Installation of Housing with 

Surface-Mounting Frame (See Figure 3)

1. Secure back box to wall with knockouts in upper right 

hand corner using screws and anchors.

2. Hang the surface-mounting frame on the back box. 

Ensure that the back edge of the surface-mounting frame
is flush against the wall.

NOTE: If heater is located in a high traffic area, where it may
be subjected to vandalism or abuse, take extreme care to see
that the box is firmly attached to the wall.

3. Power Supply Wiring

NOTE: Wiring Compartment Volume - 119in

3

(1950cm

3

).

a. Run a power supply cable into the area to the upper 

right corner of the mounting frame. Arrangement of 
wiring to this point must be in accordance with National
and Local codes. Refer to specifications on page 2 for
proper wire size.

NOTE: If the wiring is to run through the wall, cut a hole 
in the area of the top of the wall box. Run the supply wire 
through this hole. Then remove the “knockout” from the 
top of the box and proceed to step C.

b. Remove the “knockout” on the top side of the frame.
c. Remove disconnect switch bracket by loosening the 

two screws on the right side.

d. Feed the power supply cable through the frame allow-

ing 6" (152mm) of lead to remain inside the inner hous-
ing (using cable clamp, connector, or other suitable 
strain relief).

e. Secure the power supply cable to the inner housing 

(using cable clamp, connector, or other suitable strain
relief) allowing 6" (152mm) of lead to remain inside the
inner housing.

f. Connect supply wires to blue wires of disconnect 

switch using wiring connectors (see wiring diagram, 
next column).

g. Ground the housing by connecting the supply ground 

leadwire to the green ground screw located in the 
inside top of the housing.

h. Secure disconnect switch bracket in place.

Installation of Heater Assembly and Grille

After wall housing is completely installed and no further con-
struction dirt is expected, clean debris from wall housing,
remove heater assembly from its carton, then refer to Figure
4 and proceed as follows:

1. Insert the heater assembly into wall housing, placing 

the four mounting holes (with key-hole slots) over the 
screws in the housing. Tighten all screws securely.

2. If surface-mounting frame is used, ensure that the 

frame is even with all four heater assembly tabs before
tightening screws.

3. Connect the two disconnected switch wires to the heat-

control switch (thermostat) leads using wirenuts. (see 
wiring diagram, next column) After connection, push 

wires back into the opening.

4. Turn thermostat to the extreme counterclockwise 

position.

5. Push disconnect switch into ON position.
6. Install (2) plastic covers on back box as follows: (See Fig. 4)

NOTE: Both top and bottom plastic covers are identical.

• TOP - Align the screw bosses on the back of the plastic

cover with the second hole down from the top of the 
back box and attach it with the two screws provided.

• BOTTOM - Align the screw bosses on the back of the 

other plastic cover with holes at the bottom of the back
box that are just above the fan deck mounting screws 
and attach it with two screws provided.

7. Remount the wire compartment cover.  Install the front 

cover by hooking the (2) tabs on the one side then rotat-
ing the front cover into place making sure that all four tabs
are snapped onto the front cover.

8. Fit the thermostat knob onto the thermostat shaft and

push into place.

Fig. 3: Surface Mounting Installation

Fig. 4

ELEMENTS

FAN

MOTOR

FAN

DELAY

RELAY

DISCONNECT

FIELD WIRING

GND

THERMOSTAT

MANUAL

RESET

CYC

L1

1

6

8

4

6

2

1

3

2

WIRING DIAGRAM 

FOR THREE PHASE WALL HEATERS

ELEMENTS

FAN

MOTOR

FAN

DELAY

RELAY

DISCONNECT

FIELD WIRING

GND

MANUAL

RESET

1

0

8

4

6

2

1

3

2

THERMOSTAT

CYC

L2

WIRING DIAGRAM FOR 

4800 WATT 208 VOLT

SINGLE PHASE WALL HEATER

Wiring Diagrams

MOUNT BACK BOX

TO WALL USING

REAR MOUNTING

HOLES.

HANG FRAME

ON BACK BOX.

15-5/32 "
(385mm)

19" 

(482mm)

3-13/16"

(97mm)

THERMOSTAT KNOB

FRONT COVER

PLASTIC
COVER

PLASTIC COVER

POWER LEADS

BACK BOX

INNER FRAME
ASSEMBLY

RECESS WALL
HOUSING

DISCONNECT
SWITCH

THERMOSTAT 

3