Motor Switch Settings

Dual-voltage motors (motors that can operate at either 115 or
230 volts), are set at the factory to 230 volts. Do not change
motor voltage setting if line voltage is 230 volts, or if you have
a single voltage motor. 

NOTE:

Never wire a 115 volt motor to a 230 volt line.

Remove Motor End Cover

If you have a dual-voltage motor, and will connect it to 115
volts, follow the procedure below. 

You will need to remove the motor end cover to change the
voltage setting. 

Your motor terminal board (located under the motor end
cover) should look like that shown below. 

To change to 115 volts:

1. Make sure power is off.

2. Turn the dial counter-clockwise until 115 shows in the dial

window.

3. The wires from the pressure switch should already be

attached to to power lead terminals.

4. Reinstall the Motor end cover.

Pressure Switch Wiring

Step 5. Go to Wiring Connections below.

Hazardous voltage. Can shock, burn, or kill.

Connect ground wire before connecting power supply
wires. Use the wire size (including the ground wire) speci-
fied in the wiring chart.

If possible, connect the pump to a

separate branch circuit with no other appliances on it. 

Explosion hazard. Do not ground to a gas

supply line.

Electrical

Disconnect power before working on pump, motor, pressure switch, or wiring. 

Figure 4 – Removing Motor End Cover

Motor 
End Cover

 End Cover Screws

Figure 6 – Pressure Switch Wiring

Clamp the power cable to prevent strain 
on the terminal screws.

Connect the green (or bare copper)  ground wire 
to the green ground screw.

Motor wires 

connect here

.

3187 0704H

Power supply wires

 connect here. 

230 Volt:

 Connect 2 hot wires (black and red)

here and cap the white (neutral) wire. It does
not matter which wire goes to which screw. 

115 Volt:

 Connect one hot wire (black or red)

to one of these screws (it doesn't matter 
which one). Connect the white (neutral) wire 
to the other screw. Cap any remaining 
black or red wires.

Figure 5 – Voltage set to 230 volts, Dial Type

Voltage  
Change Dial

Ground 
Screw

Power Lead
Terminals

Содержание 7LT2

Страница 1: ...MPORTANT For best possible performance continuous satisfactory operation read these instructions before installing your new pump Should service be required this manual can be a valuable guide It shoul...

Страница 2: ...apped air in pump body was not removed Restart pump When pump is completely primed and builds up pressure slowly open the regulator valve turn counter clockwise and observe the pressure reading on the...

Страница 3: ...imed close the priming valve during operation as a shallow well pump Service Draining for Winter Do not touch an operating motor Modern motors are designed to operate at high temperatures To avoid bur...

Страница 4: ...Can shock burn or kill Connect ground wire before connecting power supply wires Use the wire size including the ground wire speci fied in the wiring chart If possible connect the pump to a separate b...

Страница 5: ...on Connection Procedure 1 Connect the ground wire first as shown in Figure 6 The ground wire must be a solid copper wire at least as large as the power supply wires 2 There must be a solid metal conne...

Страница 6: ...6 1 2 4 5 6 7 8 9 10 10A 10B 22 25 23 24 3 225 0993 8 11 12 12A 12B 13 14 15 16 17 18 18A 19 20 21 26 27 EXPLODED VIEW...

Страница 7: ...x 3 Lg 3 U30 528SS U30 528SS U30 528SS 13 Diffuser Ring OH SG 1 L21 1 L21 1 L21 1 14 Pipe Plug 1 2 NPT 1 U78 59ZPS U78 59ZPS U78 59ZPS 15 Pressure Gauge 1 U239 8 U239 8 U239 8 16 Pump Body 1 L76 36 L...

Страница 8: ...2 5 2B Diaphragm Assembly Incl 2C 2D 2E 2F 2G 1 J120 16 2C Stem 1 J62 9 2D Diaphragm 1 J20 16 2E Spring Follower 1 J43 31 2F Ext Tooth Washer 1 U43 23ZP 2G Nut Hex Head 1 4 20 1 U36 36ZP 3 Spring 1 J2...

Отзывы: