d11
Defrost type
0:Electric heating defrost
1:Hot gas defrost
0
0
/
F1
Fan running mode
0:Fan and compressor run or stop
synchronically
1:Fan
runs continuously, stops during
defrost
2: Fan runs continuously, stops
during defrost and defrost dripping
3: Fan runs continuously, stops
during defrost, fan time delay after
defrost
4:Controlled by defrost sensor, fan
stops during defrost.
1
1
/
F2
Fan initial start time delay after
electrified
0
~
60
0
0
min
F3
Fan start time delay after defrost
0
~
60 , 0: Fan time delay canceled
2
2
min
F4
Fan working lowest temp.
-50
℃~
Fan working highest temp.
-58
℉
-58
℉
℃
/
℉
-58
℉~
Fan working highest temp.
F5
Fan working highest temp.
Fan working lowest temp.
~
85
℃
185
℉
185
℉
℃
/
℉
Fan working lowest temp.
~
185
℉
A1
Compressor run and stop in a
proportional time after cabinet sensor
failure
0: Cancel the mode of “Run/stop in a
proportional time”
1: Start the mode of “Run/stop in a
proportional time”
1
1
/
A2
Compressor stop time in the mode of
“Run/stop in a proportional time”
1
~
60
5
5
min
A3
Compressor running time in the mode
of “Run/stop in a proportional time”
1
~
60
30
30
min
A4
Buzzer alarm output switch
0: Buzzer output disabled
1: Buzzer output enabled
1
1
/
A5
Cabinet temperature lower limit alarm
value
-50
℃
~
Cabinet temperature upper
limit alarm value
-58
℉
-58
℉
℃
/
℉
-58
℉
~
Cabinet temperature upper
limit alarm value
A6
Cabinet temperature upper limit alarm
value
Cabinet temperature lower limit
alarm value
~
85
℃
185
℉
185
℉
℃
/
℉
Cabinet temperature lower limit
alarm value
~
185
℉
A7
Cabinet over temperature alarm time
delay
0
~
60
20
20
3min
A8
The initial cabinet over temperature
alarm time delay after electrified
0
~
60
40
40
3min
A9
Over temperature alarm upper
deviation
1
℃~
30
℃
10
℃
10
℃
℃
/
℉
1
℉~
60
℉
A10
Over temperature alarm lower
deviation
1
℃~
30
℃
5
℃
5
℃
℃
/
℉
1
℉~
60
℉
A11
Over temperature alarm mode
0: Absolute temperature point
1:set value+ over temperature alarm
deviation
0
0
/
A12
Light/Alarm relay selection
0:Light output
1:Alarm output
0
0
/