USER MANUAL 1.2 | B-FORTIS CC-PRIME SERIES
Berghof Automation GmbH | Arbachtalstrasse 26 | 72800 Eningen |
64
B-Fortis
CC-Prime S01
– S08
Relative humidity
max. 85%, non-condensing
Transport and storage
Operating temperature
–20°C to +70°C
Relative humidity
max. 85%, non-condensing
Shock resistance
Vibration
sinusoidal (EN 60068-2-6) test: Fc 10 ... 150 Hz, 10 m/s²
Shock
15 G (approx. 150 m/s²), 11 ms duration, sinusoidal half-wave
(EN 60068-2-27) ; test: Ea
EMC
Emitted interference
EN 55011 group 1 class B
Resistance to interference
EN 61131-2; EN 61000-6-2, industrial areas
Protection class
III
Insulation resistance
SELV (Ue < 30 V) acc. to EN 61131-2
Protection rating
IP20
Power supply (24 V power)
Supply voltage
+24 V DC (
–20% / +25%) SELV max. Alternating current
proportion 5%
Power consumption
typ. 0.3 A, max. 1 A at +24 V DC (L+ - internal power supply),
Supply DI/O (L1+…L4+) max. 2 A per group
Protection against reverse
polarity
yes
Potential isolation
no
Voltage failure switching
10 ms at < 20.4 VDC
Power Fail < 19.2 VDC
Communication interfaces
Ethernet interfaces
1x 10/100 Base T or 3x 10/100 Base T via switch, RJ45
EtherCAT interfaces
1x EtherCAT via 2
nd
Ethernet interface, RJ45
CAN-interface
1 x CAN (optoisolated), RJ45, Finish adjustable
USB interface
1x Host USB Rev. 2.0, max 1000 Mating cycles
Connection system
RJ45 (max. 1-3)
Serial interfaces
No. / type of interfaces
1x RS 232 / RJ45; 2 x RS 485 / RJ45;
assignment according to Modbus specifications