Symptom
Cause
Solution
• Warning
(
electric fan error
)
is
displayed on the control panel and the
unit switches off automatically. The
warning will be displayed on the control
panel until the anomaly is repaired.
• Condenser fan blocked, in short circuit
or disconnected.
• 7.5A fuse in condenser fan blown.
• Repair possible obstruction of the condenser fan; if the error persists, replace the
condenser fan (
to access the condenser fan remove the unit’s outer cover
).
• Replace 7.5A fuse. To access the fuses of the condenser fan, remove the control
panel’s access cover fitted on the internal air distribution panel.
!
(If the error persists, contact the Authorised Technical Service).
• During the unit’s operation,
(
blower error
)
is displayed on the
control panel and the unit switches
off automatically. The warning will be
displayed on the control panel until the
anomaly is repaired.
• Centrifugal blower blocked in short
circuit or disconnected.
• 7.5A fuse in the blower blown.
• Repair possible obstruction of the centrifugal blower; if the error persists, replace the
centrifugal blower (
to access the centrifugal blower, remove the unit’s outer cover and
the evaporator cover
).
• Replace 7.5A fuse. To access the fuses of the centrifugal blower remove the control
panel’s access cover fitted on the internal air distribution panel.
!
(If the error persists, contact the Authorised Technical Service).
• Warning
(
compressor 1 start-up
error
) is displayed on the control panel
and the unit switches off automatically.
The warning will be displayed on the
control panel until the anomaly is
repaired.
• Compressor 1 faulty or broken.
• Compressor 1 module disconnected
from compressor or faulty.
• Replace compressor 1.
• Correctly connect the module of compressor 1 or replace (to access the modules and
the compressors, remove the unit’s external cover).
Note:
the references for each
module are different; check that it is replaced using the correct reference.
!
(If the error persists, contact the Authorised Technical Service).