79
Installation
6005770_a – 07.04.2021
EN
3.
Installation
3.1
Safety information for installation
D
WARNING!
Hazard through disregard of the installation instructions!
This chapter contains important information for the safe
installation of the device.
☞
Read through this chapter carefully before installing the
device.
☞
Follow the safety instructions.
☞
Carry out the installation as described.
y
Installation only by qualified specialist personnel.
D
“1.2 Authorised target groups” (page 76).
y
Electrical work only to be undertaken by qualified
electricians.
D
“1.2 Authorised target groups” (page 76).
y
When working at heights, ensure good stable footing
(e.g. stable stepladder).
y
Store the film or other parts of the packaging in a location
which is inaccessible to children.
y
The device must be in an undamaged and fault-free
condition prior to installation.
y
Cables must not be kinked, crushed or damaged.
y
It is not permissible to attach further components
(e.g. panels, air ducts) to the device.
y
The power supply voltage must match the voltage
information quoted on the ratings plate.
D
“2.4 Technical data” (page 78).
y
Ensure that the power supply is stable and remains so
prior to the installation.
Connect the power supply only when instructed to do so
in the installation instructions.
3.2
Requirements for the installation location
D
WARNING!
Risk of death due to improper installation!
Disregard of the ambient conditions can lead to hazardous
situations, e.g. in the handling of electrical power or gas.
☞
Make sure that the requirements for the installation
location are complied with.
y
Do not install in potentially explosive atmospheres.
y
In extracted air mode and whilst using a heating point
which uses air from the room as its oxygen supply (e.g.
chimney):
y
A safety device is absolutely essential.
y
The safety device must prevent gases being drawing
to the room.
y
It is essential to ensure that the negative pressure
in the heating point installation room does not
exceed 4 Pa.
y
An approval for commissioning (e.g. from a
chimneysweep) must be available.
y
Installation is only permitted on structural building
elements capable of bearing the load (solid structure).
y
Installation is only permitted on vertical outside walls.
y
Suitable fastening materials must be used if the outside
wall is insulated.
y
Make sure that the building electrical supply is properly
earthed.
y
The power supply voltage present must match the
voltage information quoted on the ratings plate.
y
Inside the building, there must be a max. distance of 1 m
between the device and a 230 V socket.
y
The air flowing out must be able to dissipate unimpeded.
Do not impede the air flow, e.g. through the installation of
objects on or above the device.
Country-specific, legal provisions must be observed.