DO NOT MOUNT MERCURY TYPE THERMOSTAT DIRECTLY
ON UNIT. VIBRATION COULD CAUSE HEATER TO 
MALFUNCTION.  

MANUAL RESET LIMIT (FACTORY INSTALLED OPTION
ONLY.)  THE LIMIT SWITCH IS LOCATED INTERNALLY ON
THE REAR OF THE HEATER.  ON THE 3KW AND 5KW 
MODELS, THE ACCESS TO THE RESET BUTTON IS ON THE
RIGHT SIDE (WHEN FACING REAR OF HEATER); ON ALL
OTHER MODELS IT IS NEAR THE TOP REAR OF THE
HEATER.

THE MANUAL RESET LIMIT IS IN SERIES WITH THE AUTO-
MATIC RECYCLING PROTECTOR (LIMIT). THE MANUAL
RESET LIMIT WILL NOT RESET UNTIL THE  HEATER HAS
COOLED AND THE BUTTON IS PUSHED IN.

HEATER LOCATION INSTRUCTIONS

Arrange units so their discharge air streams:

a. are subjected to a minimum of interference from columns,

machinery and partitions;

b. wipe exposed walls without blowing directly at them;

c. are directed away from room occupants in comfort heating;

d. are directed along the windward side when installed in a

building exposed to a prevailing wind.

Locate thermostats approximately 5' (1524mm) above the floor
on interior partition walls or posts, away from cold drafts, internal
heat sources and away from heater discharge air streams.

Small rooms can be heated by one unit heater.

Large rooms require multi-unit installations. Number and 
capacity of units will be determined by volume of building and
square feet of floor area to be heated. Arrange units to provide
perimeter air circulation where each unit supports the air stream
from another.

MOUNTING THE HEATER, GENERAL

The heater may be mounted to discharge the heated air either
horizontally or vertically. When the heater is mounted for vertical
discharge, it is recommended that the heater be positioned so
that the access door will open away from the wall to provide
greater access to the wiring and control compartment. If the
heater is to be mounted with the access door facing a wall, the
heater must be mounted far enough from that wall to allow full
opening of the access door (a distance approximately equal to
the width of the heater, check clearance before installing).
Refer to Table 1 for wall and ceiling clearances before mounting
heater. 

The heater may be mounted for either vertical or horizontal dis-
charge by the use of threaded rods. (Refer to Table 2 for thread-
ed rod sizes required.) Observe the detailed procedures in the
following installation instructions.

The heater may also be suspended from the wall or ceiling by
means of an optional mounting bracket (type HUHAAB or
HCMB) which permits horizontal pivoting of the heater.

After the heater is installed, the louvers may be positioned to
direct the heated air in the desired direction. When the heater is
installed for horizontal discharge, the louvers should direct the
air either straight ahead or downward. Directing the air upward
may cause the heated air to remain in the ceiling area and
waste energy.

Table 1. Wall and Ceiling Clearance, inches (mm)

Unit

Discharge

Ceiling

Side Wall

Back Wall

3 & 5 kW

Horiz.

2 (50.8)

6 (152.4)

9 (228.6)

Vert.

6 (152.4)

18 (457.2)

18 (457.2)

7.5 to 10 kW

Horiz.

6 (152.4)

6 (152.4)

13 (330.2)

Vert.

6 (152.4)

24 (609.6)

24 (609.6)

15 to 10 kW

Horiz.

6 (152.4)

9 (228.6)

12

1

/

2

(317.5)

Vert

6 (152.4)

24 (609.6)

24 (609.6)

25 to 50 kW

Horiz.

16 (406.4)

12 (304.8)

18

1

/

2

(470.0)

Vert.

12 (304.8)

36 (914.4)

36 (914.4)

Table 2. Rod Thread and Spacing Dimensions, inches (mm) 
for Horizontal Discharge

Rod Thread

Unit

Type

A

B

C

D

3 - 5 kW

6

1

/

16

3

/

4

6

1

/

16

(152.4)

(103.1)

(19.0)

7.5 - 10 kW

(153.9)

15 - 20 kW

5

/

16

- 18

11

3

/

8

8

7

/

8

1

/

8

3

/

4

(289.0)

(225.6)

(130.3)

(19.0)

25 - 30 kW

10 

9

/

16

14 

1

/

2

3

/

16

5

/

8

(268.2)

(368.3)

(157.2)

(16.0)

40 - 50 kW

3

/

8

- 16

15 

15

/

16

14 

1

/

2

3

/

16

5

/

8

(404.9)

(368.3)

(157.2)

(16.0)

TO PREVENT POSSIBLE OVERHEATING OR DAMAGE DUE
TO  OVERHEATING,  KEEP  AT  LEAST  5'  (1524MM)  CLEAR-
ANCE  IN  FRONT  OF  HEATER.  REFER  TO  TABLE  1  FOR
SIDE, TOP, AND BACK CLEARANCE REQUIREMENTS.

