO sensitivity
(yellow LED will turn on).
Leak Test Vial
The leak detector comes with a Leak Test Vial that allows the
user to make sure the detector is performing properly. To test:
4. Remove the plastic seal cap on top of the Leak Test Vial
by pulling it off (see fig. below).
5. Turn on the detector and allow the unit to complete the
warm up cycle.
6. Place the sensor close to the small hole in the top of the
Leak Test Vial. The beep rate should increase and the
Digital Leak Size Indicator should display a number from
4-6 indicating that the sensor and electronics are working
properly.
NOTE: Always remember to replace plastic seal cap after
leak test is completed. Replace Test Vial when the green
color is no longer visible.
Remove
Seal Cap
To test
Leak Test Vial