3.8
Flue gas vent and air intake
Flues and stack connections must be made in
conformity to all applicable local and national
laws and standards. The use of rigid pipes is
mandatory.
All joints between pipe sections must be her-
metically sealed and all parts of the flue must
be resistant to high temperatures, condensate
and mechanical stress.
b
Novella
boilers are equipped with a flue
gas thermostat, located inside the hood.
This thermostat shuts down the boi-
ler immediately in the event of flue gas
blowback.
b
Uninsulated flue pipes are potentially
dangerous and can cause burns.
The back draught shutter supplied with
Novella
boilers must be fitted correctly along
with the flue gas thermostat. To do so, pro-
ceed as follows.
- Fit the collar (C) to the flue gas exhaust hole
in the top panel of the casing (fig. 3.13)
- Push the back draught shutter (B) through
the collar (C) and into its seat in the flue gas
hood (fig. 3.13)
- Insert the flue gas thermostat (S) (attached
to the back of the boiler), into the socket in
the back draught shutter and fix it in place
with the nut (fig. 3.14).
A
225
225
Øi
B
C
S
Fig. 3.12
Fig. 3.13
Fig. 3.14
DESCRIPTION
MODEL
55 RAI
64 RAI
71 RAI
A
260
302
342
mm
Ø
I
182
182
202
mm