ALL BUILT-IN THERMOSTATS: IF THE HEATER IS USED TO
PREVENT  PIPING  OR  LIQUIDS  FROM  FREEZING,  AND  IF
THE  THERMOSTAT  IS  SET  BELOW  45°  F  (7°C),  THE  FAN
MUST RUN CONTINUOUSLY. 

THE CEILING MOUNTING STRUCTURE AND THE ANCHOR-
ING  PROVISIONS  MUST  BE  OF  SUFFICIENT  STRENGTH
TO  SUPPORT  THE  COMBINED  WEIGHT  OF  THE  HEATER
AND MOUNTING BRACKET.  (SEE TABLE 4).

THE HEATER MUST BE MOUNTED AT LEAST 7' (2134MM)
ABOVE THE FLOOR TO PREVENT ACCIDENTAL CONTACT
WITH THE FAN BLADE WHICH COULD CAUSE INJURY.

2

Figure 1. Horizontal Discharge Mounting and Spacing.

(TOP VIEW)

Содержание HUHAA series

Страница 1: ...fire do not block air intakes or exhaust in any manner Keep combustible materials such as crates d r a p e s etc away from heater Do not install behind door furniture towels or boxes 7 A heater has hot and arcing or sparking parts inside Do not use it in areas where gasoline paint or flammable liquids are stored 8 Use this heater only as described in this manual Any other use not recommended by th...

Страница 2: ...all and ceiling clearances before mounting heater The heater may be mounted for either vertical or horizontal dis charge by the use of threaded rods Refer to Table 2 for thread ed rod sizes required Observe the detailed procedures in the following installation instructions The heater may also be suspended from the wall or ceiling by means of an optional mounting bracket type HUHAAB or HCMB which p...

Страница 3: ...hese units are factory wired for single phase operation If these heaters are for use with three phased power recon nect the wires as indicated in the wiring diagram attached to the heater Additional information can be found by looking at the wiring illustrations in Figures 3a and 3b and following the directions shown below On models HUHAA520 HUHAA524 HUHAA720 HUHAA724 HUHAA1020 and HUHAA1024 Figur...

Страница 4: ...OVERY AT OR REMOTE H HUHAARFS2 REMOTE SUMMER FAN SWITCH HUHAARFS 1 OR SUMMER FAN SWITCH HUHAAFS MANUAL HUHAA MT 2 HUHAA MT 1 HUHAA MT 2 Figure 4 Control Terminal Board for Heaters Without Contactors NOTES 1 THIS STYLE CONTROL TERMINAL BOARD USED WITH MODELS HUHAA320 HUHAA324 HUHAA327 HUHAA520 HUHAA524 HUHAA527 2 WHEN UNIT IS WIRED FOR SINGLE PHASE JUMPER H1 TO H2 IF SINGLE POLE THER MOSTAT IS USED...

Страница 5: ...27 2 HUHAA2024 60 27 2 HUHAA2048 60 27 2 HUHAA2524 93 42 3 HUHAA2548 30 26 5 8 13 3 4 93 42 3 HUHAA3020 76 2 676 4 346 8 93 42 3 HUHAA3024 93 42 3 HUHAA3048 93 42 3 HUHAA4024 119 54 0 HUHAA4048 30 26 5 8 18 1 8 119 54 0 HUHAA5020 76 2 676 4 457 2 119 54 0 HUHAA5024 119 54 0 HUHAA5048 119 54 0 MODEL NO HUHAA324 DATE CODE 0395 MFG NO VOLTS AC KILOWATTS PHASE 60 HZ 208 240 2 2 3 1 MOTOR CONTROL VAC A...

Страница 6: ... Products THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT WHETHER BASED UPO...

Отзывы: