INSTALLATION

13

Do not fill the system in bright, sunny conditions or if 

the collectors are hot. Cover the solar collector with 

the packaging it came in for at least two hours before 

filling it.

Make sure that you have bled all the air out of the sys-

tem, using the water control system vent too.

Heat transfer fluid filling pump (accessory). A manual 

bleed valve is not required if this pump is used.

Checks

On completion of the installation, perform the checks listed in the table below.

CHECKS

Collector circuit

Cold circuit pressure:____bar (see table 

above)

Collector circuit seal test

Safety valve check

Anti-freeze checked to - ___ °C

pH of heat transfer fluid = ____

Collector circuit bled

Flow rate of 30 l/h per m

2

 checked

Non-return valve functioning

Solar collectors

Visual check of collectors

Collectors cleaned if necessary

Visual check of collector fixing points

Visual check of roof impermeability

Visual check of insulation/lagging

Содержание SCV-25

Страница 1: ...Installation Manual Solar Solar collector SCV 25 Installation Manual EN...

Страница 2: ...e used in this manual b CAUTION Identifies actions that require caution and adequate preparation a STOP Identifies actions that you MUST NOT do This manual Code Rev comprises pages GENERAL INFORMATION...

Страница 3: ...et P2 H2 L1 L2 H1 L3 Seal Insulation Bottom pipe Glass Vacuum Absorbent coating Collector foot Support frame Direction of flow Evacuated tube Aluminium absorber Top cover plat Top pipe Reflective mirr...

Страница 4: ...IMENSIONI 2046X1187X90 mm SUPERFICIE LORDA 2 43 m2 TEMPERATURA DI STAGNAZIONE 201 C SUPERFICIE DI APERTURA 2 20 m2 CONTENUTO LIQUIDO 1 6 l SUPERFICIE ASSORBITORE 2 15 m2 PESO A VUOTO 36 5 kg LIQUIDO T...

Страница 5: ...010 0 011 W m2 K2 Description U M IAM T 50 1 07 IAM L 50 0 954 Efficiency col 64 Tested according to EN 12975 referred to a 33 3 water glycol mix flow rate of 170 l h and irradiation G 800W m2 Tm Col...

Страница 6: ...nd Altitude m a s l Total load on roof from wind and snow loads and collector weight kg At angle of 45 At angle of 20 At angle of 45 At angle of 20 SCV 25 0 10 low 60 40 100 424 546 10 20 low 80 50 25...

Страница 7: ...nut ring nut union olive olive ring nut union olive olive ring nut stub pipe stub pipe stub pipe Collectors in the same line must be connected so that the heat transfer fluid flows through them in se...

Страница 8: ...k 16 Manual bleed valve accessory 17 Storage cylinder bottom temperature sensor 18 Storage cylinder top temperature sensor 19 Heat transfer fluid recovery M Collector outlet R Collector return b Conne...

Страница 9: ...r 700 800 900 600 500 400 300 200 100 0 0 500 1000 1500 2000 2500 3000 FLOW RATE l h Diameter of connection pipes for a specific flow rate of 30 lt m2 h Total surface area m2 2 4 6 12 14 20 Diameter o...

Страница 10: ...n integral part of the so lar connector Once located read it thoroughly and keep it safe A B Handling Once you have removed the outer packaging proceed as follows to unpack and handle the solar collec...

Страница 11: ...in con formity to relevant standards Lagging and insulation must be protected against damage by the weather and birds and animals Angle of collectors General Solar collectors are designed to be insta...

Страница 12: ...because the liquid becomes darker FILLING THE CIRCUIT 2 FILLING 1 Open the non return valve A 2 Open the air vent at the highest point in the system see figure alongside and keep it open throughout th...

Страница 13: ...required if this pump is used Checks On completion of the installation perform the checks listed in the table below CHECKS Collector circuit Cold circuit pressure ____bar see table above Collector cir...

Страница 14: ...e tube 3 downwards twisting it gently to re lease it from the top seal Remove the tube from the bottom of the collector If you do not have sufficient room to remove the tube down wards proceed as foll...

Страница 15: ...fault e g a large dent is found they can be replaced quickly and easily Proceed as follows taking all the necessary precautions to remove a damaged reflector Unscrew and remove the plug 1 from the fo...

Страница 16: ...23 A 23900 Lecco LC www berettaboilers com The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore...

Отзывы: