Fire Protection

Strainers

FP-60F-D/DV

Design Engineer Guide

The BERMAD FP-60F-D/DV Basket strainers are for use in firewater supply and are capable of preventing the entrance 
of solids that might block or clog fire protection nozzles or other sensitve devices. 
Install the FP-60F-D/DV strainer upstream of the sprinkler valve, deluge valve, pressure control valve or any other 
debris sensitive system device.
The Strainer must be located where there is adequate clearance for removal of the basket screen assembly to enable 
easy extraction and inspection of the strainer basket.
Install the strainer such that there will be adequate drainage for the release of water when opening the strainer for 
service and for the dirty water exhausted during the cleaning of the strainer screen using the flushing valve.
The flushing drain connection should be typically fitted with an appropriately sized normally closed valve and drain piping. 
Where a flushing valve is to be employed, the FP-60F-D/DV Basket Strainer sizes 3" to 12" are recommended to be installed 
in a horizontal position with the strainer cover and flushing valve to the side. To facilitate flushing for 14" and 16" sizes 
installation is recommended to be vertical. 
The strainers shall be installed and maintained in compliance with the NFPA-25 standard in the addition to the instructions 
given by the authorities having jurisdiction. 
The NFPA-11 standard requires that a listed strainer with a screen area to pipe cross section area ratio of 10:1 shall be used with 
foam proportioners or foam generators, and should be installed in the water pipeline upstream of the water control valve.
The NFPA 13, 15 and 16 standards stipulate that a Listed Strainer shall be provided in the main pipeline of all systems 
utilizing nozzles with waterways less than 

3

8

" (9.5 mm) and for any system where the water is likely to contain obstructive 

material. Strainers shall be capable of removing from the water all solids of sufficient size to obstruct the nozzles.

Engineer Specifications

The Fire Line Strainer shall be a basket type strainer UL listed.
The strainer shall be with high flow capacity and low pressure loss.
The strainer shall include a flushing valve capable of quickly and efficiently cleaning the strainer screen without removing 
the strainer cover, or closing system pressure.
The strainer body and cover shall be ductile iron ASTM A536 65-45-12 with anti-corrosion Fusion Bonded High Build 
Epoxy RAL 3002 coating internally and externally, all other wetted parts shall be stainless steel 316.
The screen shall be inline removable basket type, made of stainless steel 316 with screen holes diameter of 3.2 mm 
(

1

/

8

"), meeting the requirements of the NFPA codes and standards. The Strainer basket screen area shall be at least 10:1 

compared to the cross-sectional area of the pipeline. 
Strainer maintenance, inspection or service shall be carried out in-line and without disassembly of the strainer body 
from the pipeline. The Strainer shall be supplied pre-assembled with stainless steel bolting and hydraulically tested by 
a factory certified by the  ISO-9001 standard.

Cross Section Showing Inline Fushing of the Filter Screen

Содержание FP-60F-D

Страница 1: ...sted strainers shall be provided in the main pipeline of all systems using nozzles where the water is likely to contain obstructive material Features and Benefits UL Listed and ULC size for Fire systems Low pressure drop Safety and reliability ensures firewater availability Easy in line maintenance Large diameter flushing valve for fast and easy interim cleaning Suitable to prevent clogging Nozzle...

Страница 2: ... area ratio of 10 1 shall be used with foam proportioners or foam generators and should be installed in the water pipeline upstream of the water control valve The NFPA 13 15 and 16 standards stipulate that a Listed Strainer shall be provided in the main pipeline of all systems utilizing nozzles with waterways less than 3 8 9 5 mm and for any system where the water is likely to contain obstructive ...

Страница 3: ...ll as the dynamic loads It is recommended to install a differential pressure gauge rooted to upstream and downstream of the FP 60F D DV strainer in order to show the degree of strainer blockage The maximum allowable differential pressure across the strainer is 7 psi or 0 5 bar at maximum system flow Placing In Service Verify that all strainer cover bolts are well tightened close the drain plug and...

Страница 4: ...isassembly of any strainer component The strainer basket screen should be cleaned after each system operation or flow test and during routine inspections as follows For strainers fitted with a flushing valve 1 Fully open the flushing drain valve for at least 5 seconds or until the flushed water becomes visibly clear 2 Close the flushing valve tight For periodic inspection and cleaning of screens f...

Страница 5: ... 1215 47 8 B 184 7 2 228 9 0 334 13 1 388 15 3 416 16 4 502 19 8 515 20 3 554 21 8 W 215 8 5 280 11 0 355 14 0 440 17 3 540 21 3 620 24 4 665 26 2 720 28 3 C 20 0 75 25 1 25 1 40 1 5 40 1 5 50 2 40 2 50 2 D 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 Flushing Valve Length 226 8 9 226 8 9 203 8 203 8 203 8 203 8 229 9 254 10 F 2 ISO 7 Rp 2 ISO 7 Rp 3 150 3 150 3 150 3 15...

Страница 6: ...low coefficient Kv flow in m h at 1 bar differential pressure Cv flow in gpm at 1 psi differential pressure The pressure loss calculation formula Δp SG Q Cv or Kv 2 2 Leq Equivalent pipe length for turbulent flow in clean commercial steel pipe SCH 40 3 Max allowable pressure drop 7 psi 0 5 bar across the strainer basket screen shall be cleaned when pressure drop exceeds this value at maximum flow ...

Отзывы: