BERMAD BC-73Q-P Скачать руководство пользователя страница 2

 

File Name: 

IOM BC-73Q-P (1.5in-4in) 

Rev. 01 

Prepared By: 

RC 

Date: 

03/17 

 

[email protected] 

● www.vbtech.com 

 www.bermad.com

 

The information contained in this document is subject to change without notice. BERMAD shall not be liable for any errors  

contained herein.  All Rights Reserved. © Copyright BERMAD Control Valves. 

Model BC-73Q-P

 

IOM

 

PC-3Q

4

1

2

3

705

4A

S

Control Loop Diagram 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Troubleshooting 
 

Symptom 

Possible Cause 

Solution 

Valve Fails to Open 

  Insufficient inlet pressure.

 

  Pipeline isolation valve(s) closed.  

  Excessive relief pilot PC-3Q  spring 

compression.

 

  Cover/body tap/plumbing clogged.

 

  Check/create inlet pressure.

 

  Open isolation valve(s).

 

  Readjust pilot PC-3Q. See step 5 of the 

commissioning instructions. 

  Clean cover/body tap/plumbing. 

 

 

 

Valve Fails to Close or Regulate  
 
 
 
 
 
 

 

  Filter 4A clogged. 

 
 

  Insufficient relief pilot PC-3Q  spring 

compression.

 

  Debris trapped in main valve. 

 

  Diaphragm in main valve leaking  or 

diaphragm assembly loose. 

  Remove in-line filter 4A  and clean 

screen/body taps re-installing w/dot 
mark facing upstream. 

  Readjust pilot PC-3Q. See step 5 of the 

commissioning instructions. 

  Remove actuator assy. to inspect seat 

area/verify valve stroke/remove debris. 

  Remove  a  small cover plug at valve 

cover. Continuous flow indicates 
diaphragm leakage.  Inspect, tighten, 
and/or replace Diaphragm.  

 

 
 
 
 
 
 

 

PART LIST 
4A 

 

Control Filter 

 

Limit Switch Assembly 

PC-3Q   

Relief Pilot, Quick Type 

705 

 

Main Valve 

 

Отзывы: