background image

09.10.03

Operating Instructions

SIOC03_GB

Serial Input/Output Converter SIOC03

9

These handshaking connections are present for software or hardware that requires full
handshaking. Use of BERGES software on most computers does not require the full hand-
shaking, and operation may be accomplished by proper connection of only the GND, RTS,
TxD and RxD signals.

Transmission of data is enabled by raising the RTS signal prior to sending data on the TxD
line. The transmitter is enabled with 20 microseconds of the RTS assertion.

6

Troubleshooting

6.1

Introduction

This chapter provides information on using the LEDs incorporated into the design of the
SIOC03 as troubleshooting aids.

6.2

Troubleshooting Tips

Table presents a guide for troubleshooting a system based on the status LEDs in the sys-
tem. The location of these LEDs, and their function, is shown in figure 1 and 5.

Symptom

Possible Cause

Potential Solution

PWR LED not 
lit

Correct power supply 
voltage is not 
present.

Check that the power supply is connected, and that 
it is working correctly. Check for excessive load on 
the power supply. Check that the power supply se-
lection jumper in the SIOC2 is set correct for the 
voltage being applied.

TE LED not lit 
during transmit

TE command not giv-
en in source code.

Check that the TE command is being sent by the 
host.

TxD never 
comes on

No signal on the 
transmit line.

Check the RS232 connections (9 pin “D” shell con-
nector). Assure that the host is putting information 
onto the transmit bus, and that the signal is reach-
ing the module.

RxD never 
comes on

No signal on the re-
ceive line.

Check the RS485 connections to J2 and the devic-
es connected to the bus.

Table 5

Troubleshooting Hints

Figure 5

Location of Status LEDs

Содержание SIOC03

Страница 1: ...Operating Instructions Serial Input Output Converter SIOC03 ...

Страница 2: ......

Страница 3: ...ons for Control Wiring 3 3 2 3 RS232 Communication Cable 3 3 3 Terminals Found on the SIOC03 3 3 3 1 Power Supply Connections 4 3 3 2 RS233 Input Connections 5 3 3 3 RS485 Output Connections 5 4 Configuration 6 4 1 Introduction 6 4 2 Gaining Access to the Configuration Jumpers 6 4 3 Power Supply Selection 6 4 4 Echoing 7 4 5 RS232 RS485 Transmit Enable 7 4 6 Biasing an RS 485 Network 8 5 Operation...

Страница 4: ...nts Report any shipping damage to your nearest BERGES representative 2 2 Product Features Specifications Power supply requirements 5 VDC or 12 24 VDC 50 mA Module input RS232 for PC or PLC 9 pin D shell female Module output RS485 half duplex to terminal block Maximum baud rate 110 k bits per second bps Signal Isolation Optical 1 000 volts Rectified power supply input Power supply polarity makes no...

Страница 5: ...is low voltage wiring as follows 1 Shielded wire is recommended to prevent electrical noise interference from causing im proper operation or nuisance tripping Connect the shield as recommended by the equipment manufacturer 2 Twisted pairs are recommended The SIO and SIO conductors should be twisted to gether If a twisted pair is used for the power supply connection the positive voltage and common ...

Страница 6: ...lies can also be used and are connected in the same manner The power supply requirement can also be met using a power supply adapter such as BERGES part number PA24DC Such a device must be capable of supplying 24 VDC and capable of supplying 50 mA of current Power from these devices can be connected to the J12 connector of the SIOC03 module See figure 1 for the location of this connector Terminal ...

Страница 7: ...n information for such an adapter The length of the input cable assembly can be extended To do this requires a straight through cable assembly i e pin 1 connects to pin 1 pin 2 to pin 2 etc Mouse extension cables may not perform correctly To assure reliability always keep the length of this con nection as short as possible with an absolute maximum of 25 feet The cable should be kept clear of any p...

Страница 8: ...f 6 in lb or damage may result to the enclosure 4 3 Power Supply Selection Jumper J16 configures the SIOC03 module to supply current from the PWR connection on jumper J2 This setting should only be used when connecting the SIOC03 to BERGES En hanced Keypad Note that having the jumper configured to EKP with another product may cause damage to that product or the SIOC03 The default setting for this ...

Страница 9: ...ansmit enable TE or to have an automatic transmit enable based on the state of the Txd line AUTO The default setting for this jumper is AUTO Refer to table 4 for the possible connections for this jumper Figure 4 provides the location of the jumper Jumper J9 Selection 1 2 Echo On 2 3 Echo Off Table 3 Echo Configuration Figure 4 SIOC03 Component Location Diagram Jumper J17 Label Selection 1 2 TE Tra...

Страница 10: ... 2 wire RS485 multi drop connection designed primarily for use with the BERGES inverter products All drives on the common RS485 bus must have their circuit commons COM or CM terminal connected The optical isolation of the SIOC03 provides an isolation barrier between the drives and the communication host This isolation allows baud rates of up to 110 kHz When jumper J17 is configured to AUTO the tra...

Страница 11: ...ased on the status LEDs in the sys tem The location of these LEDs and their function is shown in figure 1 and 5 Symptom Possible Cause Potential Solution PWR LED not lit Correct power supply voltage is not present Check that the power supply is connected and that it is working correctly Check for excessive load on the power supply Check that the power supply se lection jumper in the SIOC2 is set c...

Страница 12: ...ntact our Application Engineers can be reached at 49 2264 17 158 or 49 2264 17 160 7 Appendix 7 1 RS232 Connection Details Pin Number Signal Name 1 DCD 2 RxD 3 TxD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 9 9 Pin D Shell Connections SIOC03 and Host 25 Pin D Shell Host 9 Pin RS232 SIOC03 Signal Name 2 3 TxD 3 2 RxD 4 7 RTS 5 8 CTS 6 6 DSR 7 5 GND 8 1 DCD 20 4 DTR 9 Pin to 25 Pin Serial Port Connections ...

Страница 13: ......

Страница 14: ...BERGES electronic GmbH Industriestraße 13 D 51709 Marienheide Rodt Postfach 1140 D 51703 Marienheide Tel 0 22 64 17 0 Fax 0 22 64 1 71 26 http www berges de e mail Info_BEL berges de ...

Отзывы: