BERG SF58V Скачать руководство пользователя страница 10

Service and Installation Manual

10

d11

Defrost type

0:Electric heating defrost

1:Hot gas defrost

0

0

/

F1

Fan running mode

0:Fan and compressor run or stop

synchronically

1:Fan

runs continuously, stops during

defrost

2: Fan runs continuously, stops

during defrost and defrost dripping

3: Fan runs continuously, stops

during defrost, fan time delay after

defrost

4:Controlled by defrost sensor, fan

stops during defrost.

1

1

/

F2

Fan initial start time delay after

electrified

0

60

0

0

min

F3

Fan start time delay after defrost

0

60 , 0: Fan time delay canceled

2

2

min

F4

Fan working lowest temp.

-50

℃~

Fan working highest temp.

-58

-58

/

-58

℉~

Fan working highest temp.

F5

Fan working highest temp.

Fan working lowest temp.

85

185

185

/

Fan working lowest temp.

185

A1

Compressor run and stop in a

proportional time after cabinet sensor

failure

0: Cancel the mode of “Run/stop in a

proportional time”

1: Start the mode of “Run/stop in a

proportional time”

1

1

/

A2

Compressor stop time in the mode of

“Run/stop in a proportional time”

1

60

5

5

min

A3

Compressor running time in the mode

of “Run/stop in a proportional time”

1

60

30

30

min

A4

Buzzer alarm output switch

0: Buzzer output disabled

1: Buzzer output enabled

1

1

/

A5

Cabinet temperature lower limit alarm

value

-50

Cabinet temperature upper

limit alarm value

-58

-58

/

-58

Cabinet temperature upper

limit alarm value

A6

Cabinet temperature upper limit alarm

value

Cabinet temperature lower limit

alarm value

85

185

185

/

Cabinet temperature lower limit

alarm value

185

A7

Cabinet over temperature alarm time

delay

0

60

20

20

3min

A8

The initial cabinet over temperature

alarm time delay after electrified

0

60

40

40

3min

A9

Over temperature alarm upper

deviation

1

℃~

30

10

10

/

1

℉~

60

A10

Over temperature alarm lower

deviation

1

℃~

30

5

5

/

1

℉~

60

A11

Over temperature alarm mode

0: Absolute temperature point

1:set value+ over temperature alarm

deviation

0

0

/

A12

Light/Alarm relay selection

0:Light output

1:Alarm output

0

0

/

Содержание SF58V

Страница 1: ...e Installation and Care Manual Please read this manual completely before attempting to install or operate this equipment Notify carrier of damage Inspect all components immediately See page 2 SR58V SF...

Страница 2: ...ding so the equipment is not damaged while being moved into the building 1 Visually inspect the exterior of the package and skid or container Any damage should be noted and reported to the delivering...

Страница 3: ...allationManual 3 SPECIFICATION MODEL V Hz Ph AMPS STORAGE CAPACITY Cu ft HP BTU H CHARGE OZ SHIP WEIGHT LBS NEMA PLUG SR58V 115 60 1 3 2 17 55 1 8 888 4 4 254 5 15P SF58V 115 60 1 6 1 17 55 3 8 2167 3...

Страница 4: ...andle is packed and fixed on the shelf inside the cabinet after locating the cabinet take out the door handle and install it with cross screwdriver according to following instruction Inside cabinet Do...

Страница 5: ...and for mobility It is very important however that the cabinet be installed in a stable condition with the front wheels locked while in use Should it become necessary to lay the unit on its side or b...

Страница 6: ...during a defrost period and when door is open 1 Every 4 hours the unit will turn off and electric heater will turn on to start the defrost cycle The controller now displays the defrost symbol When the...

Страница 7: ...driver to remove the upper hinge axis in position 2 and screw it into the opposite side position 3 4 Use hexagon wrench to remove the hinge axis D from the door and the bottom hinge insert it into the...

Страница 8: ...panel 1 Indicator light status description Indicator light Symbol Status Meaning Setting Set ON Parameter setting OFF Status of temperature measuring and controlling Refrigeration ON Refrigeration wo...

Страница 9: ...Min running time 0 90 0 Refrigeration Min running time calculation is forbidden 0 0 min d1 Evaporator sensor selection 0 Disabled 1 Enabled 1 0 d2 Evaporator sensor calibration 10 0 10 0 0 0 20 20 d3...

Страница 10: ...l time 1 Start the mode of Run stop in a proportional time 1 1 A2 Compressor stop time in the mode of Run stop in a proportional time 1 60 5 5 min A3 Compressor running time in the mode of Run stop in...

Страница 11: ...selection note 00 Fahrenheit 01 Celsius 01 00 Note Only valid when the cabinet sensor is in proper working Note After switch between Celsius Fahrenheit users need to adjust all related parameters them...

Страница 12: ...m the parameter setting by pressing it needs to input the correct password again for next parameter adjustment 2 Temperature viewing In the status of temperature measuring and controlling press to vie...

Страница 13: ...th dirty or clogged condenser coils can result in compressor failures Neglecting the condenser coil cleaning procedures will void any warranties associated with the compressor or cost to replace the c...

Страница 14: ...inside the unit which removes the condensation from the evaporator coil and evaporates it into an external condensate evaporator pan Each drain can become loose or disconnected from moving or bumping...

Страница 15: ...Service and InstallationManual 15 WIRING DIAGRAM MODEL SR58V MODEL SF58V...

Страница 16: ...16 WIRING DIAGRAM MODEL SR58V...

Страница 17: ...Service and InstallationManual 17 WIRING DIAGRAM MODEL SF58V...

Страница 18: ...UR YEAR COMPRESSOR PART WARRANTY Berg Refrigeration warrants its hermetically and semi hermetically sealed compressor to be free from defects in both material and workmanship under normal use and serv...

Страница 19: ...anties and should not be relied upon THE BUYER S REMEDY AGAINST BERG REFRIGERATION FOR THE BREACH OF ANY OBLIGATION ARISING OUT OF THE SALE OF BERG REFRIGERATION WHETHER DERIVED FROM WARRANTY OR OTHER...

Страница 20: ...20...

Отзывы: