BERMAD 410-01-3NC-200 Скачать руководство пользователя страница 2

TROUBLESHOOTING 

SYMPTOM 

CAUSE 

REMEDY 

Valve Fails to Open 

Insufficient inlet pressure/flow. 
 
Solenoid 15 is De-energized. 
 
Solenoid 15 Plunger Stuck. 
 
Manual override 0 black toggle is 
turned CCW towards C mark on base. 
 
Manual override 0 black toggle is 
turned CW towards O mark on base. 
 
Needle 5 is closed/clogged. 
No flow /Differential  across valve. 
 
 
 
Solenoid 15 Plunger Stuck. 
 
 
Solenoid 15 is energized. 
 
Filter 4A blocked. (1-1/2in & Up 
only)  

 

 
Debris trapped in main 
valve/Diaphragm in main 
valve leaking. 

Check/create inlet pressure/flow. 
 
Energize solenoid 15. 
 
Check and clean plunger in coil and base. 
 
Turn manual override 0 to its middle 
detent position for automatic mode. 
 
Turn manual override 0 to its middle 
detent position for automatic mode. 
 
Clean/Open Needle 5 out CCW. 
Create demand downstream/Create 3-5 
psi differential across the valve-higher 
upstream pressure.  

 

 

 

 

 

Check and clean plunger in solenoid base 
and inside of the coil. Clean vent tube-
hose. 
De-energize solenoid 15-See Wiring. 
                

 

             

Remove inlet filter fitting and clean 
screen/ftitting/hose & inlet port hole. 
 
De-pressurize the system and remove the 
four nuts/bolts from the cover assembly.  
Inspec seat area/remove debris/Replace 
diaphragm. 

Valve Fails to Close 

  MODEL 410-01-3NC-200 Electric Remote Control Valve w/Closing Speed Control 

  CONTROL 

VALVES

 

4070 E. Leaverton Court - Anaheim, CA. 92807 - (714) 666-1100 

INSTALLATION - OPERATION - MAINTENANCE 

PARTS LIST 
1.        Black Manual Operator knob 
5.         Closing Speed Control 
4A. In-line 

Filter 

15. 

3-way N.O. Solenoid w/Manual Override 

405 Main 

Valve